SynC · SynC Standards
Access Control Systems
Rev4
IssuedAug 26, 2026
Contents
- 1Scope
- 1.4System Composition
- 1.5Coordination
- 1.6Exclusions
- 2Referenced Standards
- 3Submittals
- 3.1Action Submittals
- 3.2Informational Submittals
- 3.3Closeout Submittals
- 4Quality Assurance
- 4.1Installer Qualifications
- 4.2Single-Source Responsibility
- 4.3Listing and Labeling
- 5Environmental and Service Conditions
- 5.1Indoor and Exterior Equipment Ratings
- 5.2Sprinkler and Plenum Exposure
- 6System Architecture
- 6.7Controller Topology
- 6.8Equipment Location
- 7Door Controllers
- 7.6Reader-to-Controller Protocol
- 7.7Controller Inputs, Outputs, and Supervision
- 8Credential Readers
- 8.6Reader Mounting Height
- 8.7Exterior and Exposed Readers
- 8.8Two-Factor Authentication
- 9Credentials
- 9.8Federal Credential Interoperability
- 9.9Credential Quantity
- 10Electrified Door Hardware
- 10.3Default Lock Type
- 10.4Electromagnetic Locks
- 10.5Fail-Safe vs. Fail-Secure
- 10.6Lock State Monitoring
- 11Request to Exit
- 11.7Push-to-Exit Buttons
- 11.8REX Behavior at Door Position
- 12Door Position Switches
- 12.8Door Held-Open Time
- 12.9Forced-Open Alarm Routing
- 13Power Supplies and Battery Backup
- 13.3Lock Voltage
- 13.4Battery Backup
- 13.5Power Supply Location
- 14Cabling
- 14.11Voltage Drop and Separation
- 15Cybersecurity
- 15.2Network Segmentation
- 15.3Default Credentials and Initial Hardening
- 15.4Reader-to-Controller Encryption
- 15.5Audit Log Retention
- 16Fire Alarm Interface and Egress Release
- 16.9Delayed-Egress Openings
- 16.10Fire Alarm Interface Coordination
- 17Software (Head-End)
- 17.3Directory and SSO Integration
- 17.4Software Deployment
- 17.5Backup and Recovery
- 18User Management and Audit
- 18.3Access Privilege Assignment
- 18.4Time and Holiday Schedules
- 18.5Audit Log
- 19Testing and Commissioning
- 19.4Per-Opening Acceptance Test
- 19.5Correction and Report
- 20Installation
- 20.1Coordination and Sequencing
- 20.2Mounting
- 20.3Terminations
- 20.4Protection During Construction
- 21Training
- 22Delivery, Storage, and Handling
- 23Warranty
- 24Spare Parts
Download
Build a datasheet from this standard
Start a project with this standard already attached — one click, no setup.
Use in a project
1 Scope
NOTE This specification covers the design, equipment, installation, programming, and testing of an electronic access control system (ACS) for controlling pedestrian entry into and movement within a building. (1.1)
1.2 The system shall identify users by credential, validate their access privileges against a rule set maintained by a head-end software platform, and electrically operate door hardware to permit or deny passage at controlled openings.
1.3 The system shall additionally monitor door position and request-to-exit conditions, log every access event and exception, and interface with the building fire alarm system to release fail-safe locking devices on alarm.
1.4 System Composition
NOTE The access control system is a coordinated assembly of electronic head-end software, networked door controllers, credential readers, request-to-exit devices, door position switches, low-voltage power supplies, and the electrified door hardware that physically secures each opening. (1.4.1)
1.4.2 This standard governs the electronic head-end, the controllers, the reader-side devices, and the wiring; the electrified locking hardware itself — the electric strike, electromagnetic lock, electrified mortise lock, electrified cylindrical lock, or electric exit device — is procured and installed under Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware and shall be coordinated under this standard.
1.5 Coordination
NOTE Every controlled opening is a system requiring coordination across multiple trades and standards. (1.5.1)
1.5.2 The Contractor shall coordinate the access control scope with Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware for lock selection, frame and door preparation, and hardware-set finalization.
1.5.3 The Contractor shall coordinate with Fire Alarm SystemsFire Alarm SystemsResolves to the current adopted revision.sync/fire-alarm-systems for the release of fail-safe locks on fire alarm.
1.5.4 The Contractor shall coordinate with Conductors And CablesConductors and CablesResolves to the current adopted revision.sync/conductors-and-cables and Raceways And ConduitRaceways and ConduitResolves to the current adopted revision.sync/raceways-and-conduit for low-voltage pathways.
1.5.5 The Contractor shall coordinate with Grounding And BondingGrounding and Bonding for Electrical SystemsResolves to the current adopted revision.sync/grounding-and-bonding and Telecommunications BondingTelecommunications Bonding and GroundingResolves to the current adopted revision.sync/telecommunications-bonding for the bonding of the head-end and controller equipment.
1.5.6 The Contractor shall coordinate with Equipment LabelingElectrical Equipment LabelingResolves to the current adopted revision.sync/equipment-labeling for device and circuit identification.
1.6 Exclusions
NOTE This standard addresses electronic access control of swinging pedestrian doors using card, smart card, or mobile credentials. (1.6.1)
1.6.2 This standard does not cover video surveillance, intrusion detection alarms, intercom systems, parking and vehicle access control, automatic pedestrian door operators beyond the lock release interface, or biometric-only systems without a supporting card or mobile credential.
