SynC · SynC Standards
Aluminum Entrances and Storefronts
Rev9
IssuedAug 29, 2026
Contents
- 1Scope
- 1.8Coordination with Adjacent Work
- 2Referenced Standards
- 3Submittals
- 3.1Action Submittals
- 3.2Informational Submittals
- 3.3Closeout Submittals
- 4Quality Assurance
- 4.1Manufacturer and Installer Qualifications
- 4.2Mock-Up
- 5Performance Classification
- 5.1Rated Performance Class and Grade
- 5.2Design Wind Pressure
- 5.3Structural Load Resistance
- 5.4Framing Deflection Limits
- 6Air Infiltration
- 7Water Penetration Resistance
- 8Thermal and Solar Performance
- 9Condensation Resistance
- 10Acoustic Performance
- 11Windborne Debris Impact Resistance
- 12Inter-Story Drift Accommodation
- 13Aluminum Extrusions
- 14Thermal Barrier
- 15Framing System Configuration
- 15.1Framing Depth and Sightline
- 15.2Glazing Pocket Position
- 15.3Framing Joinery
- 15.4Mullion Spans and Reinforcement
- 16Glass
- 16.1Glass Lite Construction
- 16.2Safety Glazing
- 16.3Laminated Glass Interlayer
- 16.4Low-Emissivity Coatings
- 17Insulating Glass Units
- 17.1Unit Make-Up
- 17.2Edge Seal and Spacer
- 18Glazing
- 18.1Glazing Method
- 18.2Glazing Gaskets
- 18.3Setting Blocks and Glass Clearances
- 18.4Glazing Pocket Drainage
- 19Perimeter Sealant Joints
- 20Entrance Doors
- 20.1Door Leaf Proportions
- 20.2Door Leaf Construction
- 20.3Door Glazing
- 20.4Door Clearances and Accessibility
- 21Entrance Door Hardware
- 21.1Hardware Sets and Coordination
- 21.2Hanging Devices
- 21.3Door Closers
- 21.4Exit Devices
- 21.5Locking Hardware
- 21.6Pulls and Push Hardware
- 21.7Thresholds and Weatherseals
- 22Aluminum Finishes
- 22.1Finish Selection
- 22.2Anodic Coatings
- 22.3Organic Coatings
- 23Anchorage and Perimeter Conditions
- 23.1Anchorage Methods
- 23.2Movement Accommodation
- 23.3Sill Water Management
- 23.4Air and Water Control Layer Continuity
- 24Delivery, Storage, and Handling
- 25Installation
- 25.1Pre-Installation Coordination
- 25.2Rough Opening Tolerances
- 25.3Framing Erection
- 25.4Glazing Installation
- 25.5Door and Hardware Installation
- 26Field Testing
- 27Cleaning and Protection
- 27.1Construction Protection
- 27.2Final Cleaning
- 28Warranty
- 29Spare Parts and Maintenance Materials
Download
Build a datasheet from this standard
Start a project with this standard already attached — one click, no setup.
Use in a project
1 Scope
NOTE This standard governs the design, fabrication, finishing, and installation of extruded aluminum entrance and storefront systems, the glass and insulating glass units glazed into them, the swing entrance doors integrated with them, and their perimeter anchorage and seals. (1.1)
1.2 The furnished work shall comprise the framing assembly, the glazing infill, the entrance door leaves and their hardware, the thermal barrier construction, the perimeter anchorage, and the sealed interfaces between the storefront perimeter and the adjoining construction.
NOTE Storefront elevations, mullion and door locations, transom and sidelight arrangement, glass type designations by lite, and hardware set assignments are established by the contract drawings and are not fixed by this standard. (1.3)
1.4 Storefront and entrance layout shall be as indicated on the contract documents.
1.5 The Contractor shall treat the storefront, its glazing, its doors, and its perimeter seals as one coordinated assembly and shall reconcile every performance criterion across those parts before fabrication is released.
NOTE Structural, thermal, water control, air control, egress, accessibility, and durability requirements are cross-coupled in a glazed aluminum assembly, so a change made to satisfy one of them routinely disturbs another. (1.6)
NOTE A deeper thermal barrier lowers the assembly U-factor and also changes the profile depth, which changes the anchor preparation and the door pocket dimension; a higher design pressure drives thicker glass, which raises unit weight and changes the closer size and hinge selection; a laminated inboard lite adds weight and thickness to every unit it appears in. (1.7)
1.8 Coordination with Adjacent Work
1.8.1 The Contractor shall coordinate hardware finish, keying, and access control preparation across entrance, storefront, and interior openings with Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware.
1.8.2 The Contractor shall coordinate continuity of the building thermal envelope at the storefront head, jambs, and sill with Building Thermal InsulationBuilding Thermal InsulationResolves to the current adopted revision.sync/building-thermal-insulation.
1.8.3 The Contractor shall coordinate head flashing, sill pan flashing, end dams, and perimeter closures and counterflashing with Sheet Metal Flashing And TrimSheet Metal Flashing and TrimResolves to the current adopted revision.sync/sheet-metal-flashing-and-trim.
1.8.4 The Contractor shall coordinate continuity of the air control layer and the water resistive barrier across the storefront rough opening with the trades installing those layers in the adjoining wall.
2 Referenced Standards
2.1 Materials, fabrication, testing, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited in the Contract Documents.
2.2 Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
2.3 The Contractor shall submit a written request for interpretation to the Engineer of Record before proceeding with work governed by a conflict identified during submittal preparation.
| Standard | Title |
|---|---|
| AAMA/WDMA/CSA 101/I.S.2/A440 | North American Fenestration Standard/Specification for Windows, Doors, and Skylights |
| AAMA 501 | Methods of Test for Exterior Walls |
| AAMA 501.2 | Quality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls, and Sloped Glazing Systems |
| AAMA 501.4 | Recommended Static Test Method for Evaluating Curtain Wall and Storefront Systems Subjected to Seismic and Wind Induced Inter-Story Drift |
| AAMA 502 | Voluntary Specification for Field Testing of Newly Installed Fenestration Products |
| AAMA 503 | Voluntary Specification for Field Testing of Newly Installed Storefronts, Curtain Walls, and Sloped Glazing Systems |
| AAMA 611 | Voluntary Specification for Anodized Architectural Aluminum |
| AAMA 612 | Combined Coatings of Anodic Oxide and Transparent Organic Coatings on Architectural Aluminum |
| AAMA 800 | Voluntary Specifications and Test Methods for Sealants |
| AAMA 1503 | Voluntary Test Method for Thermal Transmittance and Condensation Resistance of Windows, Doors, and Glazed Wall Sections |
| AAMA 2603 | Pigmented Organic Coatings on Aluminum Extrusions and Panels |
| AAMA 2604 | High Performance Organic Coatings on Aluminum Extrusions and Panels |
| AAMA 2605 | Superior Performing Organic Coatings on Aluminum Extrusions and Panels |
| AAMA CW-13 | Structural Sealant Glazing Systems |
| AAMA SSGDG-1 | Structural Silicone Glazing Design Guidelines |
| AAMA TIR-A8 | Structural Performance of Composite Thermal Barrier Framing Systems |
| ASTM B209 | Aluminum and Aluminum-Alloy Sheet and Plate |
| ASTM B221 | Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes |
| ASTM C509 | Elastomeric Cellular Preformed Gasket and Sealing Material |
| ASTM C864 | Dense Elastomeric Compression Seal Gaskets, Setting Blocks, and Spacers |
| ASTM C920 | Elastomeric Joint Sealants |
| ASTM C1036 | Flat Glass |
| ASTM C1048 | Heat-Strengthened and Fully Tempered Flat Glass |
| ASTM C1172 | Laminated Architectural Flat Glass |
| ASTM C1376 | Pyrolytic and Vacuum Deposition Coatings on Flat Glass |
| ASTM E90 | Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements |
| ASTM E283 | Determining Rate of Air Leakage Through Exterior Windows, Skylights, Curtain Walls, and Doors Under Specified Pressure Differences Across the Specimen |
| ASTM E330 | Structural Performance of Exterior Windows, Doors, Skylights, and Curtain Walls by Uniform Static Air Pressure Difference |
| ASTM E331 | Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Uniform Static Air Pressure Difference |
| ASTM E413 | Classification for Rating Sound Insulation |
| ASTM E547 | Water Penetration of Exterior Windows, Skylights, Doors, and Curtain Walls by Cyclic Static Air Pressure Difference |
| ASTM E783 | Field Measurement of Air Leakage Through Installed Exterior Windows and Doors |
| ASTM E1105 | Field Determination of Water Penetration of Installed Exterior Windows, Skylights, Doors, and Curtain Walls, by Uniform or Cyclic Static Air Pressure Difference |
| ASTM E1300 | Determining Load Resistance of Glass in Buildings |
| ASTM E1332 | Classification for Rating Outdoor-Indoor Sound Attenuation |
| ASTM E1886 | Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Missile(s) and Exposed to Cyclic Pressure Differentials |
| ASTM E1996 | Performance of Exterior Windows, Curtain Walls, Doors, and Impact Protective Systems Impacted by Windborne Debris in Hurricanes |
| ASTM E2112 | Installation of Exterior Windows, Doors, and Skylights |
| ASTM E2190 | Insulating Glass Unit Performance and Evaluation |
| ANSI Z97.1 | Safety Glazing Materials Used in Buildings — Safety Performance Specifications and Methods of Test |
| ANSI/BHMA A156.3 | Exit Devices |
| ANSI/BHMA A156.4 | Door Controls — Closers |
| ANSI/BHMA A156.5 | Cylinders and Input Devices for Locks |
| ANSI/BHMA A156.16 | Auxiliary Hardware |
| ANSI/BHMA A156.18 | Materials and Finishes |
| ANSI/BHMA A156.26 | Continuous Hinges |
| 16 CFR 1201 | Safety Standard for Architectural Glazing Materials |
| GANA Glazing Manual | Glazing Manual |
| ICC A117.1 | Accessible and Usable Buildings and Facilities |
| IBC | International Building Code |
| IECC | International Energy Conservation Code |
| NFRC 100 | Procedure for Determining Fenestration Product U-factors |
| NFRC 200 | Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence |
| NFRC 500 | Procedure for Determining Fenestration Product Condensation Resistance Values |
3 Submittals
3.1 Action Submittals
3.1.1 Action submittals shall be reviewed and returned before any framing, glass, door, or hardware item is released for fabrication or procurement.
3.1.2 Storefront, glazing, door, and hardware submittals shall be assembled into one coordinated review package so that framing depth, glazing pocket dimension, unit thickness, door leaf dimension, and hardware preparation are reconciled against one another in a single review.
