+title: Power Distribution Units and Plug-In Devices
+category: Electrical
+toc_depth: 3
+description: >
+ When to use: rack-mount power distribution units (PDUs) and plug-in power
+ devices that distribute branch power within racks, enclosures, and at busway
+ tap-off points, including basic, metered, monitored, switched, and dual-input
+ (ATS) rack PDUs, busway plug-in tap boxes (bus plugs), special-purpose
+ relocatable power taps for IT rack assemblies, and rack outlet strips, across
+ data centers, NEC Article 645 IT equipment rooms, industrial floor
+ distribution off plug-in busway, healthcare rack assemblies, and commercial
+ equipment closets.
+ Not intended for: busway feeder runs, elbows, end closures, and hangers (use
+ [[sync/busway]]); panelboard assemblies feeding busway or PDUs (use
+ [[sync/panelboards]]); fixed receptacles, switches, and plates in boxes (use
+ [[sync/wiring-devices]]); conduit, grounding, and cable tray rough-in (use
+ [[sync/common-work-results-electrical]]); UPS and battery backup upstream of
+ PDUs, standalone branch-level surge protective devices, and transfer switches
+ or medium-voltage distribution above integral PDU ratings (separate product
+ categories not in this corpus).
+---
+
+# Scope {toc}
+
+## This Standard covers the procurement of power distribution units (PDUs) and plug-in power devices that take a branch or feeder source and distribute it to plug-connected loads at the point of use. {note}
+
+## The term "PDU" carries two unrelated meanings in the construction trades, and this Standard fixes the meaning deliberately. {note}
+
+### In data center and IT contexts a PDU is a rack-mounted intelligent power strip listed under UL 1363A; to industrial and utility engineers the same letters name a large floor-standing switchboard-fed distribution assembly. This Standard governs the former (rack PDUs and plug-in devices) and uses "floor PDU" or "switchboard" for the latter, which is procured under [[sync/panelboards]]. {note}
+
+## Two distinct listing families fall within this single specification scope. {note}
+
+### Rack-mount PDUs, relocatable power taps, and outlet strips are listed under UL 1363, UL 1363A, or UL 60601-1 and installed under NEC Article 645. {note}
+
+### Busway plug-in tap boxes (bus plugs) are listed under UL 857 and installed under NEC Article 368. {note}
+
+### Both families are the same product category from a procurement standpoint -- a device that derives plug-connected branch power -- and are specified together here, with sub-type requirements called out where the listings diverge. {note}
+
+## The Contractor shall furnish PDUs and plug-in devices complete with the cord sets, inlet and outlet connectors, integral overcurrent protection, metering or monitoring intelligence, and mounting hardware required for a complete and operable installation.
+
+## Where this Standard and the Contract Drawings conflict, the Contractor shall request clarification from the Engineer of Record before procurement.
+
+# Referenced Standards {toc}
+
+## Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
+
+## Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
+
+## The 2023 edition of NFPA 70 (NEC) is the baseline for this Standard; the Contractor shall verify the edition adopted by the Authority Having Jurisdiction and comply with locally adopted amendments.
+
+| Standard | Title |
+|----------|-------|
+| NFPA 70 (NEC) Art. 368 | Busways -- plug-in busway and tap device installation, overcurrent protection, grounding, accessibility |
+| NFPA 70 (NEC) Art. 645 | Information Technology Equipment (645.4 room qualification, 645.14 derived systems, 645.17 branch-circuit sizing) |
+| NFPA 70 (NEC) Art. 240 | Overcurrent Protection (240.24(A)(1) busway plug-in accessibility per 368.17(C)) |
+| NFPA 70 (NEC) Art. 285 | Surge-Protective Devices (where integral SPD is specified) |
+| NFPA 70 (NEC) Art. 110 | Requirements for Electrical Installations (110.10 short-circuit current rating) |
+| NFPA 70 (NEC) Art. 210 | Branch Circuits (210.19(A)(1), 210.20(A) continuous-load sizing) |
+| NFPA 70E | Standard for Electrical Safety in the Workplace (arc flash and shock labeling) |
+| NFPA 75 | Standard for the Fire Protection of Information Technology Equipment |
+| UL 857 | Busways (low-voltage busway and plug-in units to 600 V) |
+| UL 1363 | Relocatable Power Taps |
+| UL 1363A | Special Purpose Relocatable Power Taps (rack-mount PDUs for IT equipment assemblies) |
+| UL 1449 | Surge Protective Devices (integral surge suppression) |
+| UL 60601-1 | Medical Electrical Equipment (PDUs in patient care vicinities) |