2 Referenced Standards
2.1 Where the contract documents, the adopted building code, or a referenced standard conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
2.2 Equipment, materials, software, and installation shall comply with the latest adopted edition of the following standards.
| Standard | Title |
|---|---|
| UL 294 | Access Control System Units |
| UL 1034 | Burglary-Resistant Electric Locking Mechanisms |
| UL 1076 | Proprietary Burglar Alarm Units and Systems |
| UL 1981 | Central Station Automation Systems |
| UL 10C | Positive Pressure Fire Tests of Door Assemblies |
| UL 10B | Fire Tests of Door Assemblies |
| NFPA 101 | Life Safety Code (egress at access-controlled openings) |
| NFPA 80 | Standard for Fire Doors and Other Opening Protectives |
| NFPA 72 | National Fire Alarm and Signaling Code (interface to ACS) |
| NFPA 70 | National Electrical Code (Articles 725 and 760) |
| IBC Chapter 10 | International Building Code — Means of Egress |
| IFC Chapter 10 | International Fire Code — Means of Egress |
| ICC A117.1 | Accessible and Usable Buildings and Facilities |
| ADA Standards for Accessible Design | Federal accessibility requirements |
| ANSI/SIA AC-01 | Access Control General Requirements |
| SIA OSDP v2.2 | Open Supervised Device Protocol |
| ANSI/BICSI 008 | Wireless LAN Best Practices for Cabling Installation |
| ANSI/TIA-568 | Generic Telecommunications Cabling for Customer Premises |
| ANSI/TIA-569 | Telecommunications Pathways and Spaces |
| ANSI/TIA-606 | Administration Standard for Telecommunications Infrastructure |
| ANSI/TIA-607 | Generic Telecommunications Bonding and Grounding |
| FIPS 201 | Personal Identity Verification (where federal credential interoperability applies) |
| NIST SP 800-116 | Use of PIV Credentials in Facility Access |
| ISO/IEC 14443 | Identification cards — Contactless integrated circuit cards (proximity) |
| ISO/IEC 7816 | Identification cards — Integrated circuit cards |
3 Submittals
3.1 Action Submittals
3.1.1 The Contractor shall submit the following to the Engineer of Record for review prior to procurement and prior to beginning installation:
- Manufacturer's product data for the head-end server platform, every door controller and panel, every reader, every credential type, every power supply, every request-to-exit device, every door position switch, every input/output module, and every accessory item
- A system riser diagram showing the head-end server, network switches and segmentation, every controller panel, every reader, every electrified door hardware connection, every REX and DPS input, every power supply with backup battery, and the interface to the fire alarm system
- A door schedule listing every controlled opening by mark number, cross-referenced to the door schedule in Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware, indicating reader type and quantity per opening, electrified hardware type (free-egress vs access-controlled vs delayed egress), fail-safe or fail-secure operation, REX device type, DPS configuration, power supply assignment, and controller and reader address
- A panel schedule for each controller cabinet listing every door served, the assigned reader address, the assigned input/output points, the panel power budget, and the upstream and downstream power supply
- A head-end architecture diagram showing the server, redundancy or high-availability arrangement, database storage, backup strategy, network segmentation, directory and SSO integration, and any cloud or remote connectivity
- A sequence-of-operations matrix listing each input (valid credential, invalid credential, REX, DPS open, DPS forced-open, DPS held-open, fire alarm, tamper) and the resulting outputs (unlock, lock, alarm, audit log, notification) for each door type
- Battery calculations for every UL 294 listed power supply showing standby and alarm current draw, required standby duration, and selected battery amp-hour capacity
- OSDP configuration documentation including baud rate, Secure Channel keys management, polling intervals, and address assignments
- Cybersecurity hardening documentation including the cipher suite, certificate management plan, default-credential change procedure, firmware version baseline, and network segmentation approach
Action Submittals Requiredcheckbox
☑ Product data for head-end, controllers, readers, credentials, power supplies, REX, DPS, modules
☑ System riser diagram
☑ Door schedule cross-referenced to door, frame, and hardware schedule
☑ Controller panel schedules with point assignments
☑ Head-end architecture diagram
☑ Sequence-of-operations matrix
☑ Battery calculations for each power supply
☑ OSDP configuration documentation
☑ Cybersecurity hardening plan
3.1.2 The access control submittal is a complete system-level package; partial or piecemeal submittals shall be returned without review.
3.2 Informational Submittals
3.2.1 The Contractor shall submit the following informational items:
- Manufacturer's installation instructions for each component, retained on site during installation
- Installer qualifications documentation, including factory training certificates for the specific controller platform
- Proposed acceptance test plan including test procedures, schedule, personnel, and forms
Informational Submittals Requiredcheckbox
☑ Manufacturer's installation instructions retained on site
☑ Installer qualifications and factory training certificates
☑ Proposed acceptance test plan with procedures, schedule, personnel, and forms
3.3 Closeout Submittals
3.3.1 At substantial completion, prior to system acceptance, the Contractor shall submit:
- Accepted acceptance test report signed by the Contractor and the testing technician
- As-built system drawings reflecting final device addresses, controller programming, and circuit routing
- Complete head-end programming record: user roles, access levels, time schedules, door groups, holiday schedules, and event-to-action mappings
- A keyholder turnover package: head-end administrator account credentials, encryption key custody record, recovery procedures, and an inventory of issued credentials at substantial completion
- Operation and maintenance manual including normal operations, lockdown procedures, after-hours access procedures, credential enrollment and revocation, backup and restore, battery replacement schedule, and firmware update procedure
- Warranty documentation
- Manufacturer service contact list and any service-agreement terms
Closeout Submittals Requiredcheckbox
☑ Accepted acceptance test report
☑ As-built system drawings with final addresses
☑ Head-end programming record
☑ Administrator credentials and encryption key turnover package
☑ Operation and maintenance manual
☑ Warranty documentation
☑ Manufacturer service contact list
4 Quality Assurance
4.1 Installer Qualifications
4.1.1 The access control system shall be installed by a contractor regularly engaged in the design and installation of electronic access control systems with documented experience on at least three projects of comparable size and complexity within the past five years.
4.1.2 The factory certification held by the installer-in-charge shall be as indicated in the datasheet.
Installer Factory Certificationradio
● Required for the specific controller platform
○ Required for the controller platform and the head-end software
○ Not required (qualification by documented project experience)
4.1.3 The installer-in-charge shall be present on site during programming, head-end configuration, and acceptance testing.
4.1.4 Personnel making low-voltage terminations at controllers and readers shall be trained in the manufacturer's wiring methods, in OSDP Secure Channel commissioning, and in the project's cybersecurity hardening procedures.
4.1.5 Cabling between controllers, readers, and head-end equipment shall be installed by personnel meeting the qualifications of Conductors And CablesConductors and CablesResolves to the current adopted revision.sync/conductors-and-cables for low-voltage and structured cabling.
4.2 Single-Source Responsibility
4.2.1 The head-end software, door controllers, reader-to-controller protocol stack, and panel-level firmware shall be furnished by a single manufacturer or by a tightly integrated ecosystem of manufacturers documented to interoperate.
4.2.2 Multi-source assemblies in which the controller, the head-end, and the readers are sourced independently and integrated only at the field level shall not be acceptable unless the Engineer specifically approves the integration after review of interoperability test documentation.
