Fire Protection Piping and Specialties

Rev 1 · Updated Jun 13, 2026 · View history

1 Scope

NOTE This standard covers the materials, joining methods, valves, specialties, supports, testing, and installation of the common piping infrastructure that serves water-based fire suppression systems. (1.1)
NOTE The piping covered here is the shared backbone that all water-based systems depend on; the system-specific standards reference this document for their supply piping, valves, and specialties rather than restating them. (1.2)
1.3Fire protection piping and specialties installed under this standard shall comply with NFPA 13, NFPA 14, and NFPA 24 as adopted by the Authority Having Jurisdiction, together with the International Building Code and International Fire Code as adopted locally.
1.4Where local amendments modify a referenced NFPA standard, the local amendment shall govern unless it is less stringent than the base standard, in which case the base standard governs.
1.5The Contractor and the designer shall confirm the edition of each governing NFPA standard adopted in the jurisdiction before beginning design or procurement.
NOTE The 2019, 2022, and 2025 editions of NFPA 13 differ in pipe schedule allowances, listed CPVC and copper provisions, dry-pipe water-delivery rules, and gridded-system rules; the 2022 edition is the most widely adopted, but many jurisdictions remain on 2019. (1.6)
NOTE The scope extends from the underground fire service main and its appurtenances through the building riser, control valves, and alarm valve trim, across all aboveground supply mains, cross mains, and branch lines, and includes the fire department connection, drains, gauges, hangers, and seismic bracing. (1.7)
NOTE This standard does not govern the hydraulic design, hazard classification, sprinkler head selection, or system layout of any suppression system; those decisions are made in the applicable system standard and are reflected on the design drawings. (1.8)

2 Referenced Standards

2.1Materials, valves, specialties, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited on the drawings or in the project specification.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard Title
NFPA 13 Standard for the Installation of Sprinkler Systems
NFPA 14 Standard for the Installation of Standpipe and Hose Systems
NFPA 24 Standard for the Installation of Private Fire Service Mains and Their Appurtenances
NFPA 25 Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
NFPA 72 National Fire Alarm and Signaling Code
NFPA 1963 Standard for Fire Hose Connections
ASTM A795 Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for Fire Protection Use
ASTM A53 Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless
ASTM A135 Electric-Resistance-Welded Steel Pipe
ASTM A536 Ductile Iron Castings
ASTM B88 Seamless Copper Water Tube
AWWA C900 Polyvinyl Chloride (PVC) Pressure Pipe and Fabricated Fittings, 4 In. Through 60 In.
AWWA C151 Ductile-Iron Pipe, Centrifugally Cast
AWWA C105 Polyethylene Encasement for Ductile-Iron Pipe Systems
AWWA C606 Grooved and Shouldered Joints
ASME B16.1 Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250
ASME B16.3 Malleable Iron Threaded Fittings: Classes 150 and 300
ASME B16.9 Factory-Made Wrought Buttwelding Fittings
UL 213 Rubber-Gasketed Fittings for Fire-Protection Service
UL 262 Gate Valves for Fire-Protection Service
UL 312 Check Valves for Fire-Protection Service
UL 405 Fire Department Connection Devices
UL 753 Alarm Accessories for Automatic Water-Supply Control Valves for Fire-Protection Service
UL 1091 Butterfly Valves for Fire-Protection Service
UL 1468 Direct Acting Pressure Reducing and Pressure Restricting Valves
UL 1821 Thermoplastic Sprinkler Pipe and Fittings for Fire-Protection Service
FM 1110 Single Gate Valves and Indicator Posts
FM 1120 Check Valves (4 in. and Larger) for Fire Protection
IBC Chapter 9 International Building Code — Fire Protection Systems

