1 Scope
NOTE This standard governs the materials, fabrication, and installation of interior gypsum board assemblies, including non-load-bearing steel-framed partitions, shaft-wall and chase-wall assemblies, area separation walls, furring assemblies, and gypsum board ceiling systems — both fire-resistance-rated and non-rated. (1.1)
NOTE Gypsum board is the dominant interior finish substrate and partition material in commercial construction because of its noncombustible core, reliable fire-resistance performance, competitive installed cost, and ease of repair. (1.2)
NOTE Properly specified and installed gypsum board assemblies also provide the acoustic separation that office buildings, healthcare facilities, hotels, and multi-family projects require. (1.3)
NOTE Gypsum board assemblies are systems, not products: the fire-resistance rating and acoustic performance of an assembly depend equally on the board type and thickness, the framing gauge and spacing, the number of layers, the fastener pattern, the acoustic insulation within the cavity, the perimeter treatment, and the quality of installation, and a change to any one of those variables can invalidate the rating. (1.4)
1.5 The Contractor shall install every rated assembly precisely as described in the applicable fire-resistance design number and as confirmed by the drawings.
1.6 The Contractor shall bring any field condition that would require a departure from the design number to the Architect of Record before proceeding.
1.8 The Contractor shall coordinate firestopping of penetrations through rated assemblies with Firestopping. 1.10 The Contractor shall coordinate interior painting of finished gypsum board surfaces with Interior Painting. 2 Referenced Standards
2.1 All materials, assemblies, and installation shall comply with the latest edition adopted by the Authority Having Jurisdiction for each of the following standards.
| Standard |
Title |
| ASTM C1396/C1396M |
Standard Specification for Gypsum Board |
| ASTM C840 |
Standard Specification for Application and Finishing of Gypsum Board |
| ASTM C645 |
Standard Specification for Nonstructural Steel Framing Members |
| ASTM C754 |
Standard Specification for Installation of Steel Framing Members to Receive Screw-Attached Gypsum Panel Products |
| ASTM C475/C475M |
Standard Specification for Joint Compound and Joint Tape for Finishing Gypsum Board |
| ASTM C1047 |
Standard Specification for Accessories for Gypsum Wallboard and Gypsum Veneer Base |
| ASTM C919 |
Standard Practice for Use of Sealants in Acoustical Applications |
| ASTM E119 |
Standard Test Methods for Fire Tests of Building Construction and Materials |
| ASTM E90 |
Standard Test Method for Laboratory Measurement of Airborne Sound Transmission Loss of Building Partitions and Elements |
| ASTM E413 |
Classification for Rating Sound Insulation |
| GA-216 |
Application and Finishing of Gypsum Panel Products (Gypsum Association) |
| GA-600 |
Fire Resistance and Sound Control Design Manual (Gypsum Association) |
| GA-214 |
Levels of Finish for Gypsum Panel Products (Gypsum Association) |
| IBC |
International Building Code (current edition adopted by jurisdiction) |
| UL Fire Resistance Directory |
UL Fire-Resistance Rated Systems |
2.2 Where the contract documents or a referenced standard impose a more stringent requirement than the minimum of any other standard, the more stringent requirement governs unless the Architect of Record directs otherwise in writing.
NOTE The Gypsum Association GA-216 is referenced by the International Building Code for gypsum board application, so compliance is a code obligation as well as a best-practice requirement on jurisdictions that have adopted the IBC, and GA-600 provides tested fire-resistance and sound-rated assembly designs that serve as the design basis for rated construction where UL-classified assemblies are used. (2.3)
3 Submittals
3.1 Action Submittals
3.1.1 The Contractor shall submit the following for the Architect's review prior to procurement and installation:
- Product data for each type of gypsum board, including manufacturer's physical properties, fire-test references, and applicable ASTM designations
- Product data for steel studs, runners, furring channels, resilient channels, and all other framing and furring members, including base metal thickness, yield strength, and coating type
- Product data for joint compound, joint tape, corner bead, trim accessories, and control joints
- Samples of each gypsum board type proposed, minimum 12 inches × 12 inches, with edge profile visible
- Identification of the specific UL or GA-600 fire-resistance design number for every fire-resistance-rated assembly shown on the drawings, cross-referenced to each partition type designation
- Identification of the specific GA-600 or tested sound assembly reference number for every acoustically rated assembly, cross-referenced to partition type designations
☑ Product data — gypsum board (all types)
☐ Product data — steel framing and furring
☐ Product data — joint compound and tape
☐ Product data — trim accessories and control joints
☐ Board samples (each type)
☐ Fire-resistance design number schedule
☐ Acoustic assembly reference schedule
3.1.2 The Contractor shall submit the action submittal items listed above for the Architect's review prior to procurement and installation.