4.2.3 Credentials and readers, where sourced from a different manufacturer than the controller, shall be confirmed compatible through OSDP v2.2 Secure Channel testing prior to procurement of credentials in quantity.
4.3 Listing and Labeling
4.3.1 The fire alarm interface point — the relay or supervised input that releases fail-safe locks on fire alarm — shall be UL 864 listed where it forms part of the fire alarm system or shall use a UL 294 listed module driven by a UL 864 listed dry contact from the fire alarm control unit.
4.3.2 All access control system units shall be listed and labeled to UL 294 by a Nationally Recognized Testing Laboratory.
4.3.3 Power supplies shall be UL 294 listed for access control service.
4.3.4 Electrified locking hardware listed to UL 1034 shall be used where the opening is required to resist burglary; the listing requirements for the hardware itself are addressed in Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware and shall be coordinated.
5 Environmental and Service Conditions
5.1 Indoor and Exterior Equipment Ratings
5.1.1 Access control equipment installed in indoor, conditioned, occupiable spaces shall be rated for 0°C to 50°C ambient operating temperature and 0 to 85 percent non-condensing humidity.
5.1.2 Equipment installed in unconditioned spaces, electrical rooms, attics, or telecommunications rooms shall be confirmed against the extreme conditions of the space.
5.1.3 Readers installed at exterior openings shall be rated for the local exterior temperature extremes.
5.1.4 The enclosure rating of readers at exterior openings shall be as indicated in the datasheet.
Exterior Reader Enclosure Ratingselect
NEMA 3R (IP55)
NEMA 4 (IP65)
NEMA 4X (IP66)
5.1.5 Readers in corrosive, coastal, or wash-down environments shall be rated NEMA 4X.
5.2 Sprinkler and Plenum Exposure
5.2.1 Equipment installed in spaces with active sprinkler systems shall be located so that direct sprinkler discharge does not impinge on the equipment, or shall be enclosed against discharge.
5.2.2 Equipment installed in plenum spaces shall be plenum-rated or shall be installed in conduit per NEC Article 300.
6 System Architecture
6.1 The system architecture shall be as indicated in the datasheet.
System Architectureradio
● Networked, on-premises head-end
○ Networked, cloud-managed head-end
○ Hybrid (on-premises controllers, cloud-hosted management)
○ Standalone per door
6.2 The access control system shall comprise a head-end software platform, intermediate door controller panels distributed throughout the building, and reader-side devices at each controlled opening.
6.3 The head-end shall hold the system of record for users, credentials, and access privileges.
6.4 Controllers shall hold a cached copy of the rule set sufficient to make access decisions autonomously if the head-end network connection is interrupted.
6.5 Standalone, per-door, non-networked systems shall be used only on very small projects with a handful of openings and no requirement for centralized audit.
NOTE A networked, on-premises head-end is the default for projects of moderate or larger size, for facilities with confidentiality concerns about credential and audit data leaving the premises, and for facilities subject to regulatory or contractual data-residency requirements; cloud-managed and hybrid architectures are appropriate where the Owner accepts the operational benefits of reduced server administration and automatic updates in exchange for ongoing subscription cost and external data residency. (6.6)
6.7 Controller Topology
6.7.1 The controller topology shall be as indicated in the datasheet.
Controller Topologyradio
● Multi-door panel (reader panels in centralized cabinets)
○ Controller-per-door (edge controller adjacent to each opening)
○ Hybrid (centralized panels for grouped doors, edge controllers elsewhere)
6.7.2 The panel size serving each group of controlled openings shall be as indicated in the datasheet.
Centralized Panel Sizeselect
2-reader panel
4-reader panel
8-reader panel
16-reader panel
Per drawings — access control riser diagram (deferred by default)
NOTE Centralized multi-door panels in a secure equipment closet are the default topology for typical commercial buildings because they consolidate power supplies, simplify battery backup, ease maintenance, and produce a cleaner cabling architecture; controller-per-door edge devices are appropriate where opening density is low, where the cable run from a central panel is impractical, or where the Owner specifically prefers the topology for redundancy reasons. (6.7.3)
6.7.4 Panel sizing should leave spare capacity for at least 20 percent additional doors beyond initial installation, to accommodate future openings without panel replacement.
6.8 Equipment Location
6.8.1 The head-end server shall be located in as indicated on the contract documents.
6.8.2 Controllers shall be located in as indicated on the panel location plan in secure equipment closets or IT rooms with physical access restricted to authorized personnel.
7 Door Controllers
7.1 Door controllers (panels) shall be UL 294 listed devices providing autonomous access decision capability, supervised reader and input/output circuits, encrypted communication to the head-end, and a local cache of the rule set sufficient to operate during head-end outage.
7.2 The controller-to-head-end communication method shall be as indicated in the datasheet.
Controller-to-Head-End Communicationradio
● TCP/IP over Ethernet with TLS 1.2 or higher
○ TCP/IP over Ethernet with TLS 1.3
○ Wireless (802.11) with TLS 1.2 or higher
7.3 Controller-to-head-end communication shall be encrypted at TLS 1.2 or higher whichever transport is selected.
7.4 Wireless controller-to-head-end communication shall not be used except where a wired pathway is genuinely impractical.
NOTE Wireless controllers introduce reliability and security complications that outweigh the installation savings in nearly all projects. (7.5)
7.6 Reader-to-Controller Protocol
7.6.1 The reader-to-controller protocol shall be as indicated in the datasheet.
Reader-to-Controller Protocolradio
● OSDP v2.2 with Secure Channel
○ OSDP v2.1 with Secure Channel
○ Wiegand (existing legacy reader infrastructure)
7.6.2 New installations shall not use Wiegand except where the Owner has a legacy reader infrastructure that cannot be replaced in the project scope.
NOTE OSDP supersedes Wiegand by providing bidirectional, supervised, encrypted communication; reader status, tamper indication, and firmware updates over the reader cable; and resistance to the credential-replay and signal-injection attacks that have been demonstrated against Wiegand. (7.6.3)
7.7 Controller Inputs, Outputs, and Supervision
7.7.1 Each controller shall provide inputs for door position switch, request-to-exit, and tamper, and outputs for lock control.