3 Submittals

3.1The Contractor shall submit the following action submittals for review before fabrication or procurement:
  • Shop drawings showing pipe routing, sizes, joint types, hanger and brace locations, and valve and specialty locations, coordinated with the system standard and the structure.
  • Hydraulic calculations and the basis-of-design narrative for the supplied system, where prepared by the same Contractor.
  • Product data for pipe, fittings, couplings, valves, alarm and supervisory devices, fire department connections, gauges, and pressure-regulating valves, with listing marks identified.
  • Manufacturer cut sheets confirming the UL listing or FM approval applicable to fire protection service for each rated component.
  • Seismic bracing calculations and details where the project is in Seismic Design Category C or higher.
Action Submittalscheckbox
Coordinated shop drawings (routing, sizes, joints, hangers, braces)
Hydraulic calculations and basis-of-design narrative
Product data for pipe, fittings, and couplings
Product data for valves and specialties
Listing/approval marks for each rated component
Seismic bracing calculations and details
3.2The Contractor shall submit the following closeout submittals before final acceptance:
  • Material and test certificates, including the contractor's material and test certificate for aboveground piping per NFPA 13 and for underground piping per NFPA 24.
  • Hydrostatic and flush test reports witnessed by the Authority Having Jurisdiction where required.
  • Record drawings reflecting the as-installed routing, valve locations, and device addresses.
  • Operation and maintenance data for valves, alarm devices, and pressure-regulating valves.
Closeout Submittalscheckbox
Contractor's material and test certificates (aboveground and underground)
Hydrostatic and flush test reports
Record (as-built) drawings
Operation and maintenance data

4 Quality Assurance

NOTE Every component that performs a fire protection function shall be listed or approved for fire protection service by a nationally recognized testing laboratory. (4.1)
NOTE A valve, fitting, or device that is merely rated for plumbing or general service is not interchangeable with a fire-service-listed equivalent, even where the body appears identical; the listing certifies tested performance under fire-service pressures and cycling. (4.2)
4.3Pipe, fittings, couplings, valves, and specialties shall bear the listing or approval mark applicable to fire protection service.
4.4Control valves, check valves, and alarm devices shall be listed under the specific UL standard or approved under the specific FM standard applicable to their type and size.
4.5The installing contractor shall hold the fire sprinkler contractor license or certification required by the Authority Having Jurisdiction.
4.6Welders performing shop or field welding of fire protection piping shall be qualified in accordance with the welding procedure and performance qualification requirements of NFPA 13.
4.7Components from different manufacturers shall not be mixed within a grooved coupling joint.
4.8Gasket and housing compatibility shall be confirmed in writing where any substitution is proposed.
NOTE Grooved couplings, fittings, and gaskets from different manufacturers are not interchangeable; housing geometry and gasket durometer are matched assemblies, and mixing brands is a frequent cause of joint leakage and listing voidance. (4.9)

5 Environmental and Service Conditions

NOTE The selection of pipe material, joining method, and gasket compound shall account for the service the piping will see, including ambient temperature, internal corrosion exposure, and external (buried or exposed) corrosion exposure. (5.1)
5.2Pipe and components shall be rated for the maximum system working pressure, which is the greater of the maximum static supply pressure or the pump discharge pressure at churn, plus any required margin.
5.3The standard 175 psi working pressure class shall be used unless the maximum system pressure exceeds 175 psi, in which case the 300 psi high-pressure class shall be used for all pressure-containing components in the affected portion of the system.
NOTE A system fed by a fire pump with a churn (no-flow) discharge above approximately 165 psi will commonly exceed the 175 psi class once supply pressure is added; failing to identify this early forces a change order to replace undersized valves and fittings. (5.4)
System Working Pressure Classradio
175 psi (standard)
300 psi (high-pressure)
Maximum System Static Pressurerange
psi
50350
Default: 100 psi
5.5CPVC fire protection pipe shall not be used where the ambient or service temperature can exceed 150°F (65°C), and shall not be used in dry-pipe, pre-action, or deluge systems.
NOTE CPVC is listed for wet-pipe service only; the thermal cycling and condensation in dry and pre-action systems drive solvent-cement joint failures, and elevated temperature softens the material below its pressure rating. (5.6)
5.7Internal corrosion protection shall be provided where the system type and water chemistry warrant it, by material selection, nitrogen inerting of dry and pre-action systems, or a listed corrosion-inhibiting treatment.
5.8Buried ductile iron pipe in corrosive soils shall be protected by polyethylene encasement to AWWA C105 or by a fusion-bonded epoxy coating.
Internal Corrosion Protection Approachselect
None required (potable wet-pipe service)
Nitrogen inerting (dry/pre-action)
Listed corrosion-inhibiting treatment
Galvanized pipe (dry-pipe)