3.1.3 The Contractor shall submit the following action submittals:
- Storefront shop drawing elevations of every storefront condition, drawn to scale, keyed to the contract drawings, showing mullion and door locations, transom and rail lines, glass type designation per lite, and rough opening dimensions
- Storefront shop drawing section details at head, jamb, sill, intermediate horizontal, intermediate vertical, door head, door jamb, and threshold, and at every transition to an adjoining assembly, showing thermal barrier, glazing pocket and gasket engagement, perimeter joint, anchor type and location, and air and water control layer continuity
- Door elevations for each door type showing stile and rail dimensions, leaf size, hand, swing, glazing, and hardware preparation locations
- Hardware schedule organized by hardware set, identifying each item by function, ANSI/BHMA designation, ANSI/BHMA A156.18 finish code, and applicable listing
- Letter from the hardware supplier confirming that the scheduled hardware satisfies the accessibility, means of egress, and panic hardware requirements of the adopted code for each opening
- Structural calculations for framing members and anchorage, signed and sealed by a professional engineer licensed in the project jurisdiction, addressing member spans, deflection, glass load resistance per ASTM E1300, anchor capacity at every anchor condition, and accommodation of building movement
- Product data for framing, doors, thermal barrier material, gaskets, sealants, setting blocks, and finish, including the tested performance class and grade and the supporting laboratory test reports
- Insulating glass unit make-up submittal for each glass type, stating each lite by thickness, heat treatment, lamination, and coating type and surface, and stating spacer, primary and secondary seal materials, and cavity fill
- Thermal and optical performance reports stating U-factor per NFRC 100, solar heat gain coefficient and visible transmittance per NFRC 200, and the condensation rating on the basis indicated in the datasheet
- Finish samples on the extrusion profile to be furnished, or on a profile of equivalent thickness and orientation, at least 12 in. by 12 in.
- Sealant compatibility and adhesion test report from the sealant manufacturer covering the framing finish, the glass edge condition, and each adjoining substrate
Action Submittals Requiredcheckbox
☑ Storefront shop drawing elevations
☑ Storefront shop drawing section details
☑ Door elevations by type
☑ Hardware schedule by hardware set
☐ Hardware supplier code compliance letter
☑ Signed and sealed structural calculations
☑ Framing, door, gasket, and sealant product data
☑ Insulating glass unit make-up submittal
☑ NFRC thermal and optical performance reports
☐ Condensation rating report
☑ Finish samples on the furnished profile
☐ Sealant compatibility and adhesion test report
☐ Mock-up test report
3.2 Informational Submittals
3.2.1 The Contractor shall submit the following informational submittals before the corresponding work begins:
- Manufacturer qualification statement with laboratory test reports for the specific framing system offered
- Installer qualification statement listing comparable completed projects with contact references
- Certification of the insulating glass unit fabricator under a program that verifies conformance to ASTM E2190
- Glazier training or certification records for the glazing method used on the project
- Field test agency qualifications and the proposed field test procedure and schedule
- Manufacturer written instructions for glazing, anchorage, and hardware installation
Informational Submittals Requiredcheckbox
☑ Manufacturer qualification statement with test reports
☑ Installer qualification statement with references
☑ Insulating glass unit fabricator certification
☐ Glazier training or certification records
☐ Field test agency qualifications and procedure
☑ Manufacturer written installation instructions
3.3 Closeout Submittals
3.3.1 The Contractor shall submit the following closeout submittals before final acceptance:
- As-built storefront elevations and door and hardware schedules reflecting field changes
- Field test reports for every field test performed, including retests after repair
- Record of door closer adjustment at each opening, stating measured opening force
- Cleaning and maintenance instructions for framing finish, glass, gaskets, sealants, and hardware, naming the products that are permitted and the products that are prohibited on each surface
- Executed warranties from the framing manufacturer, the insulating glass unit fabricator, the finish applicator, the sealant manufacturer, and the hardware supplier
- Transfer of spare parts and maintenance materials with a written inventory receipt
Closeout Submittals Requiredcheckbox
☑ As-built elevations and schedules
☑ Field test reports including retests
☑ Door closer adjustment record
☑ Cleaning and maintenance instructions
☑ Framing manufacturer warranty
☑ Insulating glass unit warranty
☑ Finish warranty
☑ Sealant warranty
☑ Hardware warranty
☑ Spare parts inventory receipt
4 Quality Assurance
4.1 Manufacturer and Installer Qualifications
4.1.1 The framing manufacturer shall furnish independent laboratory test reports for the offered framing system covering air infiltration, water penetration, and structural performance at or above the criteria established in this standard.
4.1.2 The framing manufacturer shall furnish the published span and load tables used by the structural calculations, identifying the member, reinforcement condition, and design pressure to which each table applies.
4.1.3 The installer shall have installed thermally comparable aluminum entrance and storefront systems for at least the number of years indicated in the datasheet.
Installer Minimum Years of Experience with Comparable Systemsrange
years
23510
4.1.4 Where the project includes windborne debris impact-rated assemblies, the installer shall demonstrate prior completed work on impact-rated fenestration of equivalent missile level.
4.1.5 Glaziers shall be trained by the framing system manufacturer in the glazing pocket configuration, gasket type, and sealant application used on the project, and the Contractor shall maintain the training records on site.
4.1.6 Where the parties disagree whether an installer or glazier meets these qualifications, the Engineer of Record shall make the initial determination.
4.2 Mock-Up
NOTE A mock-up establishes the accepted standard of appearance and, where it is tested, the accepted standard of air and water performance for the production installation. (4.2.1)
4.2.2 The storefront mock-up requirement shall be as indicated in the datasheet.
Storefront Mock-Up Requirementselect
Not required
Visual mock-up of a typical bay
Field mock-up of a typical bay installed in its permanent location
Field mock-up of a typical bay installed in a temporary test location
Laboratory test specimen of a typical bay
4.2.3 Where a mock-up is required, it shall include every component of a typical bay, including framing, glazing, door where a door occurs in the typical bay, perimeter sealant, anchorage, and the transition to the adjoining assembly, so that the air and water control layers can be evaluated as an assembled whole.
4.2.4 Where a mock-up is required, the Contractor shall obtain written acceptance of the mock-up from the Engineer of Record before releasing production fabrication.
4.2.5 Where a mock-up fails a required test, the Contractor shall correct the deficiency and repeat the failed test on the corrected mock-up at the Contractor's cost before production work proceeds.
4.2.6 An accepted mock-up may remain in the completed work where it is installed in its permanent location and complies with all requirements of the Contract Documents.
5 Performance Classification
5.1 Rated Performance Class and Grade
NOTE AAMA/WDMA/CSA 101/I.S.2/A440 classifies a fenestration product by a performance class letter paired with a performance grade number, written together as a class-grade designation. The class establishes the gateway test criteria the product must satisfy; the grade is the design pressure in psf at which the product was tested. (5.1.1)
5.1.2 The storefront and entrance system shall be tested, rated, and labeled in accordance with AAMA/WDMA/CSA 101/I.S.2/A440.
5.1.3 The rated performance class shall be as indicated in the datasheet.
Rated Performance Classselect
R
LC
CW
AW
5.1.4 The rated performance grade shall be not less than the design wind pressure established by the structural drawings for the storefront's exposure and elevation.
5.2 Design Wind Pressure
NOTE Design wind pressure is established by the building code wind load determination for the project location, building height, exposure category, and the storefront's position on the facade, and it differs between the inward-acting and outward-acting directions at the same location. (5.2.1)
5.2.2 The inward-acting design wind pressure shall be as indicated in the datasheet.
Inward-Acting Design Wind Pressurerange
psf
10152025304050607080100120150200
Per drawings — structural drawings (deferred by default)
5.2.3 The outward-acting design wind pressure shall be as indicated in the datasheet.
Outward-Acting Design Wind Pressurerange
psf
10152025304050607080100120150200
Per drawings — structural drawings (deferred by default)
5.2.4 Framing, glass, and anchorage shall be designed for the greater of the inward-acting and outward-acting design wind pressures at each location, applied in each direction independently.
5.3 Structural Load Resistance
5.3.1 The framing system shall withstand the design wind pressure in both directions without glass breakage, anchor failure, permanent deformation, or loss of the air or water seal.
5.3.2 Structural performance shall be verified by test in accordance with ASTM E330 at 1.5 times the design wind pressure applied for 10 seconds in each direction.
5.3.3 Permanent deformation of any framing member after the structural overload test shall not exceed 0.2 percent of the member span.
5.3.4 Glass thickness and heat treatment shall be selected in accordance with ASTM E1300 for the design wind pressure, lite dimensions, support condition, and unit make-up at each lite.
5.4 Framing Deflection Limits
NOTE Excessive framing deflection under wind load relieves gasket compression at the glazing pocket, opens the perimeter seal, and transfers load into the glass edge. Two bounds are customarily applied together because a span ratio alone permits large absolute movement on a long member. (5.4.1)
5.4.2 Framing member deflection normal to the plane of the wall under the design wind pressure shall not exceed the span ratio indicated in the datasheet.
Framing Deflection Limit — Span Ratioselect
L/120
L/175
L/240
L/360
5.4.3 Framing member deflection normal to the plane of the wall under the design wind pressure shall not exceed the absolute limit indicated in the datasheet.
Framing Deflection Limit — Absoluterange
in.
0.1250.250.3750.50.7511.5
5.4.4 Deflection of a framing member parallel to the plane of the glass under superimposed dead load shall not reduce the glass edge clearance below the value published by the framing manufacturer for the glazing pocket, and shall not exceed 1/8 in.
6 Air Infiltration
NOTE An air leakage limit is meaningless without the pressure differential at which it is measured. US energy codes rate storefront glazing and commercial glazed swinging entrance doors at 1.57 psf, while project specifications for commercial storefront commonly require the same rate to be demonstrated at 6.24 psf, which is the substantially more demanding of the two. (6.1)
6.2 Air infiltration shall be tested in accordance with ASTM E283 at the pressure differential indicated in the datasheet.
Air Infiltration Test Pressure Differentialrange
psf
1.572.866.24
6.3 Air leakage through fixed framing and glazing, excluding the operating perimeter of any door or operable unit, shall not exceed the rate indicated in the datasheet.
Air Leakage Limit — Fixed Framing and Glazingrange
cfm/ft²
0.010.030.060.10.20.3
6.4 Air leakage through a swing entrance door, measured over the door leaf area, shall not exceed the rate indicated in the datasheet.