7.7.2 The extent of circuit supervision shall be as indicated in the datasheet.
Input and Output Supervisionradio
● Required on all controller inputs and outputs
○ Required on inputs only
○ Not required (non-critical, low-security openings)
7.7.3 End-of-line resistors shall be installed per the manufacturer's instructions to enable line supervision; cut, shorted, or grounded reader and input wiring shall be detected and reported.
7.7.4 Controllers shall provide a tamper switch on the enclosure and shall report tamper conditions to the head-end.
7.7.5 Tamper events shall be logged and shall generate an operator notification.
8 Credential Readers
8.1 Readers shall be UL 294 listed and shall communicate to the controller over the reader-to-controller protocol indicated in the datasheet.
8.2 Readers shall be selected for the credential technology specified below.
8.3 The reader mounting method at each controlled opening shall be as indicated in the datasheet.
Reader Mountingradio
○ Surface mount on the door frame mullion or adjacent wall
○ Flush mount within the frame profile
○ Surface mount on a pedestal or bollard (parking and exterior gate openings)
Per drawings — access control door schedule (deferred by default)
8.4 The reader form factor shall be as indicated in the datasheet.
Reader Form Factorselect
Mullion (narrow profile for door frame mounting)
Wall switch, single-gang
Wall switch, mullion-width
Wall switch with integral keypad
NOTE A keypad-equipped reader is required at any opening where two-factor authentication is specified. (8.5)
8.6 Reader Mounting Height
8.6.1 The reader centerline height above finished floor shall be as indicated in the datasheet.
Reader Height (Centerline Above Finished Floor)range
in
3440424448
8.6.2 Reader height above finished floor shall comply with ADA and ICC A117.1 reach-range requirements.
8.6.3 The reader's active read zone shall be located between 34 inches and 48 inches above finished floor for unobstructed forward reach, and the reader shall be positioned within the accessible side reach range where applicable.
8.7 Exterior and Exposed Readers
8.7.1 Readers at exterior openings shall be rated for direct exposure to weather, ultraviolet light, and condensation.
8.7.2 Readers at openings subject to vehicle traffic, vandalism, or impact shall be protected by a guard, recessed in a wall, or selected with a vandal-resistant rating.
8.8 Two-Factor Authentication
8.8.1 The extent of two-factor authentication shall be as indicated in the datasheet.
Two-Factor Authenticationradio
● Not required (single-factor card or mobile credential)
○ Required at designated high-security openings (credential + PIN)
○ Required at all openings (credential + PIN)
8.8.2 Two-factor authentication shall not be specified for general circulation openings because it impairs throughput and frustrates users without providing meaningful security benefit at low-risk openings.
NOTE Two-factor authentication adds a PIN to the credential read for openings serving high-value or sensitive areas such as data centers, pharmaceutical storage, executive areas, and weapons storage. (8.8.3)
9 Credentials
9.1 The primary credential technology shall be as indicated in the datasheet.
Primary Credential Technologyradio
● 13.56 MHz contactless smart card, AES-128 mutual authentication (ISO/IEC 14443)
○ Mobile credential over Bluetooth Low Energy and NFC
○ Combined 13.56 MHz smart card and mobile credential
○ 125 kHz proximity (existing legacy credential population)
9.2 A smart card credential shall perform mutual authentication with the reader using AES-128 or stronger encryption with diversified, issuer-managed keys.
9.3 125 kHz proximity credentials shall not be used for new installations.
9.4 Where the Owner has an existing 125 kHz population, the migration plan to a contemporary credential shall be documented in the closeout package.
NOTE The 125 kHz proximity technology is trivially clonable, has no cryptographic protection, and is being phased out across the industry. (9.5)
9.6 Mobile credentials over Bluetooth Low Energy and NFC shall be supported where the Owner intends to issue credentials to smartphones in addition to or in place of physical cards.
NOTE Mobile credentials reduce credential reissue cost and accelerate enrollment and revocation, but require the Owner to operate a credential management process compatible with the user population's device ecosystem. (9.7)
9.8 Federal Credential Interoperability
9.8.1 Federal credential interoperability shall be as indicated in the datasheet.
Federal Credential Interoperability (FIPS 201 / PIV)radio
● Not required
○ Required — PIV credentials honored at designated openings
○ Required — PIV is the primary credential
9.8.2 Federal facilities and contractors handling federal information shall require FIPS 201 (PIV) credential interoperability per the applicable HSPD-12 mandate.
9.8.3 Where PIV is required, readers and head-end shall support the PIV authentication mechanisms specified in NIST SP 800-116.
9.9 Credential Quantity
9.9.1 The initial credential quantity furnished shall be as indicated in the datasheet.
Initial Credential Quantityrange
each
50100250500100025005000
9.9.2 Credential quantity at substantial completion shall be sufficient to enroll the initial occupant population plus a 25 percent overage for new hires, visitors, and replacements during the first year of operation.
9.9.3 The Owner shall provide the initial occupant population to the Contractor at submittal review.
10 Electrified Door Hardware
NOTE This section governs the access control system's interface to that hardware: the power supply, the lock control output from the controller, the supervision of the lock state, and the policy governing lock-type selection at each opening. (10.1)
10.2 The electrified locking device at each opening — electric strike, electromagnetic lock, electrified mortise lock, electrified cylindrical lock, or electric exit device — is procured and installed under Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware.
10.3 Default Lock Type
10.3.1 The project's default electrified locking device type shall be as indicated in the datasheet.
Default Electrified Locking Device Typeselect
Electric strike (fail-secure) on a standard mechanical lock
Electrified cylindrical or mortise lock (free-egress)
Electric exit device (free-egress)
Electromagnetic lock
NOTE An electrified cylindrical or mortise lock preserves free mechanical egress at all times because the egress-side lever operates the latch without any electrical action, which is why it is the baseline selection here. (10.3.2)
10.3.3 The lock shall secure the latch on the access side and shall release the access-side lever or trim on a valid credential or REX signal.
10.3.4 Where the locking device includes an egress-side lever, that lever shall always operate the latch mechanically.
10.4 Electromagnetic Locks
10.4.1 Electromagnetic locks (mag locks) shall be avoided where any other lock type is feasible.
10.4.2 Where the door, frame, or operational use case truly requires a mag lock — most commonly on glass-and-aluminum entrance doors with no available latch reinforcement, or on cross-corridor smoke doors — the installation shall comply with NFPA 101 7.2.1.6.2 (Access-Controlled Egress Doors), the AHJ shall accept the arrangement in advance, and the release scheme shall be documented in the sequence of operations.
