Dust and Fume Collection Systems

Rev 1 · Updated Jun 14, 2026 · View history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

NOTE This standard covers the design, selection, specification, installation, and field testing of fixed industrial and laboratory-process dust collection and fume exhaust systems that capture particulates, mists, vapors, and fumes at the source and convey them to air-cleaning equipment before discharge. (1.1)
NOTE A dust and fume collection system is a local exhaust ventilation (LEV) system serving production equipment, not occupied building space. It comprises capture devices at the point of generation, conveying ductwork sized to keep particulate entrained, an air-moving fan, a primary air-material separator that removes the contaminant, and the controls and instrumentation that keep the system in balance. (1.2)
1.3The system shall capture airborne contaminants at the point of generation in sufficient quantity to maintain employee exposures at or below the applicable OSHA Permissible Exposure Limit.
1.4The system shall convey captured contaminant to the air-cleaning equipment without settling or accumulation in the ductwork.
1.5The system shall discharge cleaned air at an emission concentration compliant with the governing air-quality permit and, where air is returned to occupied space, with the recirculation limits of this standard.
NOTE Combustible-dust streams and non-combustible-particulate streams are both within scope; a combustible stream invokes the additional hazard-analysis, explosion-protection, and isolation requirements of this standard. (1.6)
NOTE Welding fume extraction units, grinding fume collectors, downdraft tables, and central process vacuum systems are within scope as fixed source-capture configurations. (1.7)
NOTE The boundary between this standard and adjacent systems is the contaminant stream, not the room. (1.8)
NOTE Grease-laden kitchen exhaust is excluded; it requires listed hoods, grease filters, fire suppression, and NFPA 96 compliance and is covered by Kitchen Exhaust Systems. (1.8.1)
NOTE General building supply, return, and exhaust fans for occupant ventilation are excluded and are covered by Hvac Fans; pressure-classed HVAC distribution ductwork is covered by Hvac Ductwork. (1.8.2)
NOTE Laboratory bench fume hoods — listed, walk-up enclosures with a sash — and their VAV-controlled exhaust are excluded and are covered by Laboratory Exhaust And Fume Hoods; a source-capture arm or backdraft hood over a grinder or welding table is within scope here. (1.8.3)
NOTE Fixed area gas detection and alarm for toxic or flammable gases is excluded and is covered by Gas Detection Systems. (1.8.4)
NOTE Process instrument impulse tubing and sensor installation at monitoring points are excluded and are covered by Instrument Installation And Tubing; identification labeling of mechanical piping and equipment is covered by Mechanical Identification. (1.8.5)

2 Referenced Standards

2.1Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
NOTE NFPA 660 (2025) consolidated and superseded the six prior NFPA combustible-dust standards — NFPA 61, 484, 652, 654, 655, and 664 — effective December 2024; specifications drafted before that date and citing the individual standards shall be updated to NFPA 660. (2.3)
Standard Title
NFPA 91 (2026) Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Particulate Solids
NFPA 660 (2025) Standard for Combustible Dusts and Particulate Solids
ANSI/ASSP Z9.2 (2018) Fundamentals Governing the Design and Operation of Local Exhaust Ventilation Systems
ANSI/AIHA Z9.5 (2022) American National Standard for Laboratory Ventilation
ANSI/ASSP Z9.9 (2016) Portable Ventilation Systems
ANSI/ASHRAE 199 (2016) Method of Testing the Performance of Industrial Pulse-Cleaned Dust Collectors
ASHRAE 52.2 (2017) Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size
OSHA 29 CFR 1910.94 Ventilation — Abrasive Blasting, Grinding, Polishing, and Buffing Operations
OSHA 29 CFR 1910.1000 Air Contaminants (Permissible Exposure Limits)
OSHA 29 CFR 1910.1053 Respirable Crystalline Silica
ACGIH Industrial Ventilation: A Manual of Recommended Practice for Design (31st ed., 2023)
UL 508A Standard for Industrial Control Panels
NFPA 70 (NEC 2023) National Electrical Code, Article 502 — Class II (Combustible Dust) Locations
IMC 2024 International Mechanical Code, Section 510 — Hazardous Exhaust Systems
NOTE The ACGIH Industrial Ventilation Manual is an engineering reference, not a code, but is the dominant design authority for hood geometry, capture and transport velocities, and system balancing, and is frequently invoked by the AHJ during permit review. (2.4)