6 Pipe and Tube Materials

NOTE Aboveground fire protection piping shall be one of the listed steel, copper, or thermoplastic materials permitted by NFPA 13 for the system type, and underground fire service mains shall be ductile iron or another material permitted by NFPA 24. (6.1)
6.2Black steel pipe shall conform to ASTM A795, ASTM A53, or ASTM A135 and shall be the default material for aboveground wet-pipe and dry-pipe systems.
6.3Galvanized steel pipe conforming to ASTM A795 shall be used where specified to reduce internal corrosion, most commonly in dry-pipe and pre-action systems.
6.4Copper tube shall conform to ASTM B88, Type K or Type L, and shall be joined by brazing or by a listed press fitting where copper is used.
6.5CPVC pipe and fittings shall be listed to UL 1821 for fire protection service and shall be solvent-cement joined in accordance with the manufacturer's listed instructions.
6.6Underground ductile iron pipe shall conform to AWWA C151, Class 52 unless a different thickness class is required by the depth of cover and external loading.
NOTE The wall thickness (schedule) of steel pipe shall be selected together with the joining method, because groove dimensions and threadability depend on wall thickness. (6.7)
6.8Schedule 10 steel pipe shall be the default for aboveground steel piping NPS 1-1/4 and larger joined by grooved mechanical couplings.
6.9Schedule 40 steel pipe shall be used for threaded branch lines NPS 1 and smaller and where the system standard or a corrosive environment calls for the heavier wall.
NOTE Specifying Schedule 10 pipe while detailing Schedule 40 groove dimensions (or the reverse) produces a groove that does not match the wall and leaks or fails; the schedule and groove specification must be tied together on the shop drawings. (6.10)
Aboveground Pipe Materialselect
Black steel, Schedule 10 (ASTM A795)
Black steel, Schedule 40 (ASTM A795/A53)
Galvanized steel, Schedule 40 (ASTM A795)
Copper, Type L (ASTM B88)
Copper, Type K (ASTM B88)
CPVC, listed to UL 1821
Underground Fire Service Main Materialselect
Ductile iron, Class 52 (AWWA C151)
Ductile iron, Class 50 (AWWA C151)
PVC, listed (AWWA C900)
HDPE, listed
Aboveground Pipe Size Range Servedrange
in
0100
11.251.522.53468
Default: 4 in

7 Fittings and Joining Methods

NOTE The joining method shall be selected for the pipe material, size, system pressure, seismic demand, and maintenance access, and shall be one of the methods listed for fire protection service. (7.1)
7.2Grooved mechanical couplings and fittings shall be listed to UL 213 and shall conform to the dimensional requirements of AWWA C606.
7.3Threaded fittings on steel pipe NPS 2 and smaller shall be malleable iron conforming to ASME B16.3.
7.4Welded steel fittings shall conform to ASME B16.9 and shall be installed only by qualified welders using a qualified procedure.
7.5Flanged connections on large-diameter piping shall conform to ASME B16.1.
7.6Ductile iron grooved and underground fittings shall conform to ASTM A536.
NOTE Grooved couplings are furnished in rigid and flexible patterns, and the two are not freely substitutable; flexible couplings accommodate movement and seismic articulation, while rigid couplings hold the joint fixed. (7.7)
7.8Rigid grooved couplings shall be used at locations where NFPA 13 requires a rigid connection, including at riser transitions and immediately adjacent to pumps and risers.
7.9Flexible grooved couplings shall be used only where movement or seismic flexibility is intended and permitted, and shall not be substituted at locations where a rigid coupling is required.
7.10Grooved coupling gaskets shall be selected for the service: EPDM for standard wet-pipe water service, and a halogenated butyl or fluorocarbon compound for dry-pipe, antifreeze, or chemical-exposure service.
NOTE An EPDM gasket in an antifreeze loop or a petroleum-exposed environment will swell and fail; the gasket compound is a service-dependent selection, not a default. (7.11)
Primary Joining Methodselect
Grooved mechanical coupling, rigid
Grooved mechanical coupling, flexible
Threaded (malleable iron, NPS 2 and smaller)
Welded (buttweld/socket)
Flanged
Brazed (copper)
Solvent-cement (CPVC)
Grooved Coupling Gasket Compoundselect
EPDM (wet-pipe water service)
Halogenated butyl (dry-pipe/antifreeze)
Fluorocarbon (chemical exposure)

