title: Electrical Equipment Labeling
…156 unchanged lines
options:
- "Equipment designation (matches one-line)"
− - "Voltage, phase, wire (e.g., 480Y/277V 3-phase, 4-wire)"
+ - "Voltage, phase, wire (e.g., 480Y/277V 3Φ 4W)"
- "Ampere rating (main bus or main device)"
- "Short-circuit current rating (SCCR) or AIC"
…393 unchanged lines
Where labels are found to be defective during the warranty period, the Contractor shall replace the defective labels at no cost to the Owner, including the labor to remove the failed label and install the replacement. Where the failure is traced to environmental conditions exceeding the label's UL 969 listing, the Contractor and the Engineer shall coordinate selection of a replacement material rated for the actual conditions, and the replacement shall be performed at no cost to the Owner if the original selection failed to account for known conditions.