title: Fire Hydrants
175 unchanged lines
## The hydrant bury depth shall match the depth of cover over the supply main, verified against actual main depth and local frost depth.
### Hydrant barrel length is fixed at manufacture; specifying bury depth from a generic schedule without confirming the as-designed main depth and frost depth forces a field extension or a complete hydrant replacement. The 80% case in the temperate United States is 4 ft to 4.5 ft of cover.
+### Hydrant barrel length is fixed at manufacture; specifying bury depth from a generic schedule without confirming the as-designed main depth and frost depth forces a field extension or a complete hydrant replacement. Typical cover in the temperate United States is 4 ft to 4.5 ft.
### Where the main is deeper than the standard bury depth, hydrant extension sections shall be specified in 6 in. increments and called out on the civil drawings.
268 unchanged lines
## The supply pipe to each hydrant shall be not less than 6 in. for private systems, and 8 in. is the default for new private mains.
### NFPA 24 permits a 6 in. minimum supply, but an 8 in. supply is recommended for new private systems and is the 80% case because it sustains pumper flows with lower friction loss.
+### NFPA 24 permits a 6 in. minimum supply, but an 8 in. supply is recommended for new private systems and is the usual choice because it sustains pumper flows with lower friction loss.
## Hydrant placement, lateral routing, and the limits of the fire service main shall be taken from the civil/site drawings. [[drawing: hydrant location plan]]
162 unchanged lines
- Replacement nozzle caps, gaskets, chains
```