8 Control Valves

8.1Every system control valve shall be listed for fire protection service, shall be of the indicating type, and shall be electrically supervised in the open position.
NOTE An indicating valve shows its open or closed position at a glance — through the rising stem of an OS&Y gate, the position indicator of a butterfly valve, or the target window of a post indicator valve — so that an accidentally closed valve is visible during inspection. (8.2)
8.3Control valves shall be of the OS&Y gate, listed butterfly, or listed ball type as appropriate to the size and location.
8.4OS&Y gate valves shall be listed to UL 262 or approved to FM 1110 and shall be used as the default control valve where space permits.
8.5Butterfly valves shall be listed to UL 1091 and may be used in lieu of OS&Y gate valves where space is constrained, such as in mechanical rooms and at branch risers.
8.6Post indicator valves used for exterior control of underground mains shall be listed or approved and shall be supervised.
8.7Every control valve shall be provided with a supervisory (tamper) switch wired to the fire alarm control panel.
NOTE A missing tamper switch on any control valve — most often an overlooked butterfly valve on a branch riser — is a common code violation and inspection failure; NFPA 72 requires a supervisory signal on every control valve, not only the main valves. (8.8)
8.9The supervisory switch shall initiate a supervisory signal within two turns of the handwheel or within one-fifth of the distance of valve travel from the full-open position, whichever is less, in accordance with NFPA 72.
Primary Control Valve Typeradio
OS&Y gate valve (UL 262)
Butterfly valve (UL 1091)
Post indicator valve (underground)
Control Valve End Connectionselect
Grooved
Flanged
Threaded
Control Valve Tamper Switchradio
Single SPDT supervisory switch
Dual SPDT supervisory switches

9 Check Valves and Backflow

9.1Check valves used in fire protection piping shall be listed to UL 312 or, for sizes 4 in. and larger, approved to FM 1120.
9.2A check valve shall be installed in the system riser where required by NFPA 13 to prevent reverse flow and to isolate the system from the supply during alarm and test operations.
9.3The fire department connection shall be provided with a check valve so that water pumped into the connection cannot flow back out of the inlets.
9.4Where backflow prevention is required between the fire service and a potable supply, the backflow assembly shall be provided under Backflow Prevention and coordinated with the pressure loss it imposes on the fire service.
NOTE A backflow preventer introduces a fixed pressure loss that must be accounted for in the hydraulic calculation; omitting it from the calculation is a common cause of a system that fails its acceptance flow test. (9.5)

10 Alarm Valve and Riser Trim

NOTE The riser control assembly shall include the alarm or dry-pipe valve, the trim piping, the waterflow alarm device, drains, and the pressure gauges appropriate to the system type. (10.1)
10.2A wet-pipe riser shall be provided with an alarm check valve listed for fire protection service, complete with retard chamber, pressure alarm switch, and trim.
10.3A dry-pipe riser shall be provided with a listed dry-pipe valve and its trim, including the air or nitrogen supply connection, the intermediate chamber drain, and any quick-opening device required by the system standard.
10.4The alarm valve assembly shall be furnished with one pressure gauge connected above the valve clapper and one connected below, each with a range of 0 psi to 300 psi.
NOTE Pressure gauges shall be selected with a range of 0 psi to 300 psi so they are not damaged during the 200 psi hydrostatic acceptance test; a 0 psi to 100 psi gauge is pegged and ruined by the test pressure. (10.5)
Riser Alarm Valve Typeselect
Wet-pipe alarm check valve
Dry-pipe valve
Pre-action valve (provided in system standard)
None (flow switch only)
Pressure Gauge Rangeradio
0–300 psi
0–600 psi
Dry-Pipe System Supervisory Air Pressurerange
psi
1360
Default: 40 psi