NOTE Mag locks are inherently fail-safe and require ancillary release devices (REX motion sensor, push-to-exit button, fire alarm release) to comply with NFPA 101 egress requirements at all times; each ancillary device is a failure point and an enforcement point with the AHJ. (10.4.3)
10.5 Fail-Safe vs. Fail-Secure
10.5.1 Fail-safe or fail-secure operation at each controlled opening shall be as indicated in the datasheet.
Fail-Safe / Fail-Secure Operationradio
○ Fail-secure (locked on loss of power)
○ Fail-safe (unlocked on loss of power)
Per drawings — access control door schedule (deferred by default)
10.5.2 Fail-safe or fail-secure operation shall be determined for each opening by the means-of-egress analysis.
NOTE A stairwell discharge door that must release on a building power failure to permit exit is fail-safe; an office suite door that must stay secured on a power failure to protect its contents is fail-secure. (10.5.3)
10.5.4 The Engineer of Record shall make the fail-safe or fail-secure determination for each opening and shall record it on the access control door schedule.
10.6 Lock State Monitoring
10.6.1 Lock state monitoring shall be as indicated in the datasheet.
Lock State Monitoringradio
● Lock state monitored at the controller via supervised contact
○ Door position only (lock state not directly monitored)
NOTE Lock state monitoring is a supervised contact on the lock that confirms the lock is mechanically secured. (10.6.2)
NOTE Monitoring only door position (closed vs. open) does not detect a latch that has failed to engage or has been propped; lock state monitoring is the means by which the system detects a door that is closed but unlocked. (10.6.3)
11 Request to Exit
11.1 A request-to-exit (REX) device shall be provided at every controlled opening to indicate that an authorized egress is occurring and to suppress the door-forced-open alarm during egress.
11.2 REX devices shall be supervised by the controller.
11.3 The primary REX device shall be as indicated in the datasheet.
Primary REX Deviceradio
● Passive infrared (PIR) motion sensor over the door
○ Integrated REX switch in the lock or exit device
○ Wall-mounted push-to-exit button
○ Combination PIR and integrated lock REX
11.4 A PIR motion sensor shall be mounted directly above the door on the egress side and aimed at the floor immediately inside the opening.
11.5 Integrated lock REX (a switch in the exit device or lever) shall be used as a supplement where the hardware supports it.
NOTE A PIR sensor is the baseline because it triggers on actual egress traffic without requiring the user to take any action, and an integrated REX is a more deterministic indicator that the door is being operated for egress and complements the PIR. (11.6)
11.7 Push-to-Exit Buttons
11.7.1 Push-to-exit buttons shall not be used as the primary REX on access-controlled egress doors with free-egress hardware because they require a deliberate user action that adds nothing to a door that is already mechanically free to open.
11.7.2 Push-to-exit buttons shall be provided as the legally compliant egress release for mag-lock openings per NFPA 101 7.2.1.6.2, where they shall be wall-mounted, clearly identified, located within 40 to 48 inches above finished floor, and wired so that operation releases the mag lock for a minimum of 30 seconds independent of the access control system.
11.8 REX Behavior at Door Position
NOTE REX behavior is fully determined by the locking device selected — free-egress hardware needs only alarm suppression, while a mag lock has no mechanical bypass and must be electrically released — so it is stated here as a requirement rather than offered as a project selection. (11.8.1)
11.8.2 For free-egress hardware (electrified mortise, cylindrical, or exit device), REX shall suppress the forced-open alarm and shall not unlock the door.
11.8.3 For mag lock openings, REX or the push-to-exit button shall unlock the door.
12 Door Position Switches
12.1 A door position switch (DPS) shall be provided at every controlled opening to monitor whether the door is closed.
12.2 DPS contacts shall be supervised by the controller.
12.3 The controller shall report and log forced-open, held-open, and propped-open conditions.
12.4 The door position switch type shall be as indicated in the datasheet.
Door Position Switch Typeradio
● Concealed magnetic reed switch in the door frame
○ Surface-mounted magnetic switch
○ Door-mounted balanced magnetic switch
NOTE A concealed switch is installed in the head of the door frame with a matching magnet set in the top edge of the door. (12.5)
12.6 Surface-mounted switches shall be used only on retrofit projects where concealed installation is not practical.
12.7 Balanced magnetic switches shall be specified at high-security openings where defeat by an external magnet must be prevented.
12.8 Door Held-Open Time
NOTE The door held-open timer sets how long the door may remain open after a valid access before a held-open alarm is generated. (12.8.1)
12.8.2 The door held-open time shall be as indicated in the datasheet.
Door Held-Open Timerange
seconds
1530456090120
12.8.3 High-traffic openings or openings used for material movement may extend the timer with the Engineer's approval.
12.8.4 The held-open alarm shall be annunciated at the head-end, and at the door where a local annunciator is specified.
NOTE A 45-second baseline accommodates normal cart and accessibility usage. (12.8.5)
12.9 Forced-Open Alarm Routing
12.9.1 The routing of the forced-open alarm shall be as indicated in the datasheet.
Forced-Open Alarm Routingradio
● Head-end notification only
○ Head-end notification plus local annunciator at the door
○ Head-end notification plus security monitoring service
NOTE Routing to a local annunciator or to a monitoring service is an Owner security-program decision; head-end notification alone is the baseline because the head-end is the system of record for every access event. (12.9.2)
13 Power Supplies and Battery Backup
13.1 Power supplies serving access control equipment shall be UL 294 listed for access control service and shall be sized for the connected load with at least 25 percent spare capacity for future additions.
13.2 Power supplies shall provide regulated DC output, output supervision, AC fail and low-battery monitoring, and integral battery charging.
13.3 Lock Voltage
13.3.1 The lock control voltage shall be as indicated in the datasheet.
Lock Voltageradio
● 24 VDC
○ 12 VDC
13.3.2 12 VDC shall be used only where the voltage drop calculation confirms adequate voltage at the lock under worst-case current.