+| IEC 60320 | Appliance Couplers for Household and Similar General Purposes (C13/C14, C19/C20) |
+| NEMA WD 6 | Wiring Devices -- Dimensional Requirements (NEMA locking and straight-blade configurations) |
+
+# Submittals {toc}
+
+## Action Submittals {toc}
+
+### The Contractor shall submit the following action submittals for the Engineer of Record's review before fabrication or ordering:
+
+- Product data for each PDU and plug-in device type: functional tier, form factor, input voltage and ampacity, inlet connector, outlet type and count, and listing category
+- Wiring diagrams showing phase configuration, internal overcurrent device arrangement, and outlet-to-breaker grouping
+- Short-circuit current rating (SCCR) for each device with the available fault current at the point of connection and supporting coordination
+- Cord set schedule: input cord length and connector, and any outlet cord-management provisions
+- For busway plug-in tap boxes: tap rating, enclosure type, engagement height, and overcurrent device coordination with the upstream busway feeder
+- For monitored, switched, or ATS units: network interface, management protocols, sensor ports, and firmware revision
+
+```datasheet
+label: Action submittals to be provided
+type: checkbox
+options:
+ - Product data per device type
+ - Wiring and phase-configuration diagrams
+ - SCCR documentation with fault-current basis
+ - Cord set schedule
+ - Busway tap box rating and coordination (where applicable)
+ - Monitoring/management interface data (where applicable)
+default: []
+```
+
+## Closeout Submittals {toc}
+
+### The Contractor shall submit the following closeout submittals before Substantial Completion:
+
+- Manufacturer's installation, operation, and maintenance manuals for each device type
+- Factory test reports for the furnished units
+- Network configuration record for intelligent units: assigned IP addresses, device names, SNMP settings, and firmware revision as commissioned
+- Field test reports, including infrared thermography results at full load
+
+```datasheet
+label: Closeout submittals to be provided
+type: checkbox
+options:
+ - Installation, operation, and maintenance manuals
+ - Factory test reports
+ - Network configuration record (intelligent units)
+ - Field test reports including IR thermography
+default: []
+```
+
+## Informational Submittals {toc}
+
+### The Contractor shall submit the following informational submittals for record:
+
+- Listing certificates for the applicable UL category of each device
+- Manufacturer's warranty documentation
+- Arc flash and shock hazard label proofs for busway tap boxes and switchboard-fed PDU input assemblies
+
+```datasheet
+label: Informational submittals to be provided
+type: checkbox
+options:
+ - UL listing certificates
+ - Warranty documentation
+ - Arc flash / shock label proofs
+default: []
+```
+
+# Quality Assurance {toc}
+
+## Rack-mount PDUs, relocatable power taps, and outlet strips shall be listed and labeled under the applicable UL category: UL 1363A for rack-mount IT equipment PDUs, UL 1363 for standalone relocatable power taps, and UL 60601-1 for units in patient care vicinities.
+
+## Busway plug-in tap boxes shall be listed and labeled under UL 857.
+
+## Where an integral surge protective device is specified, that device shall be listed under UL 1449.
+
+## All units of a given type shall be the product of a single manufacturer.
+
+## The manufacturer shall have a minimum of five years of documented production experience with the specified device family.
+
+## Listing Selection {toc}
+
+### Select the listing category appropriate to the application; the wrong listing is a common cause of inspection and survey citations.
+
+```datasheet
+label: Required listing category
+type: radio
+options:
+ - UL 1363A special-purpose relocatable power tap (rack-mount IT PDU)
+ - UL 1363 relocatable power tap (standalone outlet strip)
+ - UL 60601-1 / hospital-grade (patient care vicinity)
+ - UL 857 busway plug-in unit (bus plug)
+default: UL 1363A special-purpose relocatable power tap (rack-mount IT PDU)
+```
+
+# Environmental and Service Conditions {toc}
+
+## PDUs and plug-in devices shall be rated for continuous operation under the service conditions at the installed location without derating below the specified load.
+
+## Rack-mount units shall be suitable for an operating ambient temperature of 0 to 50 °C and 0 to 95% relative humidity, non-condensing, consistent with the UL 1363A service environment.
+
+## Busway plug-in tap boxes installed in industrial environments shall be furnished in an enclosure rated for the area: NEMA 1 or 12 for indoor clean/dusty areas and NEMA 3R where exposed to moisture.
