Dampproofing

Rev 1 · Updated Jun 18, 2026 · View history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

NOTE This standard covers the materials, surface preparation, and application of dampproofing on below-grade foundation walls, retaining walls enclosing interior space, and slabs-on-grade where the groundwater investigation confirms no hydrostatic pressure. (1.1)
NOTE Dampproofing resists the capillary movement and vapor transmission of soil moisture; it is not a pressure-resistant barrier. (1.2)
NOTE Dampproofing and waterproofing are different systems selected on a single threshold: the presence or absence of hydrostatic pressure. (1.2.1)
NOTE Dampproofing is a moisture-resistant treatment that slows the wicking and vapor diffusion of soil moisture through a foundation. It is applied at low film thickness, is not designed to bridge cracks, and is not designed to hold back standing water. Waterproofing, by contrast, is a continuous, crack-bridging, pressure-resistant membrane required wherever a head of water can stand against the structure. The International Building Code makes this distinction the governing decision: IBC Section 1805.2 permits dampproofing only where the groundwater investigation required by Section 1803.5.4 establishes that a hydrostatic condition does not exist. Where seasonal high groundwater can reach the structure, dampproofing is not permitted and a waterproofing system per Below Grade Waterproofing or Fluid Applied Waterproofing is required instead. (1.2.2)
1.2.3Dampproofing shall be applied only where a groundwater investigation conforming to IBC Section 1803.5.4 confirms that hydrostatic pressure does not act on the structure.
NOTE The 80% application this standard addresses is a residential or light-commercial basement or crawl-space foundation wall on free-draining soil, with a footing drain, treated with cold-applied asphalt emulsion over poured concrete and a 6 mil polyethylene vapor retarder beneath the slab. (1.2.4)
NOTE Dampproofing always works as part of a moisture-management assembly, not in isolation. (1.3)
NOTE The dampproofing coating, the granular backfill, and the foundation drainage system are interdependent; specifying one without the others undersupports the assembly. (1.3.1)
NOTE A dampproofing coating relieves capillary moisture but cannot survive a continuously saturated backfill. The coating is paired with free-draining backfill and a footing drain so that water is conducted away from the wall before it can build a head against it. Where backfill is poorly draining, where the water table is uncertain, or where a finished interior space below grade cannot tolerate any moisture, the correct response is to upgrade to waterproofing and a drainage composite, not to add coats of dampproofing. Coordinate the drainage side of this assembly with Foundation Drainage. (1.3.2)

1.4 Boundaries of this standard

NOTE This standard does not cover full membrane waterproofing for hydrostatic conditions, which is specified in Below Grade Waterproofing and Fluid Applied Waterproofing. (1.4.1)
NOTE This standard does not cover drainage composites, drain board, drain tile, or footing drains, which are specified in Foundation Drainage. (1.4.2)
NOTE This standard does not cover above-grade wall vapor retarders (Class I, II, and III), which are specified in Vapor Retarders. (1.4.3)
NOTE This standard does not cover integral crystalline waterproofing admixtures used as pressure-side waterproofing, which are specified in Below Grade Waterproofing. (1.4.4)
NOTE This standard does not cover roof dampproofing or above-grade flashing systems, which fall outside the below-grade envelope scope. (1.4.5)

2 Referenced Standards

2.1Materials, surface preparation, and application shall comply with the latest adopted edition of each of the following unless a specific edition is cited or unless the adopted building code references a different edition.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard Title
IBC Section 1805.2 International Building Code — Dampproofing
IBC Section 1803.5.4 International Building Code — Groundwater Table Investigation
IRC Section R406 International Residential Code — Foundation Waterproofing and Dampproofing
ASTM D449/D449M Asphalt Used in Dampproofing and Waterproofing
ASTM D1227/D1227M Emulsified Asphalt Used as a Protective Coating for Roofing
ASTM C887/C887M Packaged, Dry, Combined Materials for Surface Bonding Mortar
ASTM C920 Elastomeric Joint Sealants
ASTM E1745 Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
ASTM E1643 Installation of Water Vapor Retarders Used in Contact with Earth or Granular Fill under Concrete Slabs
ASTM D6135 Sampling and Acceptance of Asphalt Roofing Products