Air Leakage Limit — Swing Entrance Doorrange
cfm/ft²
0.30.50.7511.5
NOTE A swing entrance door leaks more air than the fixed framing around it because the leaf needs operating clearance at every edge, and the seal at that clearance is a compressed or wiping contact rather than a captured gasket. Where the leakage rate must approach that of the fixed framing, full-perimeter compression weatherstripping and a drop seal at the sill are the mechanisms available, and a vestibule removes the exterior pressure differential from one leaf entirely. (6.5)
7 Water Penetration Resistance
7.1 Static water penetration resistance shall be tested in accordance with ASTM E331 at the test pressure indicated in the datasheet.
Water Penetration Resistance Test Pressurerange
psf
2.8656.24810121520
NOTE AAMA/WDMA/CSA 101/I.S.2/A440 derives the water test pressure as a fraction of the design wind pressure subject to a floor and a ceiling, so on most projects the value in the datasheet follows from the design pressure rather than being chosen independently. (7.2)
7.3 Where cyclic water penetration testing is required by the datasheet, it shall be performed in accordance with ASTM E547 at the same test pressure.
7.4 No water shall pass beyond the innermost plane of the framing during the water penetration test period.
7.5 Water that enters the glazing pocket or an internal framing cavity shall be collected and drained to the exterior, and shall not reach the interior face of the framing.
NOTE Controlled leakage into a drained and weeped cavity is the design intent of a captured aluminum glazing system, so a test criterion written as no water entering the system at all would fail a correctly built assembly. The criterion is that no water passes the interior plane. (7.6)
8 Thermal and Solar Performance
NOTE Whole-product ratings and center-of-glass ratings are not interchangeable. A center-of-glass U-factor omits the frame and the glass edge, which are the least insulating parts of the assembly, so it always reads better than the assembly the project actually receives. (8.1)
8.2 Thermal transmittance, solar heat gain coefficient, and visible transmittance shall be established for the complete fenestration product, including framing, in accordance with NFRC 100 and NFRC 200.
8.3 Component-level or center-of-glass values shall not be substituted for whole-product ratings where the energy code compliance path requires certified whole-product ratings.
8.4 The maximum whole-product thermal transmittance shall be as indicated in the datasheet.
Maximum Whole-Product U-Factorrange
Btu/h·ft²·°F
0.150.20.250.30.350.40.450.50.550.60.70.811.2
Per drawings — energy compliance documentation (deferred by default)
8.5 The maximum whole-product solar heat gain coefficient shall be as indicated in the datasheet.
Maximum Whole-Product Solar Heat Gain Coefficientrange
SHGC
0.10.150.20.250.30.350.40.450.50.60.70.8
Per drawings — energy compliance documentation (deferred by default)
8.6 The minimum whole-product visible transmittance shall be as indicated in the datasheet.
Minimum Whole-Product Visible Transmittancerange
VT
0.10.20.30.40.50.60.70.8
Per drawings — energy compliance documentation (deferred by default)
NOTE Solar heat gain coefficient and visible transmittance both fall as a coating is made more solar-selective, and the ratio between them is bounded by the coating chemistry available. A target pair that is unreachable by any coated unit forces a change to one of the two targets, so the pair is checked against candidate unit make-ups before the glass is released. (8.7)
8.8 The Contractor shall confirm through the insulating glass unit submittal that the U-factor, solar heat gain coefficient, and visible transmittance targets are met simultaneously by the proposed unit make-up, and shall report any target that cannot be met to the Engineer of Record before the glass is fabricated.
9 Condensation Resistance
NOTE Two US condensation metrics are in use and their values are not interchangeable. AAMA 1503 reports a condensation resistance factor from a guarded hot box test of the assembly; NFRC 500 reports a condensation resistance value on a 1 to 100 scale, determined chiefly by simulation at stated indoor humidity levels. A number quoted without its basis cannot be verified. (9.1)
9.2 The condensation rating basis shall be as indicated in the datasheet.
Condensation Rating Basisselect
Condensation resistance factor per AAMA 1503
Condensation resistance per NFRC 500
9.3 The minimum condensation rating on the indicated basis shall be as indicated in the datasheet.
Minimum Condensation Ratingrange
rating
203040455055606570758090100
Per drawings — energy compliance documentation (deferred by default)
NOTE Interior surface condensation forms where the interior surface temperature of the frame or the glass edge falls below the interior dew point, so the rating required at a given location follows from the interior design humidity and the winter design temperature rather than from the product alone. Where interior humidity is elevated by process or occupancy, as in a natatorium, an ice rink, or a food processing area, the governing dew point is well above that of a conventionally conditioned space. (9.4)
9.5 The Contractor shall submit the framing manufacturer's written confirmation that the proposed assembly meets the indicated condensation rating at the project's interior design temperature and relative humidity.
10 Acoustic Performance
NOTE Sound transmission class and outdoor-indoor transmission class rate the same assembly against different spectra. Outdoor-indoor transmission class weights low-frequency content more heavily, so an assembly selected on sound transmission class alone can perform poorly against traffic, rail, and aircraft noise. (10.1)
10.2 Where an acoustic rating is required, laboratory sound transmission loss shall be measured in accordance with ASTM E90.
10.3 The minimum sound transmission class, rated in accordance with ASTM E413, shall be as indicated in the datasheet.
Minimum Sound Transmission Classrange
STC
252830323436384042455055
Per drawings — acoustic requirements on the contract documents (deferred by default)
10.4 The minimum outdoor-indoor transmission class, rated in accordance with ASTM E1332, shall be as indicated in the datasheet.
Minimum Outdoor-Indoor Transmission Classrange
OITC
202225273032354045
Per drawings — acoustic requirements on the contract documents (deferred by default)
10.5 Where the Contract Documents establish no acoustic rating for a storefront area, no acoustic performance is required in that area.
11 Windborne Debris Impact Resistance
NOTE Where the project is located in a windborne debris region, glazed openings are required by the building code either to resist missile impact and subsequent cyclic pressure loading or to be protected by an impact-resistant covering. (11.1)
11.2 Where impact resistance is required, the assembly shall be tested in accordance with ASTM E1886 and shall satisfy the criteria of ASTM E1996 for the missile level and wind zone indicated in the datasheet.
11.3 The required missile level shall be as indicated in the datasheet.
Windborne Debris Missile Levelselect
Not in a windborne debris region
Small missile
Large missile
Per drawings — structural drawings (deferred by default)
11.4 The ASTM E1996 wind zone shall be as indicated in the datasheet.
ASTM E1996 Wind Zoneselect
Not applicable
Wind Zone 1
Wind Zone 2
Wind Zone 3
Wind Zone 4
Per drawings — structural drawings (deferred by default)
NOTE An impact rating belongs to a tested assembly, not to a component. The glass make-up, interlayer, glazing method, framing profile, bite, and anchorage are all variables in the qualifying test, so a rating earned by one combination does not transfer to another. (11.5)
11.6 Impact-rated assemblies shall be furnished exactly as configured in the qualifying test report, including glass make-up, interlayer type and thickness, glazing method, glazing bite, framing profile, and anchor type and spacing.
11.7 The Contractor shall not substitute any component of an impact-rated assembly without a revised test report or a written engineering evaluation from the framing manufacturer accepted by the Engineer of Record.
12 Inter-Story Drift Accommodation
NOTE A storefront supported at two levels of a moving structure is displaced in its own plane when the structure racks. The framing accommodates that displacement through anchor slots, joint clearance, and glass edge clearance; when those are exhausted the load transfers into the glass edge and the perimeter seal. (12.1)
12.2 The framing and anchorage shall accommodate the design inter-story drift indicated in the datasheet, in either in-plane direction, without glass breakage, permanent framing deformation, or loss of the perimeter seal.
Design Inter-Story Drift Accommodationrange
in.
0.250.50.7511.523
Per drawings — structural drawings (deferred by default)
12.3 Where the datasheet requires drift testing, drift accommodation shall be verified in accordance with AAMA 501.4 on a specimen representing the project's framing, glazing, and anchorage.
12.4 The structural calculations shall state the anchor slot length, joint width, and glass edge clearance relied on to accommodate the design drift, and the shop drawings shall dimension each of them.
13 Aluminum Extrusions
13.1 Extruded aluminum for framing members, door stiles and rails, glass stops, pressure plates, and trim shall conform to ASTM B221.
13.2 Aluminum sheet and plate for closures, anchor plates, and formed flashings furnished under this standard shall conform to ASTM B209.
13.3 The alloy and temper of structural framing members, door stiles, and door rails shall be as indicated in the datasheet.
Structural Member Alloy and Temperselect
6063-T5
6063-T6
6005A-T61
6061-T6
13.4 The alloy and temper of non-structural glass stops, pressure plates, and trim shall be as indicated in the datasheet.
Non-Structural Member Alloy and Temperselect
6063-T5
6063-T6
6005A-T61
NOTE Temper governs the strength available from a given profile, and the higher tempers are what allow a slender mullion to carry hardware reaction and wind load. The lower temper is more readily formed and is adequate where a member carries only its own weight and the gasket reaction. (13.5)
13.6 The minimum wall thickness of structural framing members and door stiles and rails shall be as indicated in the datasheet.
Minimum Wall Thickness — Structural Membersrange
in.
0.050.0620.070.080.0930.1090.1250.1560.188
13.7 The minimum wall thickness of non-structural glass stops, pressure plates, and trim shall be as indicated in the datasheet.
Minimum Wall Thickness — Non-Structural Membersrange
in.
0.040.050.0620.070.080.0930.125
13.8 Steel reinforcement furnished inside an aluminum framing cavity shall be hot-dip galvanized, or shall be isolated from the aluminum by a non-conductive separator, so that the dissimilar metals are not in direct contact in the presence of moisture.
14 Thermal Barrier
NOTE A thermal barrier interrupts the continuous aluminum path between the exterior and interior faces of a framing member. The interruption is what allows the interior surface to stay near room temperature, and it also means the two aluminum halves are joined only through the barrier, so the barrier carries shear between them. (14.1)
14.2 The thermal barrier method shall be as indicated in the datasheet.
Thermal Barrier Methodselect
Not thermally broken
Poured and debridged polyurethane
Pultruded glass-reinforced polyamide strut, mechanically crimped
Co-extruded thermoplastic composite
Thermally improved with a non-structural insulating separator
14.3 Where a thermal barrier is indicated, its nominal width measured across the interruption shall be as indicated in the datasheet.