+
+## Where units are installed in an NEC Article 645 information technology equipment room, the room shall satisfy all conditions of NEC 645.4 before Article 645 wiring methods and equipment are used.
+
+## The Contractor shall verify that the room satisfies every condition of NEC 645.4 before applying Article 645 wiring methods; a 645-listed PDU installed in a non-qualifying room is a code violation.
+
+### A 645-listed PDU installed in a room that does not meet every condition of NEC 645.4 is a code violation; verifying only the equipment listing without confirming room qualification is a common field error. {note}
+
+## Operating Environment {toc}
+
+### Specify the installed environment so the enclosure rating and temperature qualification can be confirmed. {note}
+
+```datasheet
+label: Installed environment
+type: radio
+options:
+ - Conditioned data center / server room (NEC 645)
+ - Commercial equipment closet
+ - Industrial floor (busway tap-off)
+ - Healthcare rack assembly / patient care vicinity
+default: Conditioned data center / server room (NEC 645)
+```
+
+```datasheet
+label: Busway tap box enclosure rating
+type: radio
+options:
+ - NEMA 1 (indoor general purpose)
+ - NEMA 12 (indoor dust-tight)
+ - NEMA 3R (rainproof)
+default: NEMA 1 (indoor general purpose)
+```
+
+# Functional Tier and Form Factor {toc}
+
+## The functional tier sets how much intelligence the unit carries; it is the first selection because it drives cost, network infrastructure, and the rest of the procurement. {note}
+
+### A basic unit only distributes power. A metered unit adds a local current display so a technician can read load at the rack. A monitored unit reports current, voltage, and power over the network for remote capacity management. A switched unit adds per-outlet remote on/off and reboot for lights-out operation. An ATS unit adds a second input and transfers between two independent feeds. {note}
+
+## The Contractor shall furnish PDUs of the functional tier specified for each rack position; tiers shall not be substituted downward.
+
+## Functional Tier {toc}
+
+```datasheet
+label: PDU functional tier
+type: radio
+options:
+ - Basic (no metering)
+ - Metered (local current display)
+ - Monitored (remote SNMP/web monitoring)
+ - Switched (per-outlet remote control)
+ - ATS (dual input, automatic transfer)
+default: Monitored (remote SNMP/web monitoring)
+```
+
+## Form Factor {toc}
+
+### Horizontal 1U/2U units consume rack U-space but suit shallow or network racks; vertical 0U units mount in the rack's side channel and free U-space for equipment; floor units serve whole-row distribution; busway tap boxes feed equipment from overhead bus. {note}
+
+### The form factor shall match the rack design and the cabinet's cable-management scheme.
+
+```datasheet
+label: Mounting form factor
+type: radio
+options:
+ - Horizontal 1U rackmount
+ - Horizontal 2U rackmount
+ - Vertical 0U (side-mount)
+ - Free-standing floor PDU
+ - Plug-in busway tap box
+default: Vertical 0U (side-mount)
+```
+
+# Electrical Ratings {toc}
+
+## Input ratings shall be selected for the connected load with the continuous-load derating required by code, not for the nameplate ampacity. {note}
+
+## The Contractor shall load each unit such that the continuous load does not exceed 80% of the input circuit rating, per NEC 210.19(A)(1) and 210.20(A).
+
+### A 30 A input PDU is loaded to a maximum of 24 A continuously. RFIs commonly arise when the field reads the 30 A nameplate and sizes loads to 30 A; the 80% ceiling is a code limit, not a margin to be reclaimed. {note}
+
+## The unit's short-circuit current rating shall equal or exceed the available fault current at the point of connection, per NEC 110.10.
+
+## The SCCR shall appear on the submittal with the fault-current basis stated.
+
+### SCCR is the single most-omitted line on PDU submittals and a frequent cause of AHJ rejection. {note}
+
+## Busway plug-in tap boxes shall be rated for the system voltage, up to 600 V AC maximum per UL 857; plug-in units above 600 V are outside this Standard.