3 Submittals

3.1 Action submittals

3.1.1The Contractor shall submit the following action submittals for review before any dampproofing material is delivered to the site:
  • Product data for each dampproofing material, including the asphalt type or cement type, solids content, and the manufacturer's published application rate and coverage.
  • Manufacturer's printed application instructions, including substrate moisture limits, ambient and substrate temperature limits, and recoat or curing intervals.
  • Product data for protection board, drainage mat, or insulation used over the coating, where required.
  • Product data for the under-slab polyethylene vapor retarder, including the ASTM E1745 performance class and nominal thickness.
  • A statement of the wall extent to be treated, identifying the top-of-footing elevation and the finished-grade line, so the full treated height is fixed before work begins.
Action submittals requiredcheckbox
Dampproofing material product data
Manufacturer application instructions
Protection board / drainage mat product data
Under-slab vapor retarder product data and ASTM E1745 class
Statement of treated wall extent (footing to grade)

3.2 Informational submittals

3.2.1The Contractor shall submit the following informational submittals:
  • The groundwater investigation report, or a reference to the geotechnical report section, confirming that no hydrostatic condition exists per IBC Section 1803.5.4.
  • Material safety / safety data sheets for solvent-based and hot-applied bituminous products.
  • Certification that the delivered materials conform to the referenced ASTM specifications, with ASTM D6135 sampling where the Engineer requires lot verification.
Informational submittals requiredcheckbox
Groundwater investigation / geotechnical confirmation of no hydrostatic condition
Safety data sheets for bituminous products
Material conformance certification

3.3 Closeout submittals

3.3.1The Contractor shall submit the following closeout submittals:
  • Photographic record of the prepared substrate and the completed coating before backfill, showing the coated extent and the footing-wall cove.
  • Documentation of the protection board or drainage mat installation before backfill, where required.
Closeout submittals requiredcheckbox
Pre-backfill photographic record of coating and extent
Protection board / drainage mat installation record

4 Quality Assurance

4.1The installer shall be experienced in below-grade dampproofing and shall apply each material in accordance with the manufacturer's printed instructions for the specific substrate and exposure.
4.1.1A single dampproofing material and a single manufacturer shall be used for the entire foundation unless the drawings expressly permit a transition.
4.1.2The Contractor shall not apply dampproofing over a substrate that has not been inspected and accepted for moisture, temperature, and surface condition.
4.1.3Form-tie holes, honeycomb, tie snaps, and surface voids in poured concrete shall be patched and accepted before any dampproofing coating is applied.
4.1.4Parging of unit masonry shall be inspected and accepted before the dampproofing coating is applied over it.

4.2 Mock-ups and field verification

4.2.1Where the project includes more than 2,000 sq ft of dampproofed wall, the Contractor should apply a mock-up panel of not less than 100 sq ft demonstrating the coating, the application rate, and the footing cove for the Engineer's acceptance before general application.
4.2.2The dry-film or wet-film coverage of the applied coating shall be verified against the manufacturer's published application rate at intervals agreed with the Engineer.