Thermal Barrier Nominal Widthrange
mm
61014162024283236405060
NOTE A wider interruption lowers the assembly U-factor and raises the interior surface temperature, and it also deepens the profile and increases cost. Where the barrier is a rigid strut rather than a poured polymer, more shear is transferred between the two aluminum halves, so the composite member is stiffer for the same profile depth, and the two halves can be finished separately before assembly, which is what makes a different interior and exterior color possible. (14.4)
14.5 Composite thermal barrier framing shall have been evaluated in accordance with AAMA TIR-A8 for the shear transfer relied on in the structural calculations.
14.6 The thermal barrier shall be continuous through every framing member of the thermally broken portion of the assembly, and shall not be bridged by an anchor, fastener, reinforcement, or accessory that creates a continuous metal path between the exterior and interior faces.
14.7 Where a fastener must cross the thermal barrier, the Contractor shall submit the framing manufacturer's detail showing the isolation provided, and the thermal performance report shall reflect that detail.
15 Framing System Configuration
15.1 Framing Depth and Sightline
NOTE Framing depth sets the section modulus available to carry wind load and the pocket depth available for the glazing, and it governs the wall thickness the head, jamb, and sill details must resolve. Sightline is the exposed face dimension seen in elevation and is an independent selection. (15.1.1)
15.1.2 The nominal framing system depth shall be as indicated in the datasheet.
Framing System Nominal Depthrange
in.
1.7522.53.2544.5567.510
Per drawings — storefront section details (deferred by default)
15.1.3 The nominal exposed face dimension of framing members seen in elevation shall be as indicated in the datasheet.
Framing System Nominal Sightlinerange
in.
11.3751.7522.5346
Per drawings — storefront elevations (deferred by default)
15.1.4 The framing depth shall be reconciled with the wall thickness, the head and sill flashing details, and the entrance door leaf thickness before the shop drawings are submitted.
15.2 Glazing Pocket Position
NOTE The position of the glazing pocket within the framing depth determines where the glass plane sits relative to the framing faces, which changes the elevation shading, the head and sill flashing geometry, and the depth of the interior and exterior reveals. (15.2.1)
15.2.2 The glazing pocket position within the framing depth shall be as indicated in the datasheet.
Glazing Pocket Positionradio
○ Center set
○ Front set toward the exterior
○ Back set toward the interior
Per drawings — storefront section details (deferred by default)
15.3 Framing Joinery
NOTE The method used to join a horizontal to a vertical determines how the joint is sealed against water and how much of the vertical member's section is removed to make the connection. (15.3.1)
15.3.2 The framing joinery method shall be as indicated in the datasheet.
Framing Joinery Methodselect
Screw spline
Shear block
Stick set with sealed butt joints
Captured pressure plate over a mullion body
15.3.3 Every framing joint shall be sealed with the sealant and in the sequence published by the framing manufacturer for the joinery method used, and the joint sealant shall be compatible with the glazing gaskets and the perimeter sealant.
15.3.4 Field-cut ends of framing members shall be deburred and sealed before assembly.
15.4 Mullion Spans and Reinforcement
15.4.1 Mullion spacing shall be as indicated on the storefront elevations.
15.4.2 The unsupported span of every vertical mullion shall be verified against the framing manufacturer's published span tables for the design wind pressure, the tributary width, and the reinforcement condition furnished.
NOTE A slender aluminum mullion reaches its deflection limit before it reaches its stress limit, so long spans are governed by stiffness. Reinforcement raises stiffness without changing the exposed profile, and an intermediate support removes the span problem entirely at the cost of a structural attachment the building must provide. (15.4.3)
15.4.4 The vertical mullion reinforcement method shall be as indicated in the datasheet.
Vertical Mullion Reinforcement Methodselect
No reinforcement
Steel tube inserted in the mullion cavity
Aluminum stiffener inserted in the mullion cavity
Steel plate reinforcement fastened within the mullion cavity
Intermediate structural support at an intervening floor or beam line
15.4.5 Maximum lite dimensions shall be verified against ASTM E1300 for the design wind pressure and the glass make-up furnished, and the insulating glass unit submittal shall state the largest lite on the project.
16 Glass
16.1 Glass Lite Construction
NOTE Annealed, heat-strengthened, fully tempered, and laminated glass differ in strength, in fracture behavior, and in the fabrication that must precede heat treatment. Heat treatment relieves nothing after the fact, so every hole, notch, and edge finish is completed before the lite is heat treated. (16.1.1)
16.1.2 Flat glass shall conform to ASTM C1036.
16.1.3 Heat-strengthened and fully tempered glass shall conform to ASTM C1048.
16.1.4 Laminated glass shall conform to ASTM C1172.
16.1.5 Coated glass shall conform to ASTM C1376, and the coating type and the surface on which it is applied shall be stated in the insulating glass unit submittal.
16.1.6 The heat treatment of the outboard lite shall be as indicated in the datasheet.
Outboard Lite Heat Treatmentselect
Annealed
Heat-strengthened
Fully tempered
Per drawings — glazing schedule (deferred by default)
16.1.7 The lamination of the outboard lite shall be as indicated in the datasheet.
Outboard Lite Laminationradio
○ Monolithic
○ Laminated
Per drawings — glazing schedule (deferred by default)
16.1.8 The nominal thickness of the outboard lite shall be as indicated in the datasheet.
Outboard Lite Nominal Thicknessrange
in.
0.1250.18750.250.31250.3750.50.6250.75
Per drawings — glazing schedule (deferred by default)
16.1.9 The heat treatment of the inboard lite shall be as indicated in the datasheet.
Inboard Lite Heat Treatmentselect
Annealed
Heat-strengthened
Fully tempered
Per drawings — glazing schedule (deferred by default)
16.1.10 The lamination of the inboard lite shall be as indicated in the datasheet.
Inboard Lite Laminationradio
○ Monolithic
○ Laminated
Per drawings — glazing schedule (deferred by default)
16.1.11 The nominal thickness of the inboard lite shall be as indicated in the datasheet.
Inboard Lite Nominal Thicknessrange
in.
0.1250.18750.250.31250.3750.50.6250.75
Per drawings — glazing schedule (deferred by default)
16.1.12 Where fully tempered glass is furnished, the requirement for heat soak testing shall be as indicated in the datasheet.
Heat Soak Testing of Tempered Glassradio
○ Required for all fully tempered lites
○ Not required
NOTE Nickel sulfide inclusions present in the glass batch can expand years after tempering and fracture a tempered lite with no external cause. Heat soak testing holds the tempered lite at elevated temperature long enough to break the affected lites in the factory rather than in the wall. (16.1.13)
16.2 Safety Glazing
16.2.1 Glazing in a hazardous location defined by the building code shall be safety glazing conforming to 16 CFR 1201 or ANSI Z97.1 at the category required by the code for the location.
16.2.2 Glazing in an entrance door leaf, in a sidelight adjacent to a door, and in any other hazardous location identified by IBC Section 2406 shall be fully tempered or laminated.
16.2.3 Heat-strengthened glass does not satisfy a safety glazing requirement, and shall not be furnished in a hazardous location.
16.2.4 Every safety glazing lite shall carry a permanent manufacturer marking identifying the fabricator and the safety glazing standard and category to which it conforms, located so that it remains visible after installation.
16.3 Laminated Glass Interlayer
NOTE Interlayer chemistry sets the post-breakage stiffness, the shear transfer between plies, the acoustic damping, and the ultraviolet and edge moisture tolerance of the laminate. A stiffer interlayer lets a laminate be counted on structurally after the glass has cracked; a softer or specifically damped interlayer buys sound attenuation instead. (16.3.1)
16.3.2 The laminated glass interlayer type shall be as indicated in the datasheet.
Laminated Glass Interlayer Typeselect
Polyvinyl butyral
Acoustic-grade polyvinyl butyral
Ionoplast
Ethylene vinyl acetate
Cast-in-place resin
16.3.3 The nominal laminated glass interlayer thickness shall be as indicated in the datasheet.
Laminated Glass Interlayer Nominal Thicknessrange
mil
1530456090120
16.3.4 Laminated glass edges concealed within the glazing pocket shall be sealed against moisture in accordance with the laminator's published instructions where the interlayer is moisture sensitive.
16.4 Low-Emissivity Coatings
NOTE Glass surfaces are numbered from the exterior, so surface 1 is the outdoor face of the outboard lite and the highest number is the indoor face of the innermost lite. A low-emissivity coating placed on a cavity-facing surface of the outboard lite rejects solar gain before it enters the cavity; the same coating on a cavity-facing surface of the inboard lite reflects interior heat back inward and admits more solar gain. Placement is therefore a climate and orientation decision, not a quality decision. (16.4.1)
16.4.2 The low-emissivity coating surface shall be as indicated in the datasheet.
Low-Emissivity Coating Surfaceselect
No low-emissivity coating
Surface 2
Surface 3
Surface 4
Surface 2 and surface 4
Surface 2 and surface 5
Per drawings — glazing schedule (deferred by default)
16.4.3 The low-emissivity coating type shall be as indicated in the datasheet.
Low-Emissivity Coating Typeselect
Pyrolytic hard coat
Sputtered single silver
Sputtered double silver
Sputtered triple silver
16.4.4 A sputtered coating is not durable when exposed and shall be located on a cavity-facing surface of a sealed insulating glass unit, or shall be edge deleted and sealed in accordance with the coater's published instructions.
17 Insulating Glass Units
17.1 Unit Make-Up
17.1.1 The insulating glass unit configuration shall be as indicated in the datasheet.
Insulating Glass Unit Configurationselect
Monolithic glazing with no sealed cavity
Double glazed with one sealed cavity
Triple glazed with two sealed cavities
17.1.2 The nominal cavity thickness of each sealed cavity shall be as indicated in the datasheet.
Insulating Glass Unit Cavity Thicknessrange
in.
0.250.31250.3750.50.6250.751
17.1.3 The insulating glass unit cavity fill shall be as indicated in the datasheet.
Insulating Glass Unit Cavity Fillradio
○ Air
○ Argon
○ Krypton
NOTE Cavity conductance falls as the cavity widens until convection begins within the cavity, after which further widening gives nothing back. A denser, less conductive fill gas both lowers conduction and shifts the onset of convection, which is why a krypton unit reaches its lowest conductance at a narrower cavity than an argon unit does. (17.1.4)
17.1.5 Insulating glass units shall be factory fabricated and delivered as sealed units.
17.1.6 Insulating glass units shall not be fabricated, cut, or modified at the project site.
17.1.7 The insulating glass unit fabricator shall be certified under a program that verifies conformance to ASTM E2190, and the certification shall be current at the time of fabrication.