NOTE 24 VDC is the baseline because the higher voltage reduces conductor sizing and tolerates longer runs without unacceptable voltage drop. (13.3.3)
13.3.4 The reader and controller logic voltage shall be as indicated in the datasheet.
Reader and Controller Logic Voltageradio
● 12 VDC from the controller-integrated supply
○ Power over Ethernet (PoE / PoE+)
○ Separate 24 VDC supply for readers
13.3.5 Power over Ethernet shall be used only where both the reader and the controller are listed for it.
13.4 Battery Backup
13.4.1 The battery standby duration shall be as indicated in the datasheet.
Battery Standby Durationrange
hours
481224
13.4.2 Battery backup shall be provided at every power supply serving access control loads.
13.4.3 Battery capacity shall be sized to provide a minimum of 4 hours of standby operation at the system's quiescent load.
13.4.4 Where the access control system serves life-safety egress functions or is part of a security plan with regulatory standby requirements, the battery shall be sized for a longer duration as required by the applicable standard.
13.4.5 Battery calculations shall be performed for each power supply, documented in the submittals, and the calculations shall account for both quiescent and alarm-condition current draw, the temperature derate factor specified by the battery manufacturer, and a margin above the calculated requirement of at least 25 percent.
13.5 Power Supply Location
13.5.1 Power supply locations shall be coordinated to keep the lock-cable run between supply and lock within the voltage-drop calculation tolerance.
13.5.2 Power supplies shall be installed in lockable enclosures and shall be co-located with the door controller cabinet where practical.
14 Cabling
14.1 All access control system cabling shall comply with NEC Article 725 (Class 2 circuits) for low-voltage portions and with NEC Article 800 and ANSI/TIA-568 for structured cabling portions.
14.2 Plenum-rated cable shall be used in plenum spaces.
14.3 Cable in concealed spaces, cable trays, and accessible ceilings shall be supported per NEC and per the cable manufacturer's instructions; cable shall not be supported by ceiling tile grid or other building systems not intended for cable support.
NOTE A composite cable that bundles reader, lock, REX, and DPS conductors in a single jacket installs in one pull, reduces conduit fill, and simplifies door cabling, which is why it is the baseline reader-cable selection. (14.4)
14.5 Where the lock current exceeds the rating of the composite cable's lock conductors, a separate lock cable shall be pulled and the reader cable shall carry only reader, REX, and DPS conductors.
14.6 The controller-to-head-end cable shall be as indicated in the datasheet.
Controller-to-Head-End Cableselect
Category 6 UTP
Category 6A UTP
Multimode optical fiber
14.7 The reader cable shall be as indicated in the datasheet.
Reader Cable (Controller to Reader)select
Composite 22 AWG/6-conductor shielded with 18 AWG/4-conductor
22 AWG/6-conductor overall-shielded twisted pair
Category 6 UTP for OSDP
14.8 The lock cable shall be as indicated in the datasheet, sized by the voltage drop calculation required below.
Lock Cable (Power Supply to Lock)select
18 AWG/2-conductor
16 AWG/2-conductor
14 AWG/2-conductor
14.9 The REX and DPS cable shall be as indicated in the datasheet.
REX and DPS Cableradio
● 22 AWG/2-conductor shielded per device
○ 18 AWG/2-conductor shielded
14.10 Cable pathways shall be as indicated in the datasheet.
Cable Pathwayscheckbox
☑ Conduit (EMT) in unfinished spaces and where required by code
☐ Cable tray in accessible ceilings
☑ Bridle rings or J-hooks in accessible ceilings (per TIA-569)
☑ Plenum-rated cable in plenums per NEC Article 300
14.11 Voltage Drop and Separation
14.11.1 Voltage drop on lock cables shall be calculated for the worst-case (longest, highest-current) opening on each power supply and the cable size shall be selected so that the lock voltage at the lock under fault-clearing or maximum-inrush current remains within the manufacturer's operating range.
14.11.2 The voltage drop calculation shall be documented in the submittals.
14.11.3 Cable separation from higher-voltage power circuits shall be maintained per NEC Article 725 and per the cable manufacturer's instructions.
15 Cybersecurity
15.1 Access control systems shall be hardened against the categories of attack that have repeatedly compromised installed systems: default credentials, unencrypted reader-to-controller protocols, unpatched firmware, flat-network exposure, and weak credential technologies.
15.2 Network Segmentation
15.2.1 The network segmentation method shall be as indicated in the datasheet.
Network Segmentationradio
● Dedicated VLAN, isolated from general user and IT networks
○ Dedicated physical network
15.2.3 Firewall rules shall restrict the access control VLAN to the specific protocols and destinations required for operation and management.
15.2.4 Remote access to the head-end, where permitted, shall be through an authenticated VPN or a managed gateway provided by the head-end manufacturer.
15.3 Default Credentials and Initial Hardening
15.3.1 The Contractor shall perform the initial hardening steps indicated in the datasheet before the system is placed in service.
Default Credentials and Initial Hardeningcheckbox
☑ All factory default passwords on controllers, readers, and head-end changed before commissioning
☑ Administrator accounts use unique passwords meeting Owner's password policy
☑ Service and maintenance accounts use distinct credentials from administrators
☑ Unused services and ports on controllers disabled
☑ Firmware updated to current vendor-supported version at substantial completion
15.4 Reader-to-Controller Encryption
NOTE Reader-to-controller encryption is fully determined by the protocol selected under Reader-to-Controller Protocol, so it is stated here as a requirement rather than offered as a second selection. (15.4.1)
15.4.2 OSDP Secure Channel shall be enabled at commissioning using site-specific keys, not installation-mode default keys.
15.4.3 The key management procedure shall be documented and the key custody record turned over to the Owner at substantial completion.
15.5 Audit Log Retention
15.5.1 The audit log retention period shall be as indicated in the datasheet.
Audit Log Retentionrange
days
9036573018252555
15.5.2 The head-end shall retain access and exception event logs for not less than 365 days.
15.5.3 Logs shall be exportable in a documented format for review and for archiving to long-term storage.
16 Fire Alarm Interface and Egress Release
16.1 The access control system shall interface to the fire alarm system as required by NFPA 101 and the AHJ.
16.2 The fire alarm release interface shall be as indicated in the datasheet.
Fire Alarm Release Interfaceradio
● Hardwired dry contact from FACU to a dedicated release relay at each lock requiring release
○ Hardwired dry contact from FACU to the power supply serving all locks on that supply
16.3 The interface shall release locks that must be released on fire alarm and shall do so independently of the head-end and independently of the network.