5 Environmental and Service Conditions

5.1Dampproofing materials and their application are sensitive to substrate moisture, ambient temperature, and the aggressiveness of the backfill; these conditions shall be confirmed before application.
5.1.1Cold-applied asphalt emulsions and cementitious coatings shall not be applied to a frozen, frost-bound, or visibly wet substrate.
NOTE Most cold-applied asphalt emulsions and water-based coatings require a clean, dry, frost-free substrate and an ambient and substrate temperature above approximately 4 °C (40 °F) and rising, so that the emulsion can break and cure. Applying these products to a wet or frozen wall is the leading cause of adhesion failure and the contractor disputes that follow. Hot-applied asphalt tolerates cooler substrates but introduces its own hazards from the application temperature near 93 °C (200 °F). Confirm the manufacturer's limits and the expected site conditions before selecting the material. (5.1.2)
5.1.3The minimum substrate and ambient application temperature shall be as specified, and not lower than the manufacturer's published limit.
Minimum substrate / ambient temperature at applicationrange
°C
015
Default: 4 °C
5.1.4The substrate shall be free of standing water, frost, and visible surface moisture at the time of application.
5.1.5Concrete shall be cured for the period specified before dampproofing is applied, and not less than the manufacturer's published minimum cure.
Minimum concrete cure before dampproofingselect
3
7
14
28
5.1.6The aggressiveness of the soil and backfill shall be confirmed; where sulfates or other aggressive constituents are present, the coating shall be a type compatible with that exposure.

6 Material Selection

NOTE The dampproofing material is selected from three families — bituminous, cementitious, and under-slab polyethylene — based on the substrate, the exposure, and whether the surface is vertical or horizontal. (6.1)
NOTE Bituminous dampproofing comprises hot-applied asphalt, cold-applied asphalt emulsion, and fibrous (mineral-reinforced) asphalt; these are the common treatments for vertical foundation walls. (6.1.1)
NOTE Cementitious dampproofing comprises acrylic-modified cement slurry and surface-bonding mortar; these are favored on unit masonry and where a paintable, non-bituminous surface is wanted. (6.1.2)
NOTE Polyethylene sheet dampproofing is used horizontally beneath slabs-on-grade as an under-slab vapor retarder; it is not a wall coating. (6.1.3)
6.1.4The dampproofing material family shall be as specified for each surface.
Dampproofing material family (walls)radio
Cold-applied asphalt emulsion
Hot-applied asphalt (ASTM D449 Type C)
Fibrous asphalt coating
Acrylic-modified cement slurry
Surface-bonding mortar (ASTM C887)

6.2 Bituminous dampproofing

6.2.1Hot-applied asphalt for vertical wall dampproofing shall conform to ASTM D449 Type C (steep asphalt).
NOTE ASTM D449 classifies dampproofing asphalt by softening point and flow. Type A (dead-level) and Type B (flat) are formulated for horizontal and low-slope surfaces and will sag or flow on a wall. Type C (steep asphalt), with a softening point of approximately 85 °C to 96 °C (185 °F to 205 °F), is the correct selection for vertical foundation walls because it holds a film on a vertical face without running. Specifying Type A on a wall — a common error — produces a coating that slumps and thins as it warms. (6.2.2)
6.2.3Hot-applied asphalt for vertical surfaces shall be ASTM D449 Type C; Type A and Type B shall not be used on vertical walls.
Hot-applied asphalt type (ASTM D449)radio
Type C (steep) — vertical walls
Type B (flat) — low-slope horizontal
Type A (dead-level) — horizontal
6.2.4Cold-applied asphalt emulsion shall conform to ASTM D1227 and shall be applied at the manufacturer's published coverage rate per coat.
6.2.5The number of coats of bituminous coating shall be as specified; a two-coat system shall be used for more severe soil moisture exposure.
Number of bituminous coatsradio
One coat
Two coats
6.2.6The cold-applied emulsion coverage rate per coat shall be as specified and not less than the manufacturer's published minimum.
Cold-applied emulsion coverage rate (per coat)range
sq ft/gal
50200
Default: 100 sq ft/gal
6.2.7Fibrous asphalt coating shall be applied by trowel or heavy brush at the manufacturer's published rate.
6.2.8The fibrous asphalt application rate shall be as specified and not leaner than approximately 1 gal per 50 sq ft.
Fibrous asphalt application raterange
sq ft/gal
2575
Default: 50 sq ft/gal