+
+## Input Voltage and Ampacity {toc}
+
+### The 80% case for data center racks is 208 V single-phase at 30 A (NEMA L6-30P inlet), delivering 24 A continuous. {note}
+
+```datasheet
+label: Input voltage
+type: radio
+options:
+ - 120 V single-phase
+ - 208 V single-phase
+ - 240 V single-phase
+ - 208 V 3Φ wye (120/208 V)
+ - 480 V 3Φ
+default: 208 V single-phase
+```
+
+```datasheet
+label: Input circuit rating
+type: radio
+options:
+ - 15 A
+ - 20 A
+ - 30 A
+ - 60 A
+default: 30 A
+unit: A
+```
+
+```datasheet
+label: Phase configuration
+type: radio
+options:
+ - Single-phase 2-wire
+ - Single-phase 3-wire
+ - 3Φ 4-wire wye (120/208 V)
+ - 3Φ delta
+default: Single-phase 2-wire
+```
+
+## Busway Tap Rating {toc}
+
+### Busway plug-in tap boxes are furnished across a wide ampacity span; select the standard rating that protects the tap conductors and matches the connected load. {note}
+
+```datasheet
+label: Busway plug-in tap rating
+type: select
+options:
+ - 20 A
+ - 30 A
+ - 60 A
+ - 100 A
+ - 200 A
+ - 400 A
+ - 600 A
+ - 800 A
+ - 1200 A
+default: 60 A
+unit: A
+```
+
+```datasheet
+label: Short-circuit current rating (SCCR)
+type: range
+min: 10
+max: 100
+step: 1
+unit: kAIC
+```
+
+# Connectors and Outlets {toc}
+
+## The inlet connector shall match the upstream branch circuit or busway tap and the unit's input rating. {note}
+
+### Specifying a 15 A NEMA 5-15P inlet on a rack PDU feeding high-density servers leaves no headroom; data center units shall use a 20 A or 30 A inlet on a matched circuit. {note}
+
+## The Contractor shall furnish the inlet connector specified for each unit; locking configurations shall be used where retention is required.
+
+## Outlet quantity and the C13/C19 split shall be selected from the actual server power cord population, not assumed.
+
+### IEC C13 outlets are rated 10 A / 250 V per IEC 60320, de-rated for North American use under UL 1363A; C19 outlets are rated 16 A / 250 V IEC. Loads exceeding roughly 1.5 kW per outlet shall be served from C19 outlets. {note}
+
+### GPU-dense and high-draw racks need a higher C19 count; ordering the wrong C13/C19 ratio forces field re-procurement and schedule delay. The 80% case for a 30 A 208 V unit is a 24-outlet mix of 16 x C13 and 8 x C19. {note}
+
+## Outlets in vibration-prone or high-traffic industrial environments shall provide cord retention, by IEC locking outlets or outlet retention clips, so friction-fit cords do not back out.
+
+## Healthcare rack assemblies in patient care vicinities shall use hospital-grade, green-dot outlets on units listed to UL 60601-1.
+
+## Input Connector {toc}
+
+```datasheet
+label: Input (inlet) connector
+type: select
+options:
+ - NEMA 5-20P (120 V, 20 A)
+ - NEMA L5-30P (120 V, 30 A locking)
+ - NEMA L6-20P (208 V, 20 A locking)
+ - NEMA L6-30P (208 V, 30 A locking)
+ - NEMA L14-30P (120/240 V, 30 A locking)
+ - NEMA L21-30P (208 V 3Φ, 30 A locking)
+ - Hardwired
+ - Busway tap-off
+default: NEMA L6-30P (208 V, 30 A locking)
+```
+
+## Outlet Mix {toc}
+
+```datasheet
+label: IEC C13 outlet count
+type: range
+min: 0
+max: 42
+step: 1
+unit: outlets
+```
+
+```datasheet
+label: IEC C19 outlet count
+type: range
+min: 0
+max: 24
+step: 1
+unit: outlets
+```
+
+```datasheet
+label: Additional NEMA outlets
+type: select
+options:
+ - None
+ - NEMA 5-15R
+ - NEMA 5-20R
+ - Hospital-grade 5-20R (green dot)
+default: None
+```
+
+```datasheet
+label: Outlet retention
+type: radio
+options:
+ - None (friction fit)
+ - IEC locking outlets
+ - Outlet retention clips
+default: None (friction fit)
+```
+
+# Overcurrent Protection {toc}
+
+## Integral overcurrent protection shall be coordinated with the upstream device so that a branch fault clears at the nearest protective device.
+
+### Rack PDUs may carry individual outlet-bank breakers, a single whole-unit breaker, or no integral device when the unit is cord-and-plug connected to an upstream branch breaker. Busway plug-in tap boxes carry either fusible or molded-case circuit-breaker protection sized to the tap. {note}
+
+## Busway plug-in tap box overcurrent devices shall be sized to protect the tap conductors per NEC 368.17.