11 Waterflow and Supervisory Devices

NOTE Waterflow shall be detected by a vane-type waterflow switch or by a pressure-type alarm switch, selected for the system size and the requirements of the local fire department. (11.1)
NOTE A vane (paddle) switch inserts into the flowing pipe and signals on sustained flow, while a pressure switch senses the pressure rise behind the alarm valve clapper; the choice depends on system size, pipe arrangement, and AHJ preference. (11.2)
11.3A waterflow alarm device shall be provided and wired to the fire alarm control panel to initiate an alarm on system flow.
11.4Vane-type waterflow switches shall be listed and provided with an adjustable retard, and the retard shall be set to delay the alarm signal to avoid false alarms from supply pressure surges.
11.5The waterflow switch retard shall be set between 20 and 30 seconds unless the system standard or the AHJ directs otherwise, within the device's adjustable range of 0 to 90 seconds.
NOTE Setting the retard too short causes nuisance alarms from normal pressure transients, while setting it too long delays a real alarm; the 20 to 30 second band balances both for most systems. (11.6)
Waterflow Detection Deviceradio
Vane-type waterflow switch
Pressure-type alarm switch
Waterflow Switch Retard Settingrange
s
090
Default: 30 s

12 Fire Department Connection

NOTE A fire department connection shall be provided where required so the responding fire department can augment the system supply, and its type, location, and thread standard shall be coordinated with the AHJ before procurement. (12.1)
NOTE Many jurisdictions have replaced the traditional two-inlet NST Siamese with a single large-diameter Storz connection; procuring the wrong thread or coupling type forces a costly replacement late in the project. (12.2)
12.3The fire department connection shall be listed to UL 405 and provided with clapper check valves at each inlet and a protective cap or plug on each inlet.
12.4Inlet threads shall conform to NFPA 1963, in the National Standard Thread or the Storz coupling standard adopted by the local fire department.
12.5The connection between a standpipe-supplying fire department connection and the standpipe riser shall be a minimum of 4 in. pipe in accordance with NFPA 14.
12.6The fire department connection shall be located and identified as directed by the AHJ, with the inlet height, clearances, and signage coordinated on the drawings. FDC location and mounting height
Fire Department Connection Typeselect
Free-standing Siamese, two 2-1/2 in. inlets (NST)
Wall-mounted, two 2-1/2 in. inlets (NST)
Wall-mounted Storz, 4 in.
Wall-mounted Storz, 2-1/2 in.
FDC Inlet Thread / Coupling Standardradio
National Standard Thread (NST)
Storz coupling
Per drawings — confirm with AHJ

13 Drains, Test Connections, and Gauges

NOTE A main drain shall be provided at the system riser, and an inspector's test connection shall be provided at the hydraulically most remote point, each sized in accordance with NFPA 13. (13.1)
13.2The main drain test pipe shall be sized in accordance with NFPA 13: minimum 1 in. for risers up to 2 in., minimum 1-1/4 in. for risers of 2-1/2 in. through 3-1/2 in., and minimum 2 in. for risers of 4 in. and larger.
13.3An inspector's test connection shall be provided with an orifice equivalent to the smallest sprinkler in the system and shall discharge to a location where flow can be observed safely.
13.4Auxiliary drains (drum drips) shall be provided at low points in dry-pipe and pre-action systems where trapped sections cannot drain back to the main drain.
13.5A combined test-and-drain assembly may be used to consolidate the inspector's test connection and the drain into a single listed device where permitted by the system standard.
13.6Pressure gauges shall be provided at the locations required by NFPA 13, each with a range of 0 psi to 300 psi and each removable for testing without draining the system.
Main Drain Sizeselect
1 in. (riser up to 2 in.)
1-1/4 in. (riser 2-1/2 in. to 3-1/2 in.)
2 in. (riser 4 in. and larger)
Test-and-Drain Arrangementradio
Combined test-and-drain assembly
Separate inspector's test and main drain

14 Pressure-Regulating Valves

NOTE A pressure-regulating valve shall be provided where the static pressure at a hose connection or system inlet exceeds the limit set by NFPA 13 or NFPA 14. (14.1)
NOTE Pressure-regulating valves protect downstream components and hose-stream users from excessive pressure; they are distinct from simple pressure-restricting orifices and are field-adjustable to a set discharge pressure. (14.2)
14.3A listed pressure-regulating valve shall be provided where the static pressure at any hose connection exceeds 175 psi, in accordance with NFPA 14.
14.4Pressure-regulating valves shall be listed to UL 1468 and shall be field-adjustable and verifiable by gauge during acceptance testing.
14.5The set discharge pressure of each pressure-regulating valve shall be documented on the record drawings and verified during the acceptance test.
Pressure-Regulating Valve Requiredradio
Yes — static pressure exceeds 175 psi
No — static pressure at or below 175 psi
Pressure-Regulating Valve Set Discharge Pressurerange
psi
75175
Default: 100 psi