6.3 Cementitious dampproofing

6.3.1Acrylic-modified cement slurry shall be applied at not less than 3 lb per sq yd, in one or two coats by brush or spray, as specified.
NOTE The acrylic-modified cement family — sometimes called a cementitious coating or a polymer-modified slurry — is an IBC-recognized dampproofing material for masonry. IBC Section 1805.2 cites an application of 3 lb per sq yd (about 1.63 kg/m²) as the reference rate. It is favored where a non-bituminous, paintable, light-colored surface is wanted on the interior or exterior, and it bonds well to a properly prepared masonry or concrete face. It is not a crack-bridging membrane and is not a substitute for waterproofing. (6.3.2)
6.3.3Acrylic-modified cement slurry shall be applied at not less than 3 lb per sq yd over the full treated area.
Acrylic-modified cement application raterange
lb/sq yd
26
Default: 3 lb/sq yd
6.3.4Surface-bonding mortar used as dampproofing shall conform to ASTM C887 and shall be trowel-applied in a single coat of nominal 3 mm (1/8 in.) thickness to both faces of dry-stacked masonry, or to the exterior face where the wall is conventionally laid.
6.3.5Surface-bonding mortar shall be applied at the nominal thickness specified and not less than 3 mm (1/8 in.).
Surface-bonding mortar coat thicknessrange
mm
36
Default: 3 mm

6.4 Under-slab polyethylene

6.4.1Under-slab polyethylene shall conform to ASTM E1745 and shall be not less than 6 mil (0.15 mm) thick, with the performance class as specified.
NOTE IBC Section 1805.2.3 and IRC R406 permit a minimum 6 mil polyethylene sheet beneath slabs-on-grade as the floor dampproofing element. ASTM E1745 grades these sheets into Classes A, B, and C by tensile strength and puncture resistance; the 6 mil residential default corresponds to the lowest class, while commercial slabs and slabs receiving moisture-sensitive flooring are commonly specified at 10 mil or 15 mil (Class A) for greater durability during placement. The sheet is installed in direct contact with the prepared base course, with joints lapped not less than 152 mm (6 in.) and sealed per ASTM E1643. (6.4.2)
6.4.3Under-slab polyethylene shall be not less than 6 mil (0.15 mm) thick.
Under-slab polyethylene thicknessselect
6
10
15
6.4.4The under-slab vapor retarder performance class shall be as specified.
Under-slab vapor retarder class (ASTM E1745)radio
Class C
Class B
Class A
6.4.5Joints in the under-slab polyethylene shall be lapped not less than 152 mm (6 in.) and sealed in accordance with ASTM E1643.
Under-slab polyethylene minimum joint laprange
in
612
Default: 6 in

7 Extent of Application

7.1The treated extent shall run continuously from the top of the footing to the finished-grade line on the exterior face of every wall enclosing interior space below grade; the height shall be fixed on the drawings, not left to the contractor.
NOTE The single most common dampproofing RFI is "how high does the coating go?" The answer is fixed by the relationship between the top-of-footing elevation and the finished-grade line: dampproofing covers the full earth-retaining height of the wall on its exterior face, from the top of the footing up to grade, plus a cove treatment at the footing-wall junction. Showing both elevations on the foundation drawing removes the ambiguity. Where a wall encloses interior space, the full earth-retained height is treated; where a wall is a crawl-space stem only, the extent still runs footing to grade but the interior treatment may differ. (7.2)
7.2.1Dampproofing shall extend from the top of the footing to the finished-grade line on the exterior earth face of each below-grade wall.
7.2.2A cove or fillet of compatible material shall be formed at the footing-wall junction so the coating turns the inside corner without a discontinuity.
7.2.3The top-of-footing elevation and the finished-grade line that fix the treated height shall be as indicated on the drawings.
Treated wall extentradio
Top of footing to finished grade (full earth-retained height)
Top of footing to underside of slab (crawl-space stem)
Full wall height (footing to top of wall)
Per drawings — foundation section — top-of-footing elevation and grade line
7.2.4Where the interior face of a wall enclosing finished space requires treatment, the interior extent shall be as indicated on the drawings.
NOTE The location and routing of the treated extent — which walls, which faces, and the grade line itself — are coordination items that can never be reduced to a catalog value, so they are fixed on the drawings rather than in a datasheet field. See foundation plan and sections — walls and faces to be dampproofed. (7.2.5)