+
+### Mismatched tap and feeder protection ratings generate RFIs at rough-in inspection; coordinate the tap device with the upstream busway feeder protection before ordering. {note}
+
+## Where the unit serves an NEC Article 645 IT room with a transformer-derived secondary, the secondary shall not be treated as a separately derived system for grounding, per NEC 645.14.
+
+### Running a separate grounding electrode conductor to a 645.14 derived secondary is incorrect and a common field error. {note}
+
+## Rack PDU Overcurrent Device {toc}
+
+```datasheet
+label: Integral overcurrent protection (rack PDU)
+type: radio
+options:
+ - Individual outlet-bank breakers
+ - Whole-unit breaker only
+ - None (protected by upstream branch OCPD)
+default: Individual outlet-bank breakers
+```
+
+## Busway Tap Box Overcurrent Device {toc}
+
+```datasheet
+label: Busway tap box protection
+type: radio
+options:
+ - Fusible switch
+ - Molded-case circuit breaker
+default: Molded-case circuit breaker
+```
+
+# Monitoring and Network Interface {toc}
+
+## Metered, monitored, and switched units shall provide the management interface specified.
+
+## The project shall provision the supporting network infrastructure — management VLAN, allocated IP addresses, device naming convention, and SNMP settings — before energization.
+
+### A metered or monitored PDU ordered without a dedicated management VLAN, allocated IP addresses, a device naming convention, and SNMP settings becomes an unmonitored unit after installation — the most common reason intelligent PDUs deliver no value. {note}
+
+## Monitored and switched units shall communicate over 10/100 Base-T Ethernet.
+
+## Monitored and switched units shall support SNMP v3 and an HTTPS web interface.
+
+## Switched units shall provide per-outlet remote on/off and reboot, outlet grouping, and load-shedding capability.
+
+## Units provided with environmental sensor ports shall support temperature and humidity sensing for rack-level monitoring.
+
+## The Contractor shall configure each intelligent unit with the project's assigned address, device name, and SNMP credentials.
+
+## The Contractor shall record the configuration of each intelligent unit in the closeout submittal.
+
+## Network Interface {toc}
+
+```datasheet
+label: Management interface
+type: radio
+options:
+ - None (basic unit)
+ - Local display only (metered)
+ - Ethernet SNMP / HTTPS (monitored)
+ - Ethernet SNMP / HTTPS with switching (switched)
+default: Ethernet SNMP / HTTPS (monitored)
+```
+
+```datasheet
+label: Environmental sensor port
+type: radio
+options:
+ - Not required
+ - Temperature only
+ - Temperature and humidity
+default: Temperature only
+```
+
+# Construction and Finish {toc}
+
+## Enclosure and chassis materials shall suit the mounting form factor and environment. {note}
+
+### Vertical 0U units are typically extruded-aluminum bodies; horizontal and floor units are typically formed steel. Powder-coat finishes suit data center and commercial environments; anodized aluminum suits the extruded vertical units. {note}
+
+## The unit chassis shall be furnished in the specified material and finish, free of sharp edges that could damage cords during installation.
+
+## Enclosure {toc}
+
+```datasheet
+label: Enclosure / chassis material
+type: radio
+options:
+ - Formed steel
+ - Extruded aluminum
+default: Extruded aluminum
+```
+
+```datasheet
+label: Finish
+type: radio
+options:
+ - Powder coat - black
+ - Powder coat - gray
+ - Anodized aluminum
+default: Powder coat - black
+```
+
+# Cord Sets and Cable Management {toc}
+
+## Each cord-and-plug connected unit shall be furnished with an input cord of the specified length and connector; the cord shall reach the upstream receptacle without splices or extension. {note}
+
+### The 80% case for a rack PDU input cord is 10 ft. Longer cords are special-order and shall be confirmed against the receptacle location before ordering. {note}
+
+## For busway plug-in tap boxes, the supplied cord set or drop shall reach the served equipment from the engagement height without trip hazard or tension on the plug.
+
+### Bus plug faces sit roughly 10 to 14 ft above finished floor on industrial runs; an undersized drop pulls tension on the plug, and an oversized drop creates a trip hazard. Coordinate the engagement height with the drop length. {note}
+
+## Outlet cord-management features, where specified, shall retain server cords clear of adjacent equipment.