15 Hangers and Supports

NOTE Pipe hangers and supports shall be listed for fire protection service, shall attach to the building structure or to listed trapeze assemblies, and shall be spaced in accordance with NFPA 13. (15.1)
NOTE Fire protection piping carries the weight of water plus a substantial point load from the seismic and surge forces of system operation; hangers must reach structural members, and a hanger spacing called out without confirming beam and joist locations causes field conflicts. (15.2)
15.3Hangers shall be of a material compatible with the pipe to avoid galvanic corrosion, with non-ferrous or coated hangers used on copper tube.
15.4Hanger spacing shall not exceed the maximum for the pipe size in NFPA 13 Table 17.2.3: 12 ft for pipe NPS 1 and NPS 1-1/4, and 15 ft for pipe NPS 1-1/2 and larger.
15.5Hanger and support locations shall be coordinated with the structure and shown on the shop drawings, including trapeze assemblies where individual structural attachment is not available. hanger and trapeze layout
Hanger Materialselect
Carbon steel, plated (ferrous pipe)
Galvanized steel
Copper-plated or coated (copper tube)
Maximum Hanger Spacingselect
12 ft (NPS 1 and 1-1/4)
15 ft (NPS 1-1/2 and larger)

16 Seismic Bracing

NOTE Sway bracing shall be provided where the project is in a seismic design category that triggers the bracing requirements of NFPA 13 Chapter 18, and the bracing shall be designed and detailed before installation. (16.1)
NOTE Designers in low-seismic regions frequently neglect Chapter 18 entirely, but Seismic Design Category C is more common than assumed and triggers full lateral and longitudinal bracing; the requirement is keyed to the IBC seismic design category, not to a perception of local risk. (16.2)
16.3Lateral and longitudinal sway bracing shall be provided for pipe NPS 1 and larger where required by the IBC seismic design category, in accordance with NFPA 13 Chapter 18.
16.4Lateral sway braces shall be spaced at not more than 40 ft, and longitudinal sway braces at not more than 80 ft, unless a more stringent spacing results from the brace load calculation.
16.5Flexible couplings shall be provided as required by NFPA 13 to accommodate differential movement during a seismic event.
16.6Clearances at penetrations shall be provided as required by NFPA 13 to accommodate differential movement during a seismic event.
16.7Restraint at risers shall be provided as required by NFPA 13 to accommodate differential movement during a seismic event.
Seismic Bracing Requiredradio
Yes — Seismic Design Category C or higher
No — Seismic Design Category A or B
Maximum Lateral Brace Spacingrange
ft
2040
Default: 40 ft
Maximum Longitudinal Brace Spacingrange
ft
4080
Default: 80 ft

17 Underground Fire Service Mains

NOTE Underground fire service mains and their appurtenances shall be installed in accordance with NFPA 24, including thrust restraint, depth of cover, and flushing before connection to the aboveground system. (17.1)
17.2Ductile iron underground pipe shall be joined by mechanical-joint or restrained push-on joint fittings rated for the system pressure.
17.3The depth of cover over the top of the underground main shall be at least 3 ft, and shall be increased where the local frost depth is greater.
NOTE In northern climates the frost depth commonly governs over the NFPA 24 minimum, requiring 4 ft to 6 ft of cover; specifying the 3 ft minimum without checking local frost depth creates a freeze risk. (17.4)
17.5Thrust restraint shall be provided at fittings, bends, and valves by restrained joints or by thrust blocks designed for the soil bearing capacity.
17.6The underground main shall be flushed at the required flow velocity before connection to the aboveground piping, and the flush shall be witnessed and recorded.
Underground Joint Typeradio
Restrained push-on joint
Mechanical joint
Depth of Cover Over Mainrange
ft
36
Default: 3 ft
Buried Pipe External Protectionselect
Polyethylene encasement (AWWA C105)
Fusion-bonded epoxy coating
None (non-corrosive soil)