3 Submittals

3.1 Action Submittals

3.1.1The Contractor shall submit the following action submittals for review before fabrication or ordering:
  • Product data for each collector, fan, capture device, isolation valve, and explosion-protection device.
  • Shop drawings showing duct layout, branch and main sizing, transport velocities, hood geometry and capture velocities, and equipment locations.
  • System calculations: total system airflow, duct static pressure, fan operating point at the design dirty-state static pressure, air-to-cloth ratio, and capture-velocity verification at each hood.
  • The Dust Hazard Analysis (DHA) for any combustible-dust stream, with deflagration-vent area, isolation, and suppression sizing per NFPA 660.
  • Make-up air coordination data demonstrating that replacement air equals or exceeds total exhaust volume.
  • Manufacturer's explosion-protection device listings and deflagration-vent calculations.
Action submittals requiredcheckbox
Collector and fan product data
Capture device and hood product data
Isolation and explosion-protection device data
Duct layout and sizing shop drawings
Airflow, static pressure, and fan operating-point calculations
Air-to-cloth ratio calculation
Capture-velocity verification at each hood
Dust Hazard Analysis (combustible streams)
Make-up air coordination data

3.2 Informational Submittals

3.2.1The Contractor shall submit the following informational submittals:
  • Factory performance test report per ANSI/ASHRAE 199 for pulse-cleaned collectors.
  • Filter media data sheets including efficiency rating, fabric, finish, and chemical-compatibility data.
  • NEC Article 502 electrical area classification drawing where a combustible-dust area is present.
  • Welder's qualifications and weld procedures for ductwork fabrication where welded duct is specified, per Welding Requirements.
Informational submittals requiredcheckbox
ANSI/ASHRAE 199 factory performance test report
Filter media data sheets
NEC Article 502 area classification drawing
Duct welding qualifications and procedures

3.3 Closeout Submittals

3.3.1The Contractor shall submit the following closeout submittals before final acceptance:
  • Field commissioning test report: pitot-traverse capture velocities, duct transport velocities, total system CFM, and total static pressure.
  • The 30-day re-test report confirming sustained performance after initial operation.
  • Operation and maintenance manuals, including filter-change procedure and combustible-dust hopper cleanout and lockout procedure.
  • Record drawings reflecting as-installed duct routing and equipment locations.
Closeout submittals requiredcheckbox
Field commissioning test report
30-day re-test report
Operation and maintenance manuals
Record drawings

4 Quality Assurance

NOTE A Dust Hazard Analysis is the gateway deliverable for any combustible-dust system. NFPA 660 §7 requires the DHA to be completed before design proceeds, because the analysis outputs — the dust Kst value, deflagration class, and ignition-sensitivity data — drive the venting, isolation, and suppression that the collector must be built around. Specifying a collector without a DHA is the most common cause of AHJ rejection and the most consequential liability exposure on a combustible-dust project. (4.1)
4.2A Dust Hazard Analysis conforming to NFPA 660 §7 shall be completed and accepted before the collector for any combustible-dust stream is sized or ordered.
4.3The dust shall be classified as combustible or non-combustible by laboratory test data or by an authoritative reference acceptable to the AHJ.
Dust combustibility classificationradio
Non-combustible particulate
Combustible dust — DHA required
Combustible dust deflagration class (from Kst)radio
St 0 — non-explosible (Kst = 0)
St 1 — Kst less than 200 bar-m/s
St 2 — Kst 200 to 300 bar-m/s
St 3 — Kst greater than 300 bar-m/s
4.4The installing contractor shall be experienced in industrial exhaust and dust collection system fabrication and shall employ welders qualified to the procedures referenced in Welding Requirements where welded ductwork is specified.
4.5Each collector and integral control panel shall bear the listing marks required by its application: UL 508A for the industrial control panel and the dust-ignitionproof or explosion-proof listings of NEC Article 502 where installed in a classified area.

