Clean Agent Fire Suppression Systems

Revision 4 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 11, 2026 +3 −4

Migrate datasheet deferrals to drawing_ref + default: deferred
Showing changes from Rev 3 to Rev 4 in Clean Agent Fire Suppression Systems.
Tag changes −Acceptance Testing−Clean Agent Suppression−Commissioning−Data Center−Fire Protection−Mission Critical
---
title: Clean Agent Fire Suppression Systems
483 unchanged lines
label: Discharge Piping
type: radio
options:
- "Per listed-system flow calculation — size, schedule, layout, and fittings as calculated"
default: "Per listed-system flow calculation — size, schedule, layout, and fittings as calculated"
+drawing_ref: "listed-system flow calculation"
+default: deferred
```
137 unchanged lines
label: Pressure Relief Vent Type
type: select
+drawing_ref: true
options:
- "Barometric (self-closing) relief damper"
- "Motorized relief damper interlocked to discharge"
- "Per drawings"
default: "Barometric (self-closing) relief damper"
```
130 unchanged lines
## The Owner shall be advised of the agent recharge source and the container hydrostatic-retest schedule so the system is maintained ready throughout its life.

View current revision