3.1.3 Installation of any rated assembly shall not begin until the corresponding submittals have been reviewed and returned.
3.2 Closeout Submittals
3.2.1 The Contractor shall provide the following at project closeout:
- Warranty documentation for all gypsum board products and accessories carrying a manufacturer warranty
- Record of any field substitution to a fire-resistance design number approved in writing by the Architect of Record, including the revised design number or engineering judgment letter from a licensed professional engineer
☑ Warranty documentation for products and accessories
☑ Record of approved fire-resistance design number substitutions
3.2.2 The Contractor shall provide the closeout submittal items listed above at project closeout.
4 Quality Assurance
4.1 Installer Qualifications
4.1.1 Gypsum board installation shall be performed by workers who are experienced in commercial drywall installation of the types required on this project.
4.1.2 For fire-resistance-rated assemblies, workers shall be trained in the specific requirements of the rated design.
NOTE Fire-resistance performance depends on the precise execution of fastener patterns, framing gauge, joint treatment, and perimeter conditions, and workers who are unaware of the design constraints cannot meet them. (4.1.3)
4.2 Pre-Installation Conference
4.2.1 Before gypsum board installation begins, the Contractor shall hold a pre-installation conference with the Owner's representative and the Architect to review the fire-resistance design schedule, the acoustic assembly schedule, the finish level schedule, and any special conditions shown on the drawings.
4.2.2 Departures from any fire-resistance design number shall be resolved at or before this conference, not in the field.
4.3 Mock-Up
○ Yes — one representative partition per rated type
● No
4.3.1 Where the contract documents require a mock-up, the Contractor shall construct one representative partition of each rated partition type at a location directed by the Architect.
4.3.2 The mock-up shall remain in place for review before the production installation proceeds.
4.3.3 The mock-up shall demonstrate the framing layout, board type and thickness, fastener pattern, perimeter relief, control joint detail, and finish level.
4.4 Field Inspection of Rated Assemblies
4.4.1 The Authority Having Jurisdiction and the Owner's representative shall have the right to inspect rated assemblies before they are covered by finishes.
4.4.2 The Contractor shall not cover any fire-resistance-rated or acoustically rated assembly until it has been inspected and approved or until written permission to proceed has been issued.
4.5 Testing Agency
○ Yes — by independent accredited testing agency
● No
4.5.1 Where sound transmission class or impact isolation class verification testing is specified, an independent accredited testing agency shall perform field measurements in accordance with ASTM E336 and ASTM E597 and shall issue test reports to the Owner.
5 Environmental Conditions
5.1 Temperature and Humidity During Application
5.1.1 Gypsum board installation, joint treatment, and finishing shall not proceed when ambient air temperature or substrate temperature is below 55 °F (13 °C) or above 95 °F (35 °C) unless temporary heat and ventilation are provided to maintain acceptable conditions.
5.1.2 Temperatures shall be maintained throughout the application and drying period.
5.1.3 Rapid temperature fluctuations shall be avoided, because they cause differential thermal movement that can crack freshly dried joint compound before it has fully cured.
NOTE Joint treatment products require moisture in the gypsum core and at the paper face to bond and cure properly, and both extremes — excessively dry conditions and excessively humid conditions — impair the quality of the finished joint; in winter, temporary heat sources that consume moisture from the air can produce conditions that are too dry for joint compound to cure uniformly, leading to shrinkage cracking and poor bond. (5.1.4)
5.2 Ventilation
5.2.1 Adequate ventilation shall be provided to remove excess moisture during installation and through the complete drying of joint compound.
5.2.2 Mechanical ventilation or forced-air circulation shall be used when natural ventilation is insufficient to accomplish this within the project schedule.
NOTE Stagnant air traps moisture over freshly applied compound and produces slow, uneven drying, which can cause blisters, ridging, and bond failures. (5.2.3)
5.3 Moisture Content of Framing
5.3.1 Steel framing for gypsum board shall be free of corrosion and shall not be in contact with materials containing moisture that could accelerate corrosion.
5.3.2 Where conditions indicate high moisture exposure during construction — for example, following a wet concrete pour in a space with limited drying — steel framing shall be allowed to dry and any surface rust cleaned before board is applied.
5.4 Protection of Installed Board
5.4.1 Installed gypsum board shall be protected from direct water contact, prolonged moisture exposure, and physical damage until the building is enclosed and climate-controlled.