5 Environmental and Service Conditions

NOTE Indoor versus outdoor collector placement is a primary design driver, not a field convenience. Outdoor placement removes the collector from the building electrical classification, simplifies deflagration venting to a safe outdoor location, and isolates a combustible-dust hazard from occupied space — but it imposes freeze protection on the filter media and on the pulse-cleaning compressed-air supply in cold climates. Indoor placement avoids weather exposure but pulls the building's electrical classification, venting path, and fire protection into the equipment room design. (5.1)
5.2The collector location, hopper discharge, and pulse-cleaning air supply shall be protected against freezing where the design ambient falls below 35°F.
NOTE Make-up air is a system requirement, not an accessory. Exhausting large volumes from a shop without replacing them negatively pressurizes the space, which collapses hood capture velocities, pulls exterior doors open, and backdrafts combustion appliances. Without adequate replacement air, hood capture collapses and the system cannot achieve its design performance. (5.3)
5.4Make-up air shall be provided in a volume equal to or greater than the total system exhaust volume.
5.5The duct material shall be selected for the contaminant stream; standard galvanized steel fails rapidly in hygroscopic, acidic, or high-moisture service, where stainless steel or epoxy-lined duct is required.
Collector installation locationradio
Indoors, within building electrical classification
Outdoors, weather-protected
Conveying duct materialselect
Galvanized steel (dry, non-corrosive dust)
Carbon steel, welded (abrasive dust)
Stainless steel 304 (moist, mild-corrosive)
Stainless steel 316 (acidic, chloride-bearing)
Epoxy-lined carbon steel (hygroscopic dust)
Air recirculation strategyradio
Exhaust to outdoors, no recirculation
Recirculate to occupied space with secondary after-filter

6 Capture Devices and Hoods

NOTE Capture occurs at the hood, and a system can be no better than its hoods. The hood must develop enough velocity at the point of generation to overcome the particle's escape velocity and the room cross-drafts, then taper into the duct without losing entrainment. Hood geometry and capture velocity follow the ACGIH Industrial Ventilation Manual and ANSI Z9.2; these are the figures the AHJ checks first. (6.1)
6.2Each hood shall develop the design capture velocity at the most distant point of contaminant generation it serves.
6.3Hood and duct transition geometry shall conform to the ACGIH Industrial Ventilation Manual to minimize entry loss and maintain transport velocity into the branch.
6.4A source-capture arm or backdraft hood for welding and grinding shall be positioned to draw fume away from the operator's breathing zone.
Capture device typeselect
Enclosing hood / booth
Capturing hood (side-draft)
Downdraft table
Backdraft hood
Articulated source-capture arm
Receiving hood (canopy, buoyant streams only)
Design capture velocity at point of generationrange
FPM
502000
100150200500
Default: 150 FPM

7 Conveying Ductwork

NOTE Transport velocity is the single parameter that keeps a dust system alive. Below the minimum transport velocity for the dust, particulate drops out of the airstream, settles in horizontal runs, plugs the duct, and — for a combustible dust — builds a secondary deflagration fuel layer inside the system. Velocity is set by the heaviest, coarsest particle the branch carries, not by an average. (7.1)
7.2Conveying ductwork shall maintain, at every point, the minimum transport velocity required for the dust it carries.
7.3Round duct shall be used for conveying runs.
7.4Rectangular duct shall not be used where it would create low-velocity corners that permit settling.
7.5Horizontal duct runs shall be minimized and shall include cleanout access at changes of direction.
7.6The system static pressure shall be calculated at the design dirty-state condition of the collector, not at clean-filter conditions, so the fan and motor are sized for the loaded system.
Minimum duct transport velocity by dust typerange
FPM
30005500
3500400045005000
Default: 4000 FPM
Duct construction joining methodradio
Welded seams (abrasive or combustible dust)
Clamp-together with gaskets
Flanged with full-face gaskets