18 Testing

NOTE All fire protection piping shall be hydrostatically tested, and underground mains shall be flushed, before the system is placed in service, with all tests witnessed and recorded as required by NFPA 13, NFPA 24, and NFPA 25. (18.1)
18.2Aboveground piping shall be hydrostatically tested at 200 psi for 2 hours, or at 50 psi above the maximum system static pressure where that pressure exceeds 150 psi, in accordance with NFPA 13.
18.3The hydrostatic test shall show no leakage and no drop in gauge pressure for the duration of the test.
18.4Underground mains shall be hydrostatically tested and flushed in accordance with NFPA 24 before being connected to the aboveground system.
18.5Dry-pipe systems shall additionally be tested for air-pressure tightness, with the supervisory air loss not exceeding the limit permitted by NFPA 13.
18.6Waterflow alarm, supervisory, and pressure-regulating devices shall be functionally tested and the signals verified at the fire alarm control panel and at the supervising station where provided.
18.7The completed system shall be tested and documented on the contractor's material and test certificate, which shall be submitted as a closeout document.
Hydrostatic Test Pressurerange
psi
150350
Default: 200 psi
Hydrostatic Test Durationradio
2 hours
More than 2 hours (AHJ directed)

19 Installation

NOTE Piping shall be installed straight, true, and pitched for drainage, with joints made in accordance with the manufacturer's listed instructions and the requirements of NFPA 13 and NFPA 24. (19.1)
19.2Piping shall be reamed and cleaned of cutting debris before assembly so that scale and filings do not lodge in valves, alarm trim, or sprinkler orifices.
19.3Grooved pipe ends shall be cut, rolled, or machined to the dimensions of AWWA C606 for the pipe wall thickness, and the groove dimensions shall match the coupling specified.
19.4Threaded joints shall be made up with a listed pipe-joint compound or tape applied to the male thread only, and excess shall be removed so it cannot enter the system.
19.5Wet-pipe and other water-filled piping shall be pitched to drain to the main drain or to auxiliary drains so the system can be emptied for service.
19.6Penetrations of fire-rated assemblies shall be firestopped under Firestopping, and the firestop system shall be listed for the pipe material and the rated assembly.
19.7Pipe routing, clearances, and the location of valves, drains, and the fire department connection shall be coordinated with other trades and confirmed against the drawings before installation. pipe routing and valve locations

20 Delivery, Storage, and Handling

NOTE Pipe, fittings, valves, and specialties shall be delivered, stored, and handled so that they are protected from contamination, corrosion, and physical damage until installation. (20.1)
20.2Pipe shall be stored off the ground and with the ends capped or plugged to keep dirt, debris, and rodents out of the bore.
20.3Valves and alarm devices shall be stored indoors in their original packaging, protected from freezing, dust, and impact, and kept in the closed or shipping position until installed.
20.4CPVC pipe, fittings, and solvent cement shall be stored within the manufacturer's temperature range and protected from prolonged ultraviolet exposure.
20.5Gaskets shall be stored in a cool, dark location away from ozone sources and shall not be used past the manufacturer's shelf life.

21 Warranty

NOTE The Contractor shall warrant the installed fire protection piping, valves, and specialties against defects in materials and workmanship for the project warranty period. (21.1)
21.2The Contractor shall warrant the work against leakage, joint failure, and device malfunction for a period of not less than one year from the date of substantial completion, unless a longer period is required by the contract.
21.3Manufacturer warranties for valves, alarm devices, and pressure-regulating valves shall be transferred to the Owner at closeout.
21.4The Contractor shall correct any defect discovered during the warranty period, including the repair of any damage caused by the defect or its correction, at no cost to the Owner.

22 Spare Parts

NOTE The Contractor shall furnish the spare sprinkler and valve-maintenance parts required by NFPA 13 so the system can be returned to service after operation or testing. (22.1)
22.2A spare-parts cabinet containing spare sprinklers of each type and temperature rating in the system, with the sprinkler wrench for each type, shall be furnished and mounted near the system riser in accordance with NFPA 13.
22.3Spare gaskets, trim parts, and the special tools required to service the alarm and dry-pipe valves shall be furnished to the Owner at closeout.
Spare Parts Packagecheckbox
Spare sprinkler cabinet with wrenches (per NFPA 13)
Spare grooved coupling gaskets
Alarm/dry-pipe valve trim and seat kits
Special service tools

Edit this page