16.4 Locks requiring release on fire alarm — most commonly electromagnetic locks and any electrified hardware on an opening covered by NFPA 101 7.2.1.6.1 (Access-Controlled Egress Doors) or 7.2.1.6.2 (Delayed Egress) — shall release via a hardwired dry contact from the fire alarm control unit (FACU).
16.5 The dry contact shall interrupt the lock power circuit through a UL 294 listed release relay or directly at the power supply.
16.6 The release shall not depend on the access control head-end, the network, or any software function.
16.7 Where a code analysis determines that a specific opening's electric strike or electrified lever lock must release on fire alarm, the release shall be implemented in the same hardwired manner as for mag locks.
NOTE Electric strikes and free-egress electrified lever locks generally do not require release on fire alarm because they preserve mechanical egress at all times. (16.8)
16.9 Delayed-Egress Openings
16.9.1 The use of delayed-egress hardware shall be as indicated in the datasheet.
Delayed-Egress Opening Configurationradio
● Not used
○ Used at designated openings
16.9.2 Delayed-egress hardware (NFPA 101 7.2.1.6.1) shall not be used unless the building occupancy specifically permits it (typically prohibited in Assembly and Educational occupancies), the AHJ has approved the arrangement, and the required signage, audible alarm, and 15-second (or 30-second where authorized) release time are configured per code.
16.9.3 Where delayed egress is used, the release on fire alarm shall be immediate and shall be hardwired from the FACU.
16.10 Fire Alarm Interface Coordination
16.10.1 The Contractor shall coordinate the fire alarm interface design with Fire Alarm SystemsFire Alarm SystemsResolves to the current adopted revision.sync/fire-alarm-systems and shall confirm the release scheme with the AHJ before installation.
16.10.2 Final acceptance of any opening with electrified locking hardware shall include a witnessed test of the fire alarm release.
17 Software (Head-End)
17.1 The head-end software shall be a manufacturer-supported product currently sold and maintained, with documented update and patch cycles.
17.2 The software shall provide user, credential, access privilege, time schedule, holiday schedule, door, area, and reader management; event logging and audit trail; reporting; system health monitoring and alarms; and an administrator interface with role-based access control over the administrator population.
17.3 Directory and SSO Integration
17.3.1 Administrator and operator accounts shall be authenticated through the Owner's directory or identity provider where one exists, so that administrator account lifecycle — provisioning, password rotation, and deprovisioning on departure — is managed centrally.
17.3.2 The administrator authentication method shall be as indicated in the datasheet.
Directory and SSO Integrationradio
● LDAP / Active Directory integration for administrator authentication
○ SAML 2.0 or OIDC for administrator authentication
○ Local administrator accounts (no directory or identity provider available)
17.3.3 A cloud-hosted head-end shall authenticate administrators through SAML 2.0 or OIDC unless local administrator accounts are indicated in the datasheet.
17.3.4 Where directory or identity provider integration is indicated in the datasheet, local administrator accounts shall be limited to a break-glass account for recovery from a directory outage.
17.4 Software Deployment
17.4.1 The head-end software deployment model shall be as indicated in the datasheet.
Software Deploymentradio
● On-premises server
○ Vendor-hosted cloud (SaaS)
○ Owner-hosted cloud (private cloud or Owner's IaaS)
17.4.2 The server operating system shall be one for which the head-end manufacturer publishes current support.
17.5 Backup and Recovery
17.5.1 The backup and recovery provisions shall be as indicated in the datasheet.
Backup and Recoverycheckbox
☑ Daily automated database backup
☑ Weekly off-site backup copy
☑ Documented recovery procedure tested at acceptance
☐ High-availability configuration with secondary head-end
17.5.2 A documented backup procedure shall be in place before substantial completion.
17.5.3 The recovery procedure shall be tested as part of acceptance: a restore from the latest backup to a separate environment shall be demonstrated to recover the full configuration, credential set, and audit log.
18 User Management and Audit
18.1 The system shall maintain a credential record for every user that includes at minimum the user's identifier, the credential type and serial, the issue and expiration date, the access privilege set assigned, and the status (active, suspended, revoked).
18.2 Credentials shall expire at the interval indicated in the datasheet and shall require an affirmative renewal action.
Credential Expiration Intervalselect
1 year
2 years
3 years
5 years
Indefinite (set per credential at issue)
18.3 Access Privilege Assignment
18.3.1 Access privilege assignment shall be by role (door group + time schedule) rather than by direct enumeration of doors.
18.3.2 A user assigned a role shall inherit the role's privileges, and a privilege change at the role shall propagate to every user with that role.
18.3.3 Direct per-user, per-door privilege assignment shall be permitted only where the user's required access does not match any defined role and the exception is documented.
18.4 Time and Holiday Schedules
18.4.1 The time schedules to be configured shall be as indicated in the datasheet.
Time Schedulescheckbox
☑ Business hours
☐ Extended weekday hours
☐ 24/7
☐ Weekend and off-hours
☐ Custom per role or per door
18.4.2 Holiday schedules shall be configured to override regular time schedules on dates designated by the Owner.
18.4.3 The holiday list shall be reviewed and updated annually by the Owner; the Contractor shall provide the procedure at substantial completion.
18.5 Audit Log
18.5.1 The audit log shall record every access attempt (granted and denied), every door state event (forced open, held open, restored), every administrator action (user added, privilege changed, credential issued or revoked, lockdown initiated), and every system event (controller online/offline, AC fail, low battery, tamper).
18.5.2 Each log entry shall include the timestamp, the originating device or operator, and the affected user or door where applicable.
19 Testing and Commissioning
19.1 Acceptance testing shall be performed by the Contractor, witnessed by the Engineer or the Owner's designated representative, and documented on the project test forms.
19.2 The acceptance test scope shall be as indicated in the datasheet.
Acceptance Test Scoperadio
● Every controlled opening tested individually
○ Sampling of representative openings as approved by the Engineer
19.3 Testing shall not begin until installation is complete and the system has operated under normal conditions for the burn-in period indicated in the datasheet.