8 Air-Moving Fan

NOTE The fan must be selected at the loaded operating point, in spark-resistant construction where the stream is flammable. A fan chosen off its clean-air curve will, once the collector loads up and back-pressure rises, slide left of peak efficiency and can overload the motor. For combustible or flammable streams the fan is also an ignition source unless built to a spark-resistant construction class, and it is placed downstream of the collector ("clean-air side") so it never handles the raw dust. (8.1)
8.2The fan shall be selected to deliver the design airflow at the total system static pressure calculated at the design dirty-state condition.
8.3The fan serving a combustible or flammable stream shall be of spark-resistant construction per the AMCA classification required by the DHA.
8.4The fan serving a combustible or flammable stream shall be located on the clean-air side of the collector.
8.5The fan motor shall not be overloaded at any point on the system operating curve between clean-filter and maximum-allowable-differential-pressure conditions.
Fan typeselect
Centrifugal, backward-inclined (clean air)
Centrifugal, radial-blade (material handling)
Centrifugal, radial-tip (high static)
Axial (low static, high volume)
Fan spark-resistant construction class (AMCA)radio
None (non-combustible stream)
Type A (all flow-path parts non-ferrous)
Type B (non-ferrous wheel or rubbing-point ring)
Type C (offset construction, no rubbing of ferrous parts)
Fan static pressurerange
in. w.g.
450
8101220
Default: 10 in. w.g.
Fan motor speed controlradio
Fixed-speed across-the-line
Variable frequency drive (VFD) with pressure feedback
Fan motor horsepowerrange
HP
1500
52575200
Default: 25 HP

9 Air-Material Separator

NOTE The collector is the heart of the system, and its type is the central selection. The choice among pulse-jet cartridge, pulse-jet baghouse, cyclone, wet scrubber, and electrostatic precipitator is driven by particle size, dust load, moisture, stickiness, temperature, and the combustibility of the stream. The pulse-jet cartridge collector is the 80% case for general industrial and welding fume; baghouses dominate high-volume wood, grain, and chemical dust; cyclones serve as coarse pre-separators ahead of a fabric filter; wet scrubbers quench sticky, hygroscopic, or readily ignitable dusts. (9.1)
9.2The collector type shall be selected for the particle-size distribution, dust load, moisture, temperature, and combustibility of the stream it serves.
9.3A cyclone or spark-trap pre-separator shall be installed upstream of any fabric filter that serves grinding, cutting, or other spark-generating operations, so that a single hot particle cannot reach and ignite the filter media.
Primary collector typeselect
Pulse-jet cartridge collector
Pulse-jet baghouse
Cyclone pre-separator + downstream fabric collector (two-stage)
Single-stage cyclone (coarse dust only)
Wet venturi scrubber
Electrostatic precipitator

9.4 Air-to-Cloth Ratio

NOTE The air-to-cloth (A/C) ratio is the airflow per unit of filter media, and it sizes the collector. Too aggressive a ratio drives particulate into the media, blinds the filter, and spikes the differential pressure at startup. A persistent error is using the gross media area for a cartridge collector instead of the net can-velocity area — the cartridges nest closely and the airflow squeezes through a much smaller effective face, so a gross-area calculation under-sizes the collector and it blinds in service. (9.5)
9.6The air-to-cloth ratio for a cartridge collector shall be computed on the net (can-velocity) media area, not the gross media area.
Air-to-cloth ratio — pulse-jet baghouse (gross)range
ft³/min per ft²
310
468
Default: 6 ft³/min per ft²
Air-to-cloth ratio — cartridge collector (net)range
ft³/min per ft²
14
1.523
Default: 2 ft³/min per ft²