+
+## Cord Set {toc}
+
+```datasheet
+label: Input cord length
+type: select
+options:
+ - 6 ft
+ - 10 ft
+ - 12 ft
+ - 15 ft
+default: 10 ft
+unit: ft
+```
+
+```datasheet
+label: Outlet cord management
+type: radio
+options:
+ - None
+ - Cord-retention hooks
+ - Locking outlet sleeves
+default: None
+```
+
+## Busway Tap Box Engagement {toc}
+
+### Where the engagement height is set by the busway elevation, indicate it on the drawings rather than fixing it here. {note}
+
+```datasheet
+label: Busway tap box engagement height
+type: range
+min: 8
+max: 16
+step: 0.5
+unit: ft AFF
+drawing_ref: "busway elevation"
+default: deferred
+```
+
+# Safety Labeling {toc}
+
+## Busway plug-in tap boxes and switchboard-fed PDU input assemblies shall carry arc flash and shock hazard labeling per NFPA 70E 130.5(H).
+
+## The Contractor shall furnish each busway tap box and switchboard-fed input assembly with arc flash and shock hazard labels showing the incident energy or PPE category, nominal voltage, and arc flash boundary.
+
+### Facility safety officers increasingly enforce NFPA 70E labeling at acceptance; missing labels delay closeout. {note}
+
+# Testing {toc}
+
+## Each rack-mount PDU shall be factory tested per UL 1363A for dielectric strength, grounding continuity, leakage current, and overcurrent device trip.
+
+## Leakage current for non-healthcare rack PDUs shall not exceed 0.5 mA; units in patient care vicinities shall not exceed 100 µA per UL 60601-1.
+
+## Each busway plug-in tap box shall be factory tested per UL 857, including dielectric (hi-pot) test, contact resistance, and temperature-rise test at rated current.
+
+## Busway plug-in units shall pass a mechanical engagement and withdrawal cycle test of not fewer than 100 operations.
+
+## After installation, the Contractor shall perform infrared thermography on each busway tap box and each hardwired PDU input termination at full load and shall record any connection exceeding the manufacturer's temperature limit for correction.
+
+## Intelligent units shall be functionally tested after configuration for SNMP trap generation, outlet switching (switched units), and sensor reading.
+
+## Field Test Requirements {toc}
+
+```datasheet
+label: Field testing to be performed
+type: checkbox
+options:
+ - IR thermography at full load
+ - Grounding continuity verification
+ - Intelligent unit functional test (SNMP / switching / sensors)
+ - ATS transfer test (dual-input units)
+default:
+ - IR thermography at full load
+ - Grounding continuity verification
+```
+
+# Installation {toc}
+
+## Units shall be installed in accordance with the manufacturer's instructions and the applicable NEC article for the device family.
+
+## Rack-mount units shall be secured to the rack with the manufacturer's mounting hardware so the unit and its cords bear no load on the outlets.
+
+## Vertical 0U units shall be mounted in the cabinet side channel so as not to obstruct equipment cable routing or airflow.
+
+## Busway plug-in tap boxes shall be engaged onto the busway only with the busway de-energized unless the unit and busway are listed for energized insertion, and shall be fully seated and latched before energization.
+
+## Overhead busway plug-in units not accessible from the floor shall be installed per NEC 368.17(C) and 240.24(A)(1), with a means of operating the disconnect from the floor where required.
+
+## Intelligent units shall be connected to the management network and configured before the racks they serve are placed in service.
+
+# Delivery, Storage, and Handling {toc}
+
+## Units shall be delivered in the manufacturer's original packaging, labeled with the model designation, ratings, and listing.
+
+## Units shall be stored indoors in a clean, dry location within the manufacturer's storage temperature range of -20 to 60 °C until installation.
+
+## Cords and connectors shall be protected from crushing and abrasion during storage and handling.
+
+# Warranty {toc}
+
+## The manufacturer shall warrant each PDU and plug-in device against defects in materials and workmanship for the period specified, measured from the date of Substantial Completion.
+
+## Warranty Period {toc}
+
+```datasheet
+label: Manufacturer warranty period
+type: radio
+options:
+ - 2 years
+ - 3 years
+ - 5 years
+default: 3 years
+```
+
+# Spare Parts {toc}
+
+## The Contractor shall furnish the spare parts specified below for owner stock, in the manufacturer's original packaging and labeled with the device type they serve.
+
+```datasheet
+label: Spare parts to be furnished
+type: checkbox
+options:
+ - Spare input cord sets
+ - Spare environmental sensors
+ - Spare outlet retention clips
+ - Spare fuses (busway tap boxes)
+default: []
+```