5.4.2 Gypsum board that has been wetted shall be inspected before finishing.
5.4.3 Board with surface paper separation, warping, or core softening shall be replaced.
6 Gypsum Board Materials
6.1 General Product Requirements
6.1.1 All gypsum board shall conform to ASTM C1396/C1396M.
6.1.2 Every board shall bear the manufacturer's label, the ASTM standard designation, and the type designation.
6.1.3 Board arriving on site without legible markings shall be rejected.
6.1.4 The gypsum core shall be essentially non-combustible per the ASTM standard, and the paper faces shall be bonded to the core for the full extent of the board.
6.2 Regular Gypsum Board
NOTE Regular gypsum board is the baseline product defined in ASTM C1396 for interior wall and ceiling applications where fire resistance is not required and moisture resistance is not a primary concern. (6.2.1)
NOTE It is the most economical board type and is appropriate for the majority of interior office, retail, and light commercial applications. (6.2.2)
○ 1/4 in
○ 3/8 in
● 1/2 in
○ 5/8 in
Per drawings
● Tapered (standard for two-coat finishing)
○ Square edge (for surface-applied textures or tile base)
○ Beveled
○ Rounded
6.2.3 Regular gypsum board is not formulated with fire-resistant additives and shall not be substituted for Type X board in fire-resistance-rated assemblies.
6.3 Type X Gypsum Board
NOTE Type X gypsum board is defined in ASTM C1396 as a board that achieves a fire resistance of not less than one hour for 5/8-inch thickness and not less than 45 minutes for 1/2-inch thickness when tested in accordance with ASTM E119 in a specific assembly. (6.3.1)
NOTE The 5/8-inch Type X board is the standard board for fire-resistance-rated gypsum board assemblies in commercial construction and is the most common board type required by fire-resistance design numbers. (6.3.2)
○ 1/2 in (45-minute assemblies)
● 5/8 in (one-hour and multi-hour assemblies)
Per drawings
NOTE Type X achieves its fire resistance through special core additives — typically glass fibers — that maintain core integrity and slow heat transmission, and the fire-resistance rating of an assembly using Type X board is a property of the entire assembly because the board alone does not carry a rating. (6.3.3)
6.3.4 The Contractor shall verify that the board, framing, fastener pattern, and all other assembly variables match the cited fire-resistance design number precisely.
6.4 Type C Gypsum Board
NOTE Type C gypsum board is a proprietary formulation that meets and exceeds the ASTM C1396 Type X requirements. (6.4.1)
NOTE Type C panels contain shrinkage-compensating additives — typically vermiculite — that cause the core to expand slightly when exposed to fire, maintaining joint integrity and extending fire resistance beyond what Type X achieves. (6.4.2)
NOTE All Type C products also qualify as Type X, but Type X products do not qualify as Type C. Type C is required by certain GA-600 and UL fire-resistance design numbers that demand longer fire ratings (commonly two hours) at thinner board profiles than Type X can achieve. (6.4.3)
○ Yes — assembly design number calls for Type C
● No — Type X is sufficient
Per drawings
6.4.4 The Contractor shall not substitute Type X for Type C in assemblies where the design number specifically calls for Type C, because the expansion behavior that maintains joint integrity under prolonged fire exposure is specific to the Type C formulation.
6.5 Moisture- and Mold-Resistant Gypsum Board
NOTE Moisture-resistant gypsum board is formulated for use in areas subject to intermittent moisture exposure — bathrooms adjacent to tiled showers, break rooms, locker rooms, and similar spaces where moisture is present but standing water is not. (6.5.1)
NOTE The product designation under ASTM C1396 requires both reduced water absorption of the core and reduced surface water absorption of the paper facing. (6.5.2)
NOTE Mold-resistant products additionally contain biocidal additives in the core and face paper to resist mold and mildew growth under elevated humidity conditions. (6.5.3)
○ Standard moisture resistant (meets ASTM C1396 water absorption requirements)
● Mold resistant (treated core and face paper)
○ Not required
Per drawings
6.5.4 Moisture-resistant board shall not be used as a tile backer in continuously wet areas such as shower enclosures or steam rooms.
NOTE Continuously wet tile backer applications require cement board, glass-mat tile backer, or fiber-cement backer products. (6.5.5)
6.6 Glass-Mat Gypsum Board
NOTE Glass-mat gypsum board replaces the paper facing with a glass-fiber mat embedded in and bonded to the core. (6.6.1)
NOTE The glass-mat facing is inherently resistant to moisture, mold, and mildew because it contains no organic material for mold to consume. (6.6.2)
NOTE Glass-mat boards are appropriate for high-humidity environments, behind tile in wet areas above grade, and for exterior-facing applications such as gypsum sheathing that will be exposed during construction. (6.6.3)
○ Required — interior glass-mat type
● Not required
Per drawings
NOTE Glass-mat boards designated for interior use differ from glass-mat sheathing in their surface texture, coating, and edge treatment, and the two product types are not interchangeable. (6.6.4)
6.6.5 In high-humidity interior locations, glass-mat board provides a more robust moisture-resistance performance than paper-faced moisture-resistant board and should be specified wherever the consequences of mold contamination are serious — healthcare, hospitality, and occupied multi-family.