9.7 Filter Media

NOTE Filter media selection balances efficiency against the dust's physical and chemical character. Polyester felt is the general-purpose default; woven fiberglass tolerates high temperature; a PTFE membrane gives surface filtration and easy cake release for fine or sticky dust; spunbond polyester suits cartridge pleats. The MERV efficiency required is set by where the cleaned air goes and how toxic the contaminant is — nuisance dust recirculated to occupied space needs a higher floor than dust exhausted outdoors, and toxic or carcinogenic dust (silica, hexavalent chromium, lead) demands MERV 16-plus or true HEPA. (9.8)
9.9The filter media shall be compatible with the temperature, moisture, and chemistry of the contaminant stream.
9.10The collector filter media efficiency shall be no less than the MERV rating required for the contaminant's toxicity and the air's destination.
Filter mediaselect
Polyester felt (general purpose)
Spunbond polyester (cartridge pleat)
Woven fiberglass (high temperature)
PTFE membrane (fine or sticky dust, surface filtration)
Aramid felt (elevated temperature)
Collector filter media efficiency (MERV)select
MERV 11 (nuisance dust, exhaust outdoors)
MERV 14 (fine metallic or wood dust)
MERV 16 (recirculation to occupied space)
HEPA, MERV 17 to 20 (toxic or carcinogenic dust)

9.11 Filter Cleaning and Differential Pressure

NOTE Pulse-jet cleaning fires a brief reverse blast of dry compressed air through each filter element to release the dust cake into the hopper, and it is governed by differential pressure across the media. The clean filter runs at a low pressure drop; as the cake builds the drop climbs, and a pressure switch triggers the pulse cycle at a setpoint. Wet or oily compressed air ruins media and freezes pulse valves, so the supply must be dry. A high-differential-pressure alarm is mandatory — without it the operator has no warning of filter breakthrough or a plugging duct. (9.12)
9.13A continuous differential-pressure monitor across the collector media shall be provided, with a high-differential-pressure alarm.
9.14The compressed-air supply for pulse cleaning shall be dry, with a pressure dew point below 35°F.
9.15The compressed-air supply for pulse cleaning shall be regulated to the manufacturer's required pulse pressure.
9.16The pulse-cleaning cycle shall be initiated on differential-pressure setpoint, not on a fixed timer alone, so cleaning frequency tracks the actual dust load.
Pulse-cleaning compressed-air supply pressurerange
PSI
80120
90100110
Default: 100 PSI
Clean-filter differential pressure (operating)range
in. w.g.
16
234
Default: 3 in. w.g.
High-differential-pressure alarm setpointrange
in. w.g.
612
810
Default: 10 in. w.g.

9.17 Dust Discharge and Hopper

NOTE Cleaned dust drops into a hopper and must be removed continuously or in controlled batches without breaking the system's air seal. A rotary airlock valve is the workhorse: it discharges the hopper while maintaining the pressure boundary and, for a combustible dust, doubling as a flame-isolation device. Hopper cleanout and bag-change maintenance is where a combustible-dust and confined-space exposure event most often occurs, so the design must include lockout provisions and a cleanout detail. (9.18)
9.19A discharge device shall remove collected dust from the hopper while maintaining the system's air seal.
9.20The collector shall include hopper cleanout access and lockout provisions so that bag-change and hopper-cleaning maintenance can be performed without an uncontrolled dust release.
Hopper discharge deviceselect
Rotary airlock valve
Screw conveyor
Slide gate to drum (batch)
Tipping tray / dust drawer (small units)

10 Explosion Protection and Fire Safety

NOTE A combustible-dust collector concentrates the exact conditions for a deflagration — fuel, oxygen, confinement — so the collector must be protected and isolated from the rest of the plant. NFPA 660 requires one or more protection methods sized from the DHA: deflagration venting (vent panels or a flameless vent device) that relieves the pressure to a safe place, chemical suppression that quenches the flame front, or pressure-containment that lets the vessel hold the explosion. Equally important is isolation: an abort gate, rotary airlock, or fast-acting valve in the duct keeps a deflagration from propagating back through the ductwork into occupied production areas. (10.1)
10.2A combustible-dust collector shall be provided with an explosion-protection method — deflagration venting, chemical suppression, or pressure-containment — sized per the DHA in accordance with NFPA 660.
10.3A deflagration vent shall discharge to a safe outdoor location, or a listed flameless vent device shall be used where outdoor discharge is not achievable.
10.4An explosion-isolation device shall be installed in the duct between the collector and the process to prevent flame propagation back into occupied areas.
10.5Spark detection and extinguishment shall be provided upstream of the collector where the served operation generates sparks or hot particles.
10.6Electrical equipment within or adjacent to a classified combustible-dust area shall be dust-ignitionproof or explosion-proof per NEC Article 502; standard NEMA 1 motor and starter enclosures shall not be used in a Class II area.
Explosion protection method (combustible dust)radio
Deflagration venting — vent panels to safe outdoor area
Deflagration venting — listed flameless vent device
Chemical (suppressant) explosion suppression
Pressure-containment design
Not applicable (non-combustible stream)
Explosion isolation device (duct, collector-to-process)select
Rotary airlock valve (passive)
Fast-acting (high-speed) isolation valve
Chemical isolation barrier
Abort gate / diverter
Not applicable (non-combustible stream)
Spark detection and extinguishmentradio
Required — spark/ember detection with water extinguishment
Not required (no spark-generating operation)
Electrical area classification at collectorradio
Unclassified (non-combustible stream)
Class II, Division 2
Class II, Division 1