17.2 Edge Seal and Spacer
NOTE The edge seal is the life-limiting component of an insulating glass unit. The primary seal is the vapor barrier and the secondary seal is the structural bond that holds the lites together and protects the primary seal; when the secondary seal is loaded in a way it was not designed for, the primary seal fails and the cavity fogs. (17.2.1)
17.2.2 The insulating glass unit spacer type shall be as indicated in the datasheet.
Insulating Glass Unit Spacer Typeselect
Roll-formed aluminum box spacer
Roll-formed stainless steel spacer
Thermoplastic spacer
Structural foam spacer
Silicone foam spacer
17.2.3 The insulating glass unit edge seal shall be as indicated in the datasheet.
Insulating Glass Unit Edge Sealselect
Polyisobutylene primary with polysulfide secondary
Polyisobutylene primary with polyurethane secondary
Polyisobutylene primary with silicone secondary
Single-seal silicone
Single-seal thermoplastic
NOTE Spacer conductance sets the glass edge temperature, and the glass edge is the coldest interior surface of a glazed assembly in winter, so the spacer governs where condensation appears first and it moves the assembly condensation rating more than the cavity does. (17.2.4)
17.2.5 Where structural silicone glazing is indicated, the insulating glass unit secondary seal shall be silicone and shall be compatible with the structural silicone sealant, and the unit fabricator shall confirm that compatibility in writing.
17.2.6 Where a unit is set at an elevation substantially different from its point of fabrication, the unit fabricator shall state in the submittal whether a capillary or breather tube is furnished and how it is sealed after installation.
18 Glazing
18.1 Glazing Method
NOTE A dry glazed pocket seals against compressed gaskets on both faces of the lite and is assembled without cure time. A wet seal replaces or supplements a gasket with a field-applied sealant and depends on surface preparation and cure conditions. Structural silicone transfers wind load from the glass to the frame through the sealant itself, which makes the sealant a structural element with its own design, testing, and quality control requirements under AAMA CW-13 and AAMA SSGDG-1. (18.1.1)
18.1.2 The glazing method shall be as indicated in the datasheet.
Glazing Methodselect
Dry glazed with gaskets at both faces
Wet glazed at the exterior face with a gasket at the interior face
Wet glazed at both faces
Two-sided structural silicone with captured opposing edges
Four-sided structural silicone
18.1.3 Where structural silicone glazing is indicated, the structural silicone bite and glueline thickness shall be determined by calculation for the design wind pressure and the lite dimensions, and the calculation shall be included in the structural submittal.
18.1.4 Where structural silicone glazing is indicated, the Contractor shall submit the silicone manufacturer's adhesion and compatibility test results for every substrate the sealant contacts, and shall perform daily field adhesion testing during application in accordance with the sealant manufacturer's published procedure.
18.1.5 Where structural silicone is field applied, the Contractor shall record ambient temperature, relative humidity, substrate preparation, lot numbers, and the operator for each work period, and shall include those records in the closeout submittals.
18.2 Glazing Gaskets
18.2.1 The glazing gasket material shall be as indicated in the datasheet.
Glazing Gasket Materialselect
Ethylene propylene diene monomer
Silicone
Thermoplastic elastomer
Neoprene
18.2.2 Dense elastomeric gaskets shall conform to ASTM C864 and cellular elastomeric gaskets shall conform to ASTM C509.
18.2.3 Gasket durometer and profile shall be as published by the framing manufacturer for the glazing pocket and the glass thickness furnished, so that the gasket is compressed within its working range at the design glass thickness.
18.2.4 Gaskets in contact with a silicone sealant or with a silicone insulating glass unit secondary seal shall be silicone or shall be confirmed compatible in writing by the sealant manufacturer.
NOTE An incompatible gasket can plasticize an adjacent sealant or stain the glass edge seal, and the failure appears months after glazing, when the affected units are already installed and finished around. (18.2.5)
18.3 Setting Blocks and Glass Clearances
18.3.1 The setting block material shall be as indicated in the datasheet.
Setting Block Materialselect
Ethylene propylene diene monomer
Silicone
Neoprene
18.3.2 The setting block durometer shall be as indicated in the datasheet.
Setting Block Durometerrange
Shore A
50607080859095
18.3.3 Setting blocks shall support the full width of the unit edge, including both lites and the edge seal of an insulating glass unit.
18.3.4 Setting blocks shall be located at the quarter points of the sill edge unless the framing manufacturer's published glazing instructions establish different locations for the lite size and aspect ratio furnished, in which case those locations shall govern.
NOTE A setting block placed under only one lite of an insulating glass unit loads the edge seal in shear and is a direct cause of premature seal failure. (18.3.5)
18.3.6 Edge clearance, face clearance, and glazing bite shall comply with the GANA Glazing Manual and the framing manufacturer's published glazing instructions, and the shop drawing section details shall dimension each of them.
18.4 Glazing Pocket Drainage
NOTE A captured aluminum glazing pocket is designed to admit and drain incidental water rather than to exclude it absolutely, so its performance depends entirely on the drainage path staying open. (18.4.1)
18.4.2 The exterior glazing pocket shall be drained to the exterior through weeps in the exterior glass stop or in the sill member.
18.4.3 Weep size, location, and spacing shall be as published by the framing manufacturer for the system furnished.
18.4.4 Weeps shall discharge onto an exterior surface that sheds the water clear of the wall below, and shall not discharge into a sealant joint, a concealed cavity, or a flashing pocket that has no outlet.
18.4.5 Internal framing drainage cavities shall be interconnected to a weeped outlet at every horizontal member and at the sill.
18.4.6 Weeps shall be left open and unobstructed, and the Contractor shall verify that every weep is open before the work is accepted.
NOTE Blocked weeps convert a drained pocket into a reservoir and are the most frequently identified cause of water reaching the interior through an otherwise correctly built storefront. (18.4.7)
19 Perimeter Sealant Joints
NOTE The perimeter joint between the storefront frame and the adjoining construction accommodates thermal movement of the aluminum relative to a substrate with a different coefficient of expansion, construction tolerance, and structural movement, all at once. Joint width follows from the total calculated movement and the movement capability of the sealant, so narrowing the joint to improve appearance moves the sealant outside its rated range. (19.1)
19.2 The perimeter sealant chemistry shall be as indicated in the datasheet.
Perimeter Sealant Chemistryselect
Silicone
Polyurethane
Silyl-terminated polyether hybrid
Polysulfide
19.3 The perimeter sealant shall conform to ASTM C920, Type S or Type M, Grade NS, at the movement class indicated in the datasheet.
Perimeter Sealant Movement Classrange
% movement capability
12.5253550100
19.4 Sealant joints exposed to pedestrian traffic or to abrasion at a threshold or a sill shall be Grade P or shall be protected by a cover, and shall not be Grade NS.
19.5 The backer rod type shall be as indicated in the datasheet.
Backer Rod Typeselect
Closed-cell polyethylene
Open-cell polyurethane
Bi-cellular with a closed skin
NOTE An open-cell rod lets a moisture-cure sealant cure from both faces; a closed-cell rod punctured during installation outgasses into the uncured sealant and blisters the joint. The rod type therefore follows from the sealant chemistry rather than being an independent selection. (19.6)
19.7 Backer rod type shall be confirmed compatible with the selected sealant by the sealant manufacturer, and the Contractor shall not substitute a rod type without that written confirmation.
19.8 Joint width and depth shall comply with the sealant manufacturer's published joint design, sized for the calculated total movement between the storefront frame and the adjoining construction.
19.9 The sealant manufacturer shall confirm in writing the compatibility and adhesion of the selected sealant to the framing finish and to each adjoining substrate, based on samples of the actual materials to be used.
19.10 Where an adhesion test fails, the Contractor shall apply the primer or surface preparation directed by the sealant manufacturer and shall repeat the test at the Contractor's cost until it passes.
20 Entrance Doors
20.1 Door Leaf Proportions
NOTE Stile width sets the section available to resist the reaction of a closer arm and the anchorage of a lock or exit device, and it is also the most visible proportion of the door in elevation. The trade names narrow, medium, and wide stile refer to conventional dimension bands rather than to fixed values, and manufacturers differ on where the bands fall. (20.1.1)
20.1.2 The entrance door lock stile width shall be as indicated in the datasheet.
Entrance Door Lock Stile Widthrange
in.
1.752.1252.53.54.556
Per drawings — door schedule (deferred by default)
20.1.3 The entrance door bottom rail height shall be as indicated in the datasheet.
Entrance Door Bottom Rail Heightrange
in.
3.54566.581012
Per drawings — door schedule (deferred by default)
NOTE ICC A117.1 requires the push side of a door on an accessible route to present a smooth, uninterrupted surface within 10 in. of the floor, which a bottom rail satisfies directly and which otherwise requires an applied armor plate. (20.1.4)
20.1.5 The entrance door mid-rail arrangement shall be as indicated in the datasheet.
Entrance Door Mid-Railradio
○ No mid-rail
○ Mid-rail at lock height
Per drawings — door schedule (deferred by default)
NOTE A mid-rail provides the continuous section that a mortise exit device or a mortise lock case is housed in, so a leaf without one constrains the hardware that can be mounted on it. (20.1.6)
20.1.7 The entrance door leaf thickness shall be compatible with the framing pocket depth so that the leaf operates within its frame without binding and within the perimeter clearance the weatherseal is designed to close.
20.2 Door Leaf Construction
20.2.1 The entrance door corner construction shall be as indicated in the datasheet.
Entrance Door Corner Constructionselect
Mechanical mortise and tenon with sealed joints
Screw spline with sealed joints
Welded and dressed corners
Deep penetration welded corners
NOTE The corner joint is where the leaf's racking resistance is developed and where water entering the glazing pocket collects, so it is both the structural and the water-management critical detail of the leaf. (20.2.2)
20.2.3 Every corner joint shall be sealed against water entry into the internal leaf cavity.
20.2.4 The internal cavity of the door leaf shall be drained to the exterior at the bottom rail.
20.2.5 Hardware anchorage in a door leaf shall bear on a reinforcement, a backing plate, or a tie rod within the stile or rail, and shall not rely on the extrusion wall alone.
NOTE Cyclical hardware loads work fasteners loose out of a thin extrusion wall over the life of a high-traffic entrance, and the resulting play is what eventually distorts the leaf. (20.2.6)
20.3 Door Glazing
20.3.1 Door leaf glazing shall be as indicated in the glazing schedule, and where the schedule does not identify a separate door glass type it shall match the adjacent storefront glazing.