Burn-In Period Before Acceptancerange
days
371430
19.4 Per-Opening Acceptance Test
19.4.1 For each controlled opening, the acceptance test shall verify the following:
- Valid credential read results in lock release, door opens freely, DPS reports open, REX (if motion-based) suppresses forced-open during egress, lock re-secures on door close
- Invalid credential is denied and logged with the reason
- Forced-open condition (door opened without valid credential or REX) generates an alarm at the head-end and logs the event
- Held-open condition generates an alarm at the configured timer and logs the event
- Tamper at the controller or reader is detected and logged
- Loss of head-end connectivity at the controller does not interrupt access decisions for credentials in the controller cache
- Fire alarm dry contact, when actuated, releases every lock required to release per the sequence of operations, within the time required by the AHJ
- Battery backup at each power supply maintains the system for the specified standby duration during a simulated AC failure
- OSDP Secure Channel is confirmed enabled on every reader and the installation-mode keys have been replaced
19.5 Correction and Report
19.5.1 Test failures shall be corrected and the affected items re-tested.
19.5.2 The acceptance test report shall record the test method, the result, and the corrective action for any failed item.
19.5.3 The Owner's representative shall sign the report at acceptance.
20 Installation
20.1 Coordination and Sequencing
20.1.1 Access control rough-in shall be coordinated with Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware so that frame preparations, hardware mortise cutouts, electric power transfer hinges or door loops, and lock body conduits are correctly sized and located before frames and doors are delivered to the site.
20.1.2 Cable rough-in shall be completed before finished ceilings are installed and before walls are closed.
20.1.3 Controller cabinet and power supply locations shall be confirmed against the head-end architecture drawing before equipment is mounted.
NOTE Late discovery of a missed frame preparation typically requires field cutting that compromises the fire rating, the finish, or the structural integrity of the frame. (20.1.4)
20.2 Mounting
20.2.1 Readers shall be mounted plumb and square, at the height specified above, and secured to a backbox or to the frame with the manufacturer's hardware.
20.2.2 Surface-mounted readers shall be installed with weatherstripping or a gasket at exterior openings to prevent water and pest intrusion.
20.2.3 Controllers and power supplies shall be wall-mounted in lockable enclosures in secure equipment closets.
20.2.4 Enclosure penetrations shall be made with listed cable connectors or grommets; conduit stubs into controller enclosures shall be sealed.
20.2.5 DPS magnets and contacts shall be aligned within the manufacturer's tolerance and shall be tested for actuation at the maximum gap before the frame is finished.
20.3 Terminations
20.3.1 Terminations at controllers, readers, and power supplies shall be made by personnel trained in the manufacturer's wiring methods.
20.3.2 Conductor jackets shall be stripped to the minimum length required and stranded conductors shall be terminated in approved ferrules or directly under screw terminals per the manufacturer's instructions; bare twisted strands shall not be terminated under screw terminals.
20.3.3 Shields on reader cables shall be terminated at the controller end only, with the shield grounded at a single point per the manufacturer's instructions.
NOTE Floating both ends or grounding both ends creates ground loops that introduce noise on the OSDP line. (20.3.4)
20.4 Protection During Construction
20.4.1 Equipment installed before the building is secure shall be protected against dust, water, and physical damage by other trades.
20.4.2 Readers installed at exterior openings before the building envelope is closed shall be temporarily covered.
20.4.3 Energization of locks and other electrified hardware shall not occur until acceptance testing is scheduled and the system is ready for commissioning.
21 Training
21.1 The Contractor shall provide training to the Owner's designated administrators and operators before substantial completion. Training shall include the following:
- Head-end operation: log in, navigate the user interface, monitor real-time events, respond to alarms
- User and credential management: enroll a user, issue a credential, assign roles, modify access privileges, suspend and revoke a credential, issue and recover a lost credential
- Reporting: generate and export audit reports, query events by user, door, time range, and event type
- Time schedule and holiday management
- Lockdown and emergency procedures: initiate a building lockdown, release a lockdown, override an individual door
- Routine system health checks: review system status, check controller and reader online state, review power supply and battery status, review pending firmware updates
- Backup and recovery: confirm a backup ran, perform a restore drill
21.2 The training duration shall be as indicated in the datasheet.
Training Hoursrange
hours
48162440
21.3 Training shall be delivered on the installed system, not on a generic demonstration platform, so that the Owner's personnel are trained on the actual configuration, naming conventions, and door schedule of the project.
21.4 Training materials shall be left with the Owner.
22 Delivery, Storage, and Handling
22.1 Access control equipment shall be delivered in the manufacturer's original packaging with listing marks and serial numbers intact.
22.2 Equipment shall be stored indoors in a clean, dry, conditioned space until installation.
22.3 Credentials shall be stored in a locked container with controlled access; the credential inventory log shall be maintained from receipt through issuance.
22.4 Batteries shall be stored at the manufacturer's recommended temperature and shall not be installed in equipment until commissioning is imminent.
22.5 Batteries shall not be allowed to discharge below the manufacturer's storage voltage during construction.
23 Warranty
23.1 The Contractor shall warrant the system installation, including all wiring, terminations, programming, and integration, for the period indicated in the datasheet.
Installation Warranty Periodselect
1 year from substantial completion
2 years from substantial completion
3 years from substantial completion
23.2 The software support and maintenance term shall be as indicated in the datasheet.
Software Support and Maintenance Agreementradio
● Manufacturer software maintenance for 1 year
○ Manufacturer software maintenance for 3 years
○ Owner self-maintains after substantial completion (perpetual license)
23.3 Manufacturer warranties on individual products (controllers, readers, power supplies, batteries) shall be passed through to the Owner.
23.4 The software maintenance term shall include firmware updates for controllers and readers, security patches for the head-end, and access to technical support.
23.5 Lapsed maintenance has been the cause of unresolved vulnerabilities on installed systems; the Owner shall be advised at turnover of the renewal schedule.
24 Spare Parts
24.1 The Contractor shall deliver to the Owner at substantial completion the spare parts inventory below. Spare parts shall be of the same manufacturer and model as the installed equipment and shall be packaged and labeled for storage.
Spare Parts Inventorycheckbox
☑ One reader per installed reader model (minimum one)
☑ One door position switch (concealed and surface, as installed)
☑ One REX device per installed type
☑ One power supply per installed model
☑ One battery per installed power supply
☑ 10 percent overage on credentials (minimum 25)
☐ One controller per installed model
24.2 Spare parts shall be stored by the Owner in the equipment room or designated storage area with the system documentation.
24.3 The spare parts list shall be included in the closeout package.
This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.
"Access Control Systems." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/access-control-systems — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.