8 Surface Preparation

NOTE Surface preparation is where most dampproofing failures begin: an unpatched form-tie hole or an unparged masonry face is a direct moisture path that no thickness of coating will close. (8.1)

8.2 Poured concrete walls

8.2.1Form-tie holes, snap-tie pockets, honeycomb, and surface voids shall be filled and struck flush before any dampproofing coating is applied.
NOTE IBC Section 1805.2.2 requires that the concrete surface be prepared and that tie holes be sealed before dampproofing. A snapped form tie leaves a through-wall void on the line of least resistance for moisture; coating over it merely hides it. Fill tie holes and voids with a compatible bituminous patching material or an approved non-shrink or cementitious patch, struck flush, and allow the patch to cure before coating. (8.2.2)
8.2.3Form-tie holes and pockets shall be filled with a bituminous patching material or an approved sealant or patch compatible with the dampproofing coating.
8.2.4Fins, projections, and form offsets shall be removed and the surface left reasonably smooth and free of laitance, form-release agent, and loose material.
8.2.5Patched areas shall be cured before the dampproofing coating is applied over them.

8.3 Unit masonry walls

8.3.1Unit masonry shall receive a Portland cement parge coat not less than 9.5 mm (3/8 in.) thick, coved at the footing, before the dampproofing coating is applied.
NOTE A concrete masonry face is a field of mortar joints and open block voids; a thin coating cannot bridge that texture. IBC Section 1805.2.1 and IRC R406.1 therefore require unit masonry to be parged with not less than a 3/8 in. Portland cement mortar coat, coved at the footing, and then dampproofed. Parging is a surface-preparation step that belongs to this work unless the drawings assign it to the masonry trade; omitting it and coating bare block is a non-compliant, leak-prone shortcut. Where parging is performed by the masonry trade, coordinate the responsibility on the drawings so it is neither duplicated nor dropped. (8.3.2)
8.3.3The parge coat shall be Portland cement mortar not less than 9.5 mm (3/8 in.) thick.
Masonry parge coat thicknessrange
in
0.3750.75
Default: 0.375 in
8.3.4The parge coat shall be coved at the footing-wall junction to form a continuous transition for the coating.
8.3.5The parge coat shall be moist-cured and shall cure before the dampproofing coating is applied over it.
NOTE Where surface-bonding mortar conforming to ASTM C887 is used as the dampproofing material, a separate parge coat is not required because the bonding mortar performs the same function. (8.3.6)

9 Application

9.1The coating shall be applied continuously and at the specified rate over the prepared, accepted substrate, and shall be protected from damage until backfill.
9.1.1The dampproofing coating shall be applied continuously over the full treated extent, free of pinholes, holidays, voids, and thin spots.
9.1.2The coating shall be applied at not less than the specified rate or film thickness, verified against the manufacturer's published coverage.
9.1.3Each coat of a multi-coat system shall cure or set for the manufacturer's published interval before the next coat is applied.
9.1.4The coating shall be carried into the footing cove and lapped onto the footing top so the wall-footing transition is continuous.
9.1.5Cold-applied emulsion and cementitious coatings shall not be applied when rain, freezing temperatures, or condensation is expected before the coating has cured.
9.1.6Penetrations through the wall below grade shall be sealed and the coating shall be carried tight to each penetration.