20.3.2 Door leaf glazing and sidelight glazing shall satisfy the safety glazing requirements of this standard for hazardous locations.
20.3.3 Door leaf glazing stops shall be secured from the interior face of the leaf, or shall be secured with tamper-resistant fasteners where they occur on the exterior face.
20.4 Door Clearances and Accessibility
20.4.1 Doors on an accessible route shall comply with ICC A117.1 for clear opening width, maneuvering clearance, opening force, hardware operability, hardware mounting height, and threshold height.
20.4.2 The clear opening width of each entrance door leaf, measured between the face of the open leaf and the opposite stop with the leaf open 90 degrees, shall be as indicated in the datasheet.
Entrance Door Clear Opening Widthrange
in.
28303234364248
Per drawings — door schedule (deferred by default)
20.4.3 The clear opening width of a door on an accessible route shall be not less than 32 in.
20.4.4 The maximum force required to operate the door hardware and set the leaf in motion shall be as indicated in the datasheet.
Maximum Door Opening Forcerange
lbf
358.51530
NOTE ICC A117.1 limits the opening force of an interior door on an accessible route to 5 lbf, and that limit applies to the force required to operate the hardware and overcome the closer, not to the force required to overcome a pressure differential across the opening. The building code sets separate, higher limits for exterior and other doors. (20.4.5)
20.4.6 Where the measured opening force at an exterior door exceeds the indicated limit because of wind, stack effect, or building pressurization, the Contractor shall report the condition to the Engineer of Record rather than reduce the closer spring power below the size required to reliably latch the leaf.
20.4.7 Threshold height above the adjacent finished floor shall be as indicated in the datasheet.
Maximum Threshold Heightrange
in.
0.250.3750.50.75
20.4.8 A change in level at a threshold exceeding 1/4 in. shall be beveled at a slope no steeper than 1:2.
21 Entrance Door Hardware
21.1 Hardware Sets and Coordination
21.1.1 Hardware shall be grouped into hardware sets, and each opening shall be assigned a hardware set as indicated on the door schedule.
21.1.2 Every opening assigned the same hardware set shall receive identical hardware.
21.1.3 The hardware schedule shall be prepared or reviewed by a certified architectural hardware consultant.
21.1.4 The hardware schedule shall confirm for each opening that every scheduled item is compatible with the door stile and rail dimensions, is listed by its manufacturer for use on an aluminum stile and rail door, and satisfies the egress and accessibility requirements of the adopted code for that opening.
21.1.5 A device listed only for hollow metal or wood doors shall not be furnished on an aluminum entrance door without the device manufacturer's written confirmation of the application.
21.1.6 Where the parties disagree whether a scheduled item is suitable for an opening, the Engineer of Record shall make the initial determination.
21.2 Hanging Devices
NOTE An entrance leaf carries its weight through the hanging device across a service life measured in millions of cycles, so the hanging method sets both the sag behavior of the leaf and the floor and header construction the opening requires. A continuous device distributes the load along the full leaf height; a pivot concentrates it at two points and puts the closer, where a floor closer is used, into the floor construction. (21.2.1)
21.2.2 The entrance door hanging device shall be as indicated in the datasheet.
Entrance Door Hanging Deviceselect
Continuous geared hinge
Continuous pin and barrel hinge
Offset top pivot with an offset bottom pivot
Offset top pivot with a floor closer
Center hung top pivot with a floor closer
Butt hinges
21.2.3 Continuous hinges shall conform to ANSI/BHMA A156.26.
21.2.4 Where a floor closer is indicated, the Contractor shall coordinate the floor closer case, its recess, and its waterproofing with the floor construction before the slab is placed or the recess is formed.
21.2.5 The hanging device shall be sized by its manufacturer for the leaf weight, leaf width, and cycle rate of the opening, and the sizing basis shall be stated in the hardware submittal.
21.3 Door Closers
21.3.1 Door closers shall conform to ANSI/BHMA A156.4 and shall be sized by the closer manufacturer for the leaf weight, leaf width, and wind exposure of the opening.
21.3.2 The door closer mounting type shall be as indicated in the datasheet.
Door Closer Mounting Typeselect
Surface mounted on the door face
Surface mounted on the frame
Concealed in the transom bar
Concealed in the door top rail
Floor closer concealed in the floor
21.3.3 The door closer functions required shall be as indicated in the datasheet.
Door Closer Functions Requiredcheckbox
☑ Adjustable closing speed
☑ Adjustable latch speed
☑ Back-check
☐ Adjustable back-check position
☐ Delayed action
☐ Hold-open
☐ Adjustable spring power
NOTE Back-check resists the leaf beyond a set opening angle, which is what stops a wind-caught leaf from driving its hardware into the adjacent glazing or wall. It restrains the leaf; it does not stop it, so it does not replace a stop or holder. (21.3.4)
21.3.5 Each closer shall be adjusted at substantial completion so that the leaf latches reliably from the fully open position under the building's normal operating pressure differential, and so that the measured opening force complies with the limit indicated in the datasheet.
21.3.6 Where the two adjustments conflict at a given opening, the Contractor shall report the conflict to the Engineer of Record rather than resolve it unilaterally.
21.4 Exit Devices
21.4.1 Exit devices shall conform to ANSI/BHMA A156.3.
21.4.2 Where the adopted building code requires panic hardware or fire exit hardware for the occupancy and occupant load served by an opening, an exit device satisfying that requirement shall be furnished at that opening.
21.4.3 The exit device type shall be as indicated in the datasheet.
Exit Device Typeselect
No exit device
Rim device
Surface vertical rod device
Concealed vertical rod device
Concealed vertical cable device
Mortise exit device
NOTE Vertical rod devices latch a leaf at its head and sill, which is what allows a pair of leaves to be secured without a fixed mullion; a rim device latches into a strike and therefore needs something fixed to latch into. The concealed variants place the rods within the leaf, which requires the leaf section to accommodate them. (21.4.4)
21.4.5 The exit device outside trim shall be as indicated in the datasheet.
Exit Device Outside Trimselect
No outside trim
Key cylinder that retracts the latch
Lever trim operated by a key cylinder
Lever trim without a cylinder
Pull trim with a key cylinder
Electrified lever trim
21.4.6 The exit device strike preparation, mounting anchorage, and projection from the leaf face shall be reconciled against the door stile and rail dimensions on the shop drawings before the device is procured.
21.4.7 Where an access control system controls entry through an opening, the exit device, its trim, and its electrical preparation shall be coordinated with the access control hardware and its power supply, and the coordination shall be shown in the hardware submittal.
21.5 Locking Hardware
21.5.1 The entrance door locking method shall be as indicated in the datasheet.
Entrance Door Locking Methodselect
No locking hardware
Mortise hookbolt deadlock
Mortise deadbolt
Mortise lock with latch and lever
Cylindrical lock with latch and lever
Electric strike with a mortise latch
Electromagnetic lock at the head
Electrified exit device
NOTE A hookbolt engages a shallow strike by rotating into it, which is what allows a narrow stile leaf or a pair without a fixed mullion to be secured where a straight-throw bolt would have nothing to enter. (21.5.2)
21.5.3 An electrically locked opening shall release on loss of power, on activation of the fire alarm system, and on operation of the egress hardware, and the release means shall be shown on the hardware submittal.
21.5.4 Cylinders shall conform to ANSI/BHMA A156.5 and shall be keyed into the Owner's keying system, coordinated with Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current adopted revision.sync/doors-frames-and-hardware.
21.5.5 Cylinders shall be furnished with construction keying, and the Contractor shall void the construction keying and turn over the permanent keys at substantial completion.
21.6 Pulls and Push Hardware
21.6.1 Where an opening has no exterior lever trim and no exit device crossbar on the exterior face, exterior pull hardware shall be furnished.
21.6.2 The exterior door pull type shall be as indicated in the datasheet.
Exterior Door Pull Typeselect
Offset pull handle
Straight ladder pull
Exit device crossbar or touchbar serving as the pull
Lever handle
Flush pull
21.6.3 Auxiliary pull and push hardware shall conform to ANSI/BHMA A156.16.
21.6.4 Pull hardware shall be mounted at a height that complies with ICC A117.1 for operable parts on an accessible route.
21.6.5 Pull hardware shall be through-bolted to a reinforcement or backing plate within the stile.
21.6.6 Hardware finish shall be as indicated in the datasheet, designated by ANSI/BHMA A156.18 finish code.
Hardware Finishtext
Enter value...
Per drawings — hardware schedule (deferred by default)
21.7 Thresholds and Weatherseals
21.7.1 The threshold type shall be as indicated in the datasheet.
Threshold Typeselect
Saddle threshold beveled at both sides
Offset threshold with a sealing strip
Half-saddle threshold
Recessed threshold set flush with the walking surface
Thermally broken threshold
21.7.2 Thresholds shall be extruded aluminum, shall be set in a full bed of sealant on a continuous substrate, and shall be anchored so that the anchors do not penetrate the sill pan or subsill drainage path.
21.7.3 The door bottom seal shall be as indicated in the datasheet.
Door Bottom Sealselect
Surface mounted brush sweep
Surface mounted fin sweep
Surface mounted adjustable sweep with an elastomeric insert
Surface mounted automatic drop seal
Concealed automatic drop seal mortised into the bottom rail
NOTE A drop seal is raised clear of the floor while the leaf swings and is driven down against the threshold as the leaf closes, so it can seal against a tighter clearance than a sweep that must ride over the floor through the whole swing. It also introduces a cam mechanism that requires adjustment and eventual replacement. (21.7.4)
21.7.5 The door perimeter weatherseal shall be as indicated in the datasheet.
Door Perimeter Weathersealselect
Pile weatherstrip set in a kerf
Fin seal set in a kerf
Compression bulb seal
Adjustable jamb weatherstrip
21.7.6 Perimeter weatherseals shall be continuous at the head, at both jambs, and at the meeting stiles of a pair, with no gap at a corner or a transition.
21.7.7 Weatherseals and door bottom seals shall be replaceable from the accessible face without removing the leaf, the frame, or the threshold.