6.7 Impact- and Abuse-Resistant Gypsum Board
NOTE Abuse-resistant and impact-resistant gypsum board products have reinforced cores — typically higher-density gypsum with glass fiber and polymer additives — and reinforced face papers that resist dents, scuffs, and penetration better than standard board. (6.7.1)
NOTE They are appropriate in corridors, stairwells, gymnasiums, activity rooms, healthcare support spaces, and other areas where the wall surface will be subject to carts, equipment, rolling loads, and physical contact. (6.7.2)
○ Required — high-abuse type (densified core, reinforced face)
○ Required — moderate-abuse type
● Not required
Per drawings
NOTE The board type alone does not determine abuse resistance; the framing gauge, stud spacing, number of layers, and base layer attachment also contribute. (6.7.3)
6.7.4 The Contractor shall confirm that the complete assembly matches the intended performance level.
6.8 Shaftliner and Coreboard
NOTE Shaftliner board is a 1-inch-thick gypsum board with a specially formulated dense core designed for use in 2-inch-deep H-stud shaft-wall assemblies and area separation walls. (6.8.1)
NOTE Shaftliner is installed without framing on its back side — it is captured between I- or H-shaped steel studs and bears against the steel directly. (6.8.2)
NOTE Its density and thickness allow it to perform structurally in this configuration without supplemental framing on the cavity-facing side. (6.8.3)
NOTE Shaftliner board is a Type X designation product whose specific fire-resistance performance is established by the tested assembly design, not by a standalone product rating. (6.8.4)
NOTE Coreboard is a related product in 1-inch thickness used in solid or laminated solid-core partition systems; its application is limited to specific design configurations. (6.8.5)
○ Yes — 1-inch Type X shaftliner for H-stud shaft wall assembly
● No
Per drawings
6.9 Board Dimensions
● 48 in (standard)
○ 54 in
8 ft
9 ft
10 ft
12 ft
14 ft
16 ft
Per drawings
6.9.1 Boards shall be cut to minimize joints and to allow horizontal orientation of boards on walls where the assembly height makes it practical.
6.9.2 Where boards must be oriented vertically, butt joints between non-tapered ends shall be back-blocked to provide a stiff substrate for joint treatment.
NOTE Horizontal orientation reduces the number of butt-end joints, which are the most difficult to finish invisibly because horizontal joints occur at tapered edges. (6.9.3)
7 Steel Framing and Furring
7.1 General Framing Requirements
7.1.1 All nonstructural steel framing and furring members shall conform to ASTM C645.
7.1.2 Installation shall conform to ASTM C754 and GA-216.
7.1.3 The Contractor shall not attach hangers, mechanical equipment, or structural loads to nonstructural steel framing without Engineer of Record approval.
NOTE Steel framing for gypsum board assemblies is non-load-bearing — it is designed to carry the self-weight of the gypsum board and to resist lateral loads (wind load on exterior curtain partitions, seismic drift at full-height partitions) but is not designed to carry vertical structural loads. (7.1.4)
7.1.5 Full-height partitions that extend to the structural deck above shall be provided with deflection heads — slip-track or similar top-runner details — that allow the structure to deflect vertically without transferring load into the partition and without cracking the gypsum board at the top of the partition.
7.1.6 The deflection head detail shall be shown on the drawings and the Contractor shall execute it precisely, because a partition that is structurally loaded at its top will crack at the ceiling line even if the board is otherwise perfectly installed.
7.2 Steel Stud Width
1-5/8 in (T-bar partition, extremely limited use)
2-1/2 in
3-5/8 in
4 in
6 in
Per drawings
7.2.1 For partitions requiring high STC ratings (above STC 50), the wall cavity width and the type of framing — whether single-stud, double-stud, or staggered-stud — are critical design variables and shall be coordinated with the acoustic assembly reference number.