11 Controls and Monitoring

NOTE The control package keeps the system in balance and gives the operator visibility. A VFD on the fan holds duct velocity as branches open and close and trims energy when the full system is not running; differential-pressure monitoring reports filter health; and interlocks tie the cleaning cycle, fan, and process together. The control panel is a listed industrial control panel, which matters both for the AHJ and for any motor or controller placed in a classified area. (11.1)
11.2The control panel shall be a listed industrial control panel conforming to UL 508A.
11.3The system controls shall monitor and display collector differential pressure and shall annunciate the high-differential-pressure alarm.
11.4Where a VFD is used, the controls shall maintain duct transport velocity across the operating range of branch dampers.
11.5Recirculation of cleaned air to occupied space shall be interlocked so that a secondary after-filter breakthrough or loss of monitoring diverts the system to outdoor exhaust or shuts it down.
Control packageselect
Across-the-line starter, DP gauge only
Across-the-line starter, DP transmitter + alarm
VFD with PLC, DP transmitter, pressure-feedback control
VFD with PLC and integrated explosion-protection interlocks

12 Recirculation and Emissions

NOTE Returning cleaned air to the building saves the heating and cooling energy that would be lost exhausting it outdoors, but it is the highest-risk decision in the system because a filter breakthrough now dumps contaminant directly into the breathing zone. ANSI Z9.2 and ACGIH require a secondary HEPA or MERV 16-plus after-filter on any recirculated stream, and OSHA 29 CFR 1910.94 prohibits recirculation of certain toxic dusts without AHJ approval. A specification that says "recirculate" without naming the after-filter is a guaranteed RFI. (12.1)
12.2Recirculated air shall pass through a secondary after-filter of MERV 16 or HEPA before return to occupied space.
12.3Recirculation shall not be used for a toxic dust prohibited from recirculation by OSHA 29 CFR 1910.94 without written AHJ approval.
12.4The design capture efficiency shall maintain employee exposures at or below 50% of the applicable OSHA PEL as an engineering-control margin.
NOTE The exposure benchmarks that drive the design — total nuisance particulate 15 mg/m³ TWA and respirable 5 mg/m³, respirable crystalline silica 50 µg/m³ TWA, and general welding fume 5 mg/m³ TWA — are PEL ceilings, not targets; the system is sized to hold the breathing zone well below them. (12.5)
Secondary after-filter (recirculation only)radio
MERV 16 final filter
HEPA (MERV 17 to 20) final filter
Not applicable (exhaust to outdoors)
Governing exposure limit for capture designselect
Nuisance particulate (PNOC) 15 mg/m³ total
Respirable particulate 5 mg/m³
Respirable crystalline silica 50 µg/m³
General welding fume 5 mg/m³
Project-specific contaminant PEL