22 Aluminum Finishes
22.1 Finish Selection
NOTE An anodic coating is an integral conversion of the aluminum surface and its color comes from the oxide itself or from pigment deposited within it; an organic coating is applied over the metal and its color comes from the coating. The two families weather differently, are repaired differently, and differ in the color ranges available. (22.1.1)
22.1.2 The finish on exterior-exposed aluminum shall be as indicated in the datasheet.
Exterior Exposed Aluminum Finishselect
Mill finish
Architectural Class I clear anodic coating
Architectural Class I integral color anodic coating
Architectural Class I electrolytically deposited color anodic coating
Architectural Class II clear anodic coating
Architectural Class II integral color anodic coating
Anodic coating with a clear organic topcoat per AAMA 612
Organic coating per AAMA 2603
Organic coating per AAMA 2604
Organic coating per AAMA 2605
22.1.3 The finish on interior-exposed aluminum shall be as indicated in the datasheet.
Interior Exposed Aluminum Finishselect
Same finish as exterior exposed aluminum
Mill finish
Architectural Class I clear anodic coating
Architectural Class I integral color anodic coating
Architectural Class II clear anodic coating
Architectural Class II integral color anodic coating
Anodic coating with a clear organic topcoat per AAMA 612
Organic coating per AAMA 2603
Organic coating per AAMA 2604
Organic coating per AAMA 2605
NOTE A different interior and exterior finish requires that the two halves of a framing member be finished before they are joined, which is available where the thermal barrier is assembled from separately finished profiles and is not available where the barrier is poured into a single extrusion. (22.1.4)
22.1.5 The finish color shall be as indicated in the datasheet.
Finish Colortext
Enter value...
Per drawings — finish schedule (deferred by default)
22.2 Anodic Coatings
22.2.1 Anodic coatings shall conform to AAMA 611 at the architectural class indicated in the datasheet.
22.2.2 Minimum anodic coating thickness and coating weight shall be as established by AAMA 611 for the indicated class:
| Architectural class | Minimum coating thickness | Minimum coating weight |
|---|---|---|
| Class I | 0.7 mil | 32 mg/in² |
| Class II | 0.4 mil | 17 mg/in² |
NOTE Anodic coating thickness governs how long the oxide layer resists the abrasion, weathering, and cleaning that will be applied to it, so the class is selected against the exposure and the expected maintenance rather than against appearance, which is indistinguishable between classes when new. (22.2.3)
NOTE Anodic color is developed in the oxide and varies with alloy chemistry, extrusion lot, bath condition, and rack position, so two runs of the same specified color will not match exactly. Anodized aluminum also cannot be touched up in the field the way an organic coating can. (22.2.4)
22.2.5 All anodized extrusions for a single storefront elevation shall be anodized from the same alloy lot and in a single production run, or shall be run in a controlled sequence with documented color matching between runs.
22.2.6 The Contractor shall submit range samples establishing the acceptable color limits before production anodizing begins, and finished work outside the accepted range shall be replaced at the Contractor's cost.
22.3 Organic Coatings
NOTE AAMA 2603, AAMA 2604, and AAMA 2605 establish progressively more demanding requirements for the same measured properties, principally color retention, gloss retention, chalk resistance, and film integrity after a stated period of South Florida exposure. The three are distinguished by the severity and duration of the exposure the coating must survive, not by the coating being a different kind of product. (22.3.1)
22.3.2 Organic coatings shall conform to the AAMA specification indicated in the datasheet, and the coating applicator shall furnish test data demonstrating conformance for the specific color furnished.
22.3.3 Organic coatings shall be applied to a pretreated surface in accordance with the coating manufacturer's published process, and the pretreatment shall be identified in the submittal.
22.3.4 Dry film thickness shall be as required by the applicable AAMA specification and shall be verified and recorded by the applicator for each production run.
22.3.5 Field touch-up of an organic coating shall be limited to abrasion and minor damage, shall use the coating manufacturer's air-dry touch-up product for the furnished color, and shall not be used to repair a member with damage to the substrate or to the pretreatment.
NOTE An air-dry touch-up is a different chemistry from the factory-cured coating and weathers differently, so an extensive touch-up will become visible as the surfaces age at different rates. (22.3.6)
23 Anchorage and Perimeter Conditions
23.1 Anchorage Methods
23.1.1 The storefront shall be anchored to the surrounding structure at the head, sill, and jambs by anchors sized and located by the project structural calculations.
23.1.2 The head anchorage method shall be as indicated in the datasheet.
Head Anchorage Methodselect
Steel angle welded to an embedded plate
Mechanical expansion anchor into concrete
Screw anchor into concrete
Through-bolt to structural steel
Self-drilling fastener to engineered light-gauge steel framing
Through-bolt to structural wood blocking
23.1.3 The sill anchorage method shall be as indicated in the datasheet.
Sill Anchorage Methodselect
Anchor bolt embedded during the concrete pour
Mechanical expansion anchor into cured concrete
Screw anchor into cured concrete
Anchorage through a subsill receptor into the substrate
Steel angle welded to an embedded plate
23.1.4 The jamb anchorage method shall be as indicated in the datasheet.
Jamb Anchorage Methodselect
Steel clip welded to an embedded plate
Mechanical expansion anchor into concrete or masonry
Screw anchor into concrete or masonry
Through-bolt to a steel jamb
Self-drilling fastener to engineered light-gauge steel framing
23.1.5 Anchor spacing shall be as required by the structural calculations, and shall not exceed the maximum spacing published by the framing manufacturer for the design wind pressure and the member furnished.
23.1.6 Fasteners and anchors in contact with aluminum shall be stainless steel, or shall be a coated carbon steel isolated from the aluminum, so that the connection is not a galvanic cell.
23.1.7 Anchors shall not be installed into light-gauge steel framing, wood framing, or a substrate that has not been engineered to receive the calculated anchor reactions.
23.1.8 Where the surrounding construction cannot receive the anchor reactions, the Contractor shall report the condition to the Engineer of Record before installation, and reinforcement of the surrounding construction shall be provided before the storefront is set.
23.2 Movement Accommodation
NOTE The structure above a storefront deflects under live load and creep after the storefront is set, and the framing must absorb that movement without transferring the load above into the head member. (23.2.1)
23.2.2 The vertical movement allowance at the head anchorage shall be as indicated in the datasheet.
Head Anchorage Vertical Movement Allowancerange
in.
0.250.3750.50.7511.52
Per drawings — structural drawings (deferred by default)
23.2.3 The head condition shall be detailed so that the indicated vertical movement is accommodated without loading the framing, without closing the perimeter joint below its minimum sealant width, and without loss of the air and water seal.
23.2.4 Anchor slots and clearances relied on for movement shall not be filled with sealant, grout, shim stock, or fastener heads that prevent the movement they were provided for.
23.3 Sill Water Management
NOTE A sill component that collects and drains incidental water is what keeps water that gets past the exterior seal from reaching the construction below. It only works if the water it collects has somewhere to go and cannot run off the end of the run. (23.3.1)
23.3.2 The sill water management method shall be as indicated in the datasheet.
Sill Water Management Methodselect
Continuous extruded aluminum subsill receptor
Sheet metal sill pan flashing
Flexible membrane sill pan flashing
Fluid-applied sill pan flashing
Direct anchorage to the substrate with a sealed joint
23.3.3 The sill end dam method shall be as indicated in the datasheet.
Sill End Dam Methodselect
End dam formed integrally with the subsill or pan
Separate end dam piece sealed to the subsill or pan
No end dam
23.3.4 Unless the datasheet indicates otherwise, an end dam shall be provided at every termination of a subsill or sill pan, including at each jamb and at each intermediate break in the run.
23.3.5 The sill component shall be drained to the exterior, and its drainage outlet shall discharge onto an exterior surface rather than into a concealed cavity.
23.3.6 Sill pan flashing, head flashing, end dams, and perimeter counterflashing shall be coordinated with Sheet Metal Flashing And TrimSheet Metal Flashing and TrimResolves to the current adopted revision.sync/sheet-metal-flashing-and-trim.
23.3.7 Sill and head flashings shall be installed and sealed before the storefront framing is set into the rough opening.
NOTE Water collected by a sill component that runs out an open end enters the wall construction directly below the sill, where it is concealed from view until the damage is substantial. (23.3.8)
23.4 Air and Water Control Layer Continuity
23.4.1 The air control layer and the water resistive barrier of the adjoining wall shall be sealed continuously to the perimeter of the storefront framing, with no break in either layer across the opening.
23.4.2 The perimeter air and water control transition shall be as indicated in the datasheet.
Perimeter Air and Water Control Transitionselect
Self-adhered flashing tape lapped to the frame face
Fluid-applied flashing membrane lapped to the frame face
Sheet transition membrane sealed to both the barrier and the frame
Sealant and backer rod joint with a bond breaker
Per drawings — perimeter transition details
23.4.3 The transition material shall be confirmed compatible with the adjoining barrier, with the framing finish, and with the perimeter sealant by the transition material manufacturer.
23.4.4 Transition materials shall be lapped in shingle fashion from the bottom up so that water reaching the transition from above is directed onto the exterior face of the storefront or into the sill component, and never behind the barrier.
23.4.5 The Contractor shall obtain the Engineer of Record's observation of a completed perimeter transition at the first opening of each condition type before the transition is concealed by adjoining construction.
24 Delivery, Storage, and Handling
24.1 Framing members shall be delivered with the finish protected by a strippable film, a paper interleaf, or an equivalent protection, and the protection shall remain in place until the member is installed.
24.2 Materials shall be stored above grade, under cover, on skids or in racks, and shall be protected from standing water, from mortar and concrete splatter, and from ultraviolet degradation of gaskets and sealants.
24.3 Insulating glass units shall be stored upright on resilient blocking with air circulation between units, and shall not be stacked flat.
NOTE Glass stored in contact with standing water, or in a stack where water can be drawn between lites, stains at the glass surface, and the stain cannot be removed. (24.4)
24.5 Sealants, gaskets, and thermal barrier components shall be stored within the temperature range published by their manufacturers, and material stored outside that range or past its shelf life shall be removed from the site.
24.6 Damaged, deformed, or finish-marred members shall be replaced and shall not be repaired in the field except as permitted by the finish requirements of this standard.
25 Installation
25.1 Pre-Installation Coordination
25.1.1 Before storefront framing is delivered to the site, the Contractor shall conduct a pre-installation meeting attended by the storefront installer, the glazier, the trades installing the adjoining air barrier, flashing, and cladding, and the structural engineer's representative where anchorage is engineered.
25.1.2 The pre-installation meeting shall establish rough opening dimensions and tolerances, the sequence of perimeter barrier work relative to storefront installation, anchor type and embedment at each condition, glazing and hardware delivery timing, and the field test schedule.
25.1.3 Deficiencies in the adjoining construction identified at the meeting or at delivery shall be corrected before the storefront is installed.
25.2 Rough Opening Tolerances
25.2.1 Rough openings shall be plumb, level, and square within the framing manufacturer's published tolerances, and within the tolerance indicated in the datasheet, whichever is more stringent.
