Fire Alarm Systems

Revision 4 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 11, 2026 +8 −17

Migrate datasheet deferrals to drawing_ref + default: deferred
Showing changes from Rev 3 to Rev 4 in Fire Alarm Systems.
Tag changes −Acceptance Testing−Fire Alarm−NFPA 72−Sequence of Operations
---
title: Fire Alarm Systems
264 unchanged lines
- "Relocation — alarm floor and floors above/below evacuate; others remain"
- "Defend in place — shelter-in-place with selective notification (healthcare)"
- "As indicated in the sequence of operations matrix on drawings"
drawing_ref: true
default: "Total (simultaneous) evacuation — all NACs activate on any alarm"
67 unchanged lines
- "20% spare on all circuit types (installed, usable without hardware addition)"
- "25% spare — enhanced expansion requirement"
- "As indicated on drawings"
drawing_ref: true
default: "20% spare on all circuit types (installed, usable without hardware addition)"
137 unchanged lines
- "Alarm signal — fan shutdown + occupant notification"
- "Alarm signal — fan shutdown + occupant notification + FACU relay for damper closure"
- "Per sequence of operations matrix on drawings"
drawing_ref: true
default: "Per sequence of operations matrix on drawings"
+drawing_ref: "sequence of operations matrix"
+default: deferred
```
54 unchanged lines
- "194°F (90°C) — high-temperature environment (near kitchen equipment)"
- "212°F (100°C)"
- "Per drawings based on ambient temperature survey"
drawing_ref: true
+drawing_ref: "ambient temperature survey"
default: "135°F (57°C) — standard low-temperature spaces"
```
140 unchanged lines
- "82 dB — standard commercial ambient"
- "88 dB — elevated-ambient spaces (mechanical rooms, labs)"
- "Per voltage drop calculation and ambient survey — see drawings"
drawing_ref: true
+drawing_ref: "voltage drop calculation and ambient survey"
default: "82 dB — standard commercial ambient"
```
33 unchanged lines
- "135 cd"
- "185 cd"
- "Per room-by-room coverage calculation — see drawings"
drawing_ref: true
default: "Per room-by-room coverage calculation — see drawings"
+drawing_ref: "room-by-room coverage calculation"
+default: deferred
```
132 unchanged lines
- "Level 3 — listed 2-hour fire-rated cable system with tested assembly"
- "Level 4 — listed 1-hour fire-rated cable (2022 edition addition)"
- "Per drawings — as required by AHJ and evacuation strategy"
drawing_ref: true
default: "Level 0 — no survivability requirement (conventional wiring, Class B)"
213 unchanged lines
- "16 AWG"
- "14 AWG"
- "Per voltage drop calculation — see drawings"
drawing_ref: true
+drawing_ref: "voltage drop calculation"
default: "18 AWG (minimum per NFPA 72)"
```
8 unchanged lines
- "14 AWG"
- "12 AWG"
- "Per voltage drop calculation — see drawings"
drawing_ref: true
+drawing_ref: "voltage drop calculation"
default: "14 AWG"
```
312 unchanged lines
### Where nuisance alarms exceed this threshold, the Contractor shall investigate, reprogram, or replace devices as necessary to achieve compliance.