13 Testing

NOTE Testing happens twice: at the factory for the collector and in the field for the assembled system. Factory acceptance for a pulse-cleaned collector follows ANSI/ASHRAE 199, the only standardized laboratory test for these collectors — requiring it ties the manufacturer to a measured initial and dust-loaded efficiency, average pressure drop, and compressed-air consumption rather than proprietary marketing data. Field commissioning verifies that the installed system actually develops capture velocity at every hood and transport velocity in every branch, by pitot-traverse per the ACGIH Manual and ANSI Z9.2. (13.1)
13.2A pulse-cleaned collector shall be factory-tested in accordance with ANSI/ASHRAE 199, reporting initial efficiency, dust-loaded efficiency, average pressure drop, air-to-cloth ratio, and compressed-air consumption.
13.3The installed system shall be field-commissioned by pitot-traverse per the ACGIH Industrial Ventilation Manual and ANSI Z9.2, verifying capture velocity at each hood, transport velocity in each branch, total system CFM, and total static pressure.
13.4The field commissioning test shall be repeated after 30 days of operation to confirm sustained performance after the filter cake has stabilized.
13.5Measured capture velocity at each hood shall meet or exceed the design capture velocity, and measured transport velocity in each branch shall meet or exceed the design transport velocity.
Required testscheckbox
ANSI/ASHRAE 199 factory performance test
Field pitot-traverse capture-velocity test (each hood)
Field pitot-traverse transport-velocity test (each branch)
Total system CFM and static pressure measurement
30-day re-test

14 Installation

NOTE Installation discipline preserves the design on the floor. Duct that is reassembled with low-velocity rectangular fittings, hoods relocated away from the work, or make-up air omitted will fail commissioning regardless of how well the equipment was specified. Equipment locations, duct routing, and the discharge point are coordinated on the drawings because they cannot be reduced to a datasheet selection. (14.1)
14.2Ductwork shall be installed to the routing shown on the drawings duct routing plan and shall be supported independently of the served equipment.
14.3The collector shall be installed at the location shown on the drawings collector location with the manufacturer's required clearances for filter access and maintenance.
14.4The deflagration-vent discharge shall be directed to the safe location shown on the drawings vent discharge zone, clear of personnel access, building openings, and combustible exposures.
14.5Ductwork shall be sealed so that joint leakage does not reduce transport velocity below the design minimum.
14.6Equipment and ductwork shall be supported and braced for the project's structural and seismic loads.
14.7Each collector, fan, and major duct branch shall be identified per Mechanical Identification.
Duct support and seismic bracingradio
Gravity and wind loads only
Seismic bracing per project seismic design category

15 Delivery, Storage, and Handling

NOTE Filter media and collector internals are the vulnerable items in transit and storage. Felt and membrane media absorb moisture and tear, and a wetted or damaged filter blinds or leaks from day one, so media is kept dry, sealed, and uninstalled until the system is ready to run. (15.1)
15.2Filter media shall be delivered in the manufacturer's sealed packaging and stored dry and protected from physical damage until installation.
15.3Collectors and fans shall be stored with openings covered to keep out construction debris and weather until connected.
15.4Filter elements shall not be installed until the ductwork is clean and the system is ready for startup, to avoid loading the media with construction debris.

16 Warranty

NOTE The warranty splits between the equipment and the consumable media, which wears by design. The collector housing, fan, and controls carry the equipment warranty; filter elements are consumables and carry a separate, shorter media warranty that excludes normal loading and abrasion wear. (16.1)
16.2The collector housing, fan, motor, and control package shall be warranted against defects in materials and workmanship for the project warranty period.
16.3Filter media shall carry the manufacturer's media warranty against manufacturing defects, exclusive of normal service wear.
Equipment warranty periodselect
1 year
2 years
3 years
5 years

17 Spare Parts

NOTE A dust system depends on consumables that must be on hand, because a plugged filter or a failed pulse valve idles the production equipment the system serves. A complete spare set of filter elements, pulse-valve diaphragms, and door gaskets keeps a media change from becoming a production outage. (17.1)
17.2The Contractor shall furnish one complete spare set of filter elements for each collector.
Spare parts to be furnishedcheckbox
One complete spare set of filter elements per collector
Spare pulse-valve diaphragms
Spare access-door and hopper gaskets
Spare differential-pressure sensor

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Dust and Fume Collection Systems." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/dust-and-fume-collection — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.