Rough Opening Tolerancerange
in. per 12 ft
0.06250.1250.18750.250.3750.5
25.2.2 An out-of-tolerance opening shall be corrected before framing is set.
NOTE Forcing framing to fit an out-of-square opening locks stress into the assembly, which distorts gasket compression, opens the perimeter joint unevenly, and shortens the life of the sealant. (25.2.3)
25.3 Framing Erection
25.3.1 Storefront framing shall be installed in accordance with the framing manufacturer's written instructions and ASTM E2112 where its practices apply to the condition.
25.3.2 The Contractor shall install the sill component and seal it to the substrate, then the jamb members, then the head member, then the intermediate horizontals and verticals, then the perimeter joint, then the glazing, and finally the doors and their hardware.
25.3.3 Framing members shall be installed plumb, level, and square.
25.3.4 Vertical members shall be within 1/16 in. of plumb over the full member height.
25.3.5 Horizontal members shall be within 1/16 in. of level over the full member length.
25.3.6 Misalignment shall be corrected by adjusting the anchorage or by refabricating the member, and shall not be corrected by shimming the member out of plane.
25.3.7 Aluminum in contact with concrete, masonry, mortar, or preservative-treated wood shall be separated from that material by a coating, a gasket, or a membrane.
25.4 Glazing Installation
25.4.1 Glazing shall be installed after the framing is complete, aligned, anchored, and protected from weather.
25.4.2 Glazing pockets shall be clean, dry, and free of debris and construction residue before a unit is set.
25.4.3 Units shall be set on setting blocks with the interior gasket continuous around the perimeter and the exterior stop and gasket fully engaged.
25.4.5 Insulating glass units shall not be cut, drilled, ground, or otherwise modified at the site, and a unit that does not fit its opening shall be replaced by the fabricator.
NOTE Site modification of a sealed unit breaches the edge seal, and the resulting failure is excluded from the unit warranty. (25.4.6)
25.4.7 Glazing sealants shall be applied within the temperature and humidity range published by the sealant manufacturer, and work performed outside that range shall be removed and replaced.
25.5 Door and Hardware Installation
25.5.1 Entrance doors shall be installed after framing and glazing are complete so that the leaves are not exposed to damage during those operations.
25.5.2 Hardware shall be installed and adjusted in accordance with each hardware manufacturer's written instructions.
25.5.3 Each closer shall be adjusted at substantial completion for closing speed, latch speed, back-check, and, where furnished, delayed action.
25.5.4 The Contractor shall measure and record the opening force at each door at substantial completion and shall include the record in the closeout submittals.
25.5.5 The hardware adjustment verification requirement shall be as indicated in the datasheet.
Hardware Adjustment Verificationselect
Installer adjusts and documents each opening
Certified architectural hardware consultant adjusts and documents each opening
Independent third party verifies and documents each opening
Not required
26 Field Testing
NOTE Laboratory testing qualifies the system as designed; field testing verifies the assembly as built, including the perimeter transitions that no laboratory specimen contains. Field water test pressures are set below laboratory pressures by AAMA 502 and AAMA 503 because the field specimen includes those transitions and the chamber seal itself. (26.1)
26.2 The laboratory tests required shall be as indicated in the datasheet.
Laboratory Performance Tests Requiredcheckbox
☑ Air infiltration per ASTM E283
☑ Static water penetration per ASTM E331
☐ Cyclic water penetration per ASTM E547
☑ Structural performance per ASTM E330
☐ Thermal transmittance and condensation resistance per AAMA 1503
☐ Inter-story drift per AAMA 501.4
☐ Missile impact and cyclic pressure per ASTM E1886 and ASTM E1996
☐ Sound transmission loss per ASTM E90
26.3 The field tests required shall be as indicated in the datasheet.
Field Performance Tests Requiredcheckbox
☑ Diagnostic water spray check per AAMA 501.2
☐ Field air leakage per ASTM E783
☐ Field water penetration per ASTM E1105
☐ Newly installed fenestration product test per AAMA 502
☐ Newly installed storefront system test per AAMA 503
26.4 The number of field test locations shall be as indicated in the datasheet.
Field Test Locationsrange
locations
1234568101520
Per drawings — field test plan (deferred by default)
26.5 Field test locations shall be selected by the Engineer of Record to represent typical construction, and shall include at least one door perimeter and at least one typical mid-elevation bay where those conditions occur on the project.
NOTE The diagnostic water spray check per AAMA 501.2 applies a calibrated nozzle at no pressure differential and is used to locate leakage at gaskets, joints, and transitions during construction. It does not measure performance and does not satisfy a requirement for chamber testing. (26.6)
26.7 Field testing shall be scheduled after the storefront and the adjoining envelope construction at the test location are complete, and before interior finishes conceal the interior face.
26.8 The field test agency shall be independent of the storefront installer, and shall be engaged and paid by the Owner unless the Contract Documents assign that engagement otherwise.
26.9 Where a field test fails, the Contractor shall repair the deficiency and shall repeat the failed test at the same location at the Contractor's cost until it passes.
26.10 Where a field test fails, the Contractor shall bear the cost of the retest, of the repair, and of removing and reinstating any adjoining work required to make the repair.
26.11 Where two consecutive tests fail at different locations, the Engineer of Record may direct additional test locations, and the Contractor shall bear the cost of those additional tests and of any resulting repairs.
26.12 A repair requiring disassembly of framing shall be documented in writing before it is performed, and shall not void the warranty on framing sections not disassembled.
27 Cleaning and Protection
27.1 Construction Protection
27.1.1 Installed framing, glass, and hardware shall be protected from damage by adjoining construction operations from installation through substantial completion.
27.1.2 Protection shall include guards at door stiles and at exposed mullions where material handling occurs, covering at glass in openings through which construction traffic passes, and removal of abrasive debris before any cleaning operation.
27.1.3 Welding, cutting, and grinding shall not be performed within 25 ft of installed glass unless the glass is shielded by a sacrificial blanket or screen.
NOTE Weld spatter and grinding debris fuse into the glass surface and cannot be removed, so the affected lite is replaced. The cost of that replacement late in a project is far larger than the cost of the shielding. (27.1.4)
27.1.5 Runoff from concrete, masonry, mortar, and fireproofing shall be kept off the storefront finish and glass, and any that reaches those surfaces shall be removed before it dries.
27.2 Final Cleaning
27.2.1 At substantial completion, framing, glass, gaskets, and hardware shall be cleaned in accordance with the framing manufacturer's and the finish manufacturer's published cleaning procedures.
27.2.2 Acidic cleaners, alkaline cleaners, abrasive cleaners, and solvents not identified as acceptable by the finish manufacturer shall not be used on any finished aluminum surface.
NOTE Cleaning agents that damage an anodic or organic finish do so on first contact, and the damage is a permanent change to the finish rather than a soil that can be cleaned off. (27.2.3)
27.2.4 Glass shall be cleaned with a non-abrasive glass cleaner accepted by the glass fabricator.
27.2.5 Razor scraping shall not be performed on a coated glass surface.
27.2.6 The Contractor shall replace glass and finished members that cannot be restored to the accepted appearance standard by the permitted cleaning methods.
28 Warranty
28.1 The framing manufacturer shall warrant the framing system against defects in materials and workmanship, including the cost of replacement components and the labor to install them, for the term indicated in the datasheet.
Warranty Term — Framing Systemrange
years
123510
28.2 The insulating glass unit fabricator shall warrant the units against seal failure, defined as visible obstruction, condensation, or film formation between the lites, for the term indicated in the datasheet.
Warranty Term — Insulating Glass Unit Sealrange
years
5101520
28.3 The finish applicator shall warrant the finish against color change and gloss loss beyond the limits of the applicable AAMA specification, against chalking beyond those limits, and against film adhesion loss, for the term indicated in the datasheet.
Warranty Term — Finishrange
years
51015202530
28.4 The sealant manufacturer shall warrant the perimeter sealant against adhesive failure, cohesive failure, and loss of movement capability for the term indicated in the datasheet.
Warranty Term — Perimeter Sealantrange
years
5101520
28.5 The hardware supplier shall warrant the entrance door hardware against defects in materials and workmanship for the term indicated in the datasheet.
Warranty Term — Entrance Door Hardwarerange
years
123510
28.6 Each warranty term shall begin at the date of substantial completion.
28.7 Warranties shall be written in the name of the Owner and shall be transferable for the remainder of their term.
28.8 Where a warranted component is repaired or replaced under warranty, the warranty on the repaired or replaced component shall run for a full new term from the date of that repair, or for the remainder of the original term, whichever is longer.
NOTE A re-warranty limited to the remainder of the original term expires almost immediately for a repair performed late in that term, which leaves the Owner with a new component and no coverage on it. (28.9)
28.10 Warranty repair shall include the cost of removing and reinstating adjoining work required for access, and the cost of repairing collateral damage caused by the warranted failure or by the repair.
28.11 Warranty exclusions shall be stated specifically in the warranty document, identifying the excluded cause and its scope.
28.12 A blanket exclusion that does not identify a specific cause shall not be accepted.
28.13 A field test performed under AAMA 502 or AAMA 503, and a repair performed to correct a field test failure, shall not be an excluded cause under any warranty furnished for this work.
29 Spare Parts and Maintenance Materials
29.1 The Contractor shall furnish spare parts and maintenance materials to the Owner at substantial completion, with a written inventory receipted by the Owner.
29.2 The spare parts furnished shall be as indicated in the datasheet.
Spare Parts Furnishedcheckbox
☑ Glazing gasket stock by profile
☑ Door perimeter weatherseal stock by profile
☐ Door bottom seal assemblies
☐ Setting blocks by size
☐ Threshold sealing strips
☑ Door closer adjustment tools
☐ Exit device strikes and mounting hardware
☐ Cylinders keyed to the Owner's system
☑ Touch-up coating in each furnished color
29.3 The quantity of gasket and weatherseal stock furnished, expressed as a percentage of the installed length of each profile, shall be as indicated in the datasheet.
Gasket and Weatherseal Spare Stock Quantityrange
% of installed length
123510
29.4 Spare gaskets, seals, and setting blocks shall be from the same production lot as the installed material where the material is lot-sensitive, and shall be labeled with the profile designation, the lot, and the date of manufacture.
NOTE Spare material stored beyond the shelf life published by its manufacturer is not usable for its intended repair, so the labeling is what lets the Owner know when the stock must be replaced rather than relied on. (29.5)
This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.
"Aluminum Entrances and Storefronts." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/aluminum-entrances-and-storefronts — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.