9.2 Joints in precast and panelized foundations

9.2.1Joints between precast concrete foundation panels shall be sealed with an elastomeric joint sealant conforming to ASTM C920, Type S or M, Grade NS, Class 25, Use NT, before dampproofing is applied across the joint.
9.2.2Precast panel joints shall be sealed with an ASTM C920 sealant of the class and use specified.
Precast panel joint sealant (ASTM C920)select
Type S, Grade NS, Class 25, Use NT
Type M, Grade NS, Class 25, Use NT
Type M, Grade NS, Class 25, Use M

9.3 Protection of the coating

9.3.1Protection board or a drainage mat shall be installed over the cured coating where the backfill contains aggregate larger than 19 mm (3/4 in.) or where mechanical compaction will occur within about 1.5 m (5 ft) of the wall.
NOTE A dampproofing coating is thin and is easily gouged by angular backfill or torn by a plate compactor working close to the wall. Damage during backfill is one of the leading callback causes for below-grade moisture. A protection course — a rigid protection board, a board of rigid insulation, or a dimpled drainage mat — is installed over the cured coating before backfill to take that abuse. A dimpled drainage mat additionally creates a drainage plane; where a drainage plane is required as part of the moisture-management assembly, coordinate it with Foundation Drainage rather than relying on the protection board alone. (9.3.2)
9.3.3A protection course shall be installed over the cured coating where required by the backfill or compaction conditions.
Protection course over coatingradio
None
Rigid protection board
Rigid insulation board (min. 12 mm)
Dimpled drainage mat
9.3.4The protection course shall be installed only after the coating has cured sufficiently to resist displacement.
9.3.5Backfill shall not be placed until the coating, and the protection course where required, have been inspected and accepted.

10 Coordination with Foundation Drainage

NOTE Dampproofing relieves capillary moisture; the footing drain and free-draining backfill relieve the water that would otherwise build a head against the wall. The two are specified and detailed together. (10.1)
10.1.1A footing drain and free-draining backfill conforming to Foundation Drainage shall be provided wherever this dampproofing standard is applied below grade.
10.1.2Where the drainage investigation or the soil cannot reliably keep a head of water off the wall, dampproofing shall not be used and a waterproofing system per Below Grade Waterproofing shall be specified instead.
10.1.3The dampproofing coating and the drainage composite or drain mat shall be sequenced so neither damages the other during installation and backfill.

11 Inspection

11.1The completed coating shall be inspected before it is concealed by backfill or slab placement, because no remedy short of excavation is available afterward.
11.1.1The Contractor shall request inspection of the completed coating and of the protection course, where required, before any backfill is placed.
11.1.2The under-slab polyethylene shall be inspected for continuity, lap, and seal before reinforcement and concrete are placed over it.
11.1.3Any holiday, tear, or thin area found at inspection shall be repaired with the same material, lapped onto sound coating, before the work is concealed.

12 Delivery, Storage, and Handling

12.1Bituminous and cementitious dampproofing materials shall be delivered, stored, and handled so they are not contaminated, frozen, or degraded before use.
12.1.1Materials shall be delivered in the manufacturer's original, labeled, unopened containers.
12.1.2Solvent-based and emulsion materials shall be stored within the manufacturer's temperature range and protected from freezing.
12.1.3Polyethylene sheet shall be stored protected from prolonged sunlight and mechanical damage.
12.1.4Materials past the manufacturer's shelf-life or showing separation, skinning, or freeze damage shall not be used.

13 Warranty

NOTE Dampproofing is a low-cost, concealed treatment whose warranty is necessarily modest; a long warranty is the signature of waterproofing, not dampproofing. (13.1)
13.1.1The Contractor shall warrant the dampproofing application against defects in materials and workmanship for the period specified.
Workmanship warranty periodselect
1
2
5
13.1.2Where a manufacturer offers a material warranty for the dampproofing product, it shall be transferred to the Owner.
13.1.3A warranty against water intrusion under hydrostatic pressure shall not be implied by this work, because dampproofing is not a pressure-resistant system.

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Dampproofing." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/dampproofing — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.