NOTE The stud width determines the cavity depth available for acoustic insulation, the separation between wall faces (which affects STC), and the flexural stiffness of the partition, so wider studs generally produce stiffer and better-performing acoustic assemblies. (7.2.2)
7.3 Steel Stud Gauge
NOTE Nonstructural steel studs are available in 25-gauge (25 mil base metal thickness per ASTM C645), 20-gauge, 18-gauge, and heavier sections. (7.3.1)
NOTE The 25-gauge (20-mil delivered product minimum per ASTM C645) is the minimum conforming gauge for interior gypsum board partitions. (7.3.2)
NOTE For typical commercial partitions up to 10 feet in height under normal lateral loading, 25-gauge studs at 16 inches on center are often acceptable; partitions over 12 feet in height, or partitions subject to elevated lateral loads such as those adjacent to exterior walls in high-wind zones, require heavier gauge. (7.3.3)
25 gauge (20 mil delivered, 33 ksi min)
20 gauge (30 mil delivered)
18 gauge (43 mil delivered)
16 gauge (54 mil delivered)
Per drawings
7.3.4 The Contractor shall not substitute 25-gauge studs for heavier gauge specified on the drawings without the Engineer of Record's approval.
7.3.5 EQ studs meeting the minimum ASTM C645 requirements are acceptable; EQ studs that do not meet ASTM C645 minimum thickness requirements are not acceptable regardless of yield strength unless specifically designed and approved.
NOTE A common field error is the use of equivalent-gauge (EQ) studs, which achieve a given minimum moment of inertia through a combination of thinner steel and higher yield strength rather than the same steel thickness as the nominal gauge. (7.3.6)
NOTE Stud gauge determines the load-carrying capacity, stiffness, and height of the partition. (7.3.7)
7.4 Stud Spacing
12 in o.c.
16 in o.c.
24 in o.c.
Per drawings
7.4.1 For single-layer board applications, studs at 16 inches on center are standard; 24 inches on center is acceptable for lightweight partitions under limited height and loading conditions and where the board thickness and fastener pattern are adjusted accordingly.
7.4.2 Acoustic assemblies using resilient channel attachment of the gypsum board may require closer stud spacing to avoid excess deflection at the channel span.
NOTE Stud spacing affects the spanning capacity of the framing, the stiffness of the partition, and the fastener pattern of the gypsum board. (7.4.3)
7.5 Runners and Bridging
7.5.1 Top and bottom runners shall be the same width as the studs and shall conform to ASTM C645.
7.5.2 Bottom runners shall be anchored to the floor slab at intervals not exceeding 24 inches on center and at each end of the run.
7.5.3 Top runners for full-height partitions extending to the structure shall be anchored to the deck assembly.
7.5.4 Deflection head top runners used in lieu of fixed top runners shall have a minimum 2-inch leg depth that allows the stud top to slide vertically within the track by at least 3/4 inch to accommodate structural deflection, with the amount of slop confirmed against the structural deflection indicated on the drawings.
7.5.5 Bridging or bracing of studs shall be installed per ASTM C754 at intervals not exceeding the ASTM C754 span tables for the gauge and spacing selected, and additionally at all locations where the partition height-to-width ratio makes lateral bracing necessary for stability during construction.
7.5.6 Bridging channels shall be fastened to each stud with two approved fasteners.
7.6 Furring Channels
NOTE Furring channels — hat-shaped channels and resilient channels — are used to attach gypsum board to masonry or concrete substrates, to provide a cavity for mechanical and electrical runs, and, in the case of resilient channels, to acoustically decouple the gypsum board from the framing to improve sound isolation. (7.6.1)
● Hat channel (rigid — direct attachment to substrate)
○ Resilient channel (flexible — acoustic decoupling from framing)
○ Not applicable
Per drawings
7.6.2 Furring channel installation shall conform to ASTM C754 and to the applicable fire-resistance design number where furring is part of a rated assembly.
7.6.3 The Contractor shall use the correct screw length for each layer of board and shall verify that screws used to attach gypsum board to resilient channel do not contact the stud below.
7.6.4 The furring channel shall be fastened to the stud with a self-drilling screw, and the board shall be attached to the channel with a screw that engages only the channel.
NOTE The single most common error with resilient-channel assemblies is short-circuiting — fastening the gypsum board through the resilient channel and into the framing below with a screw that is too long — which bypasses the channel's resilience and can drop the STC of the assembly by 10 to 15 points. (7.6.5)
NOTE This standard does not govern structural cold-formed framing. (7.7.2)
8 Fire-Resistance-Rated Assemblies
8.1 General Fire-Resistance Requirements
● UL Fire-Resistance Directory
○ GA-600 Fire Resistance and Sound Control Design Manual
○ Other tested assembly — approved engineering judgment
Per drawings
Not rated
45 minutes
1 hour
1.5 hours
2 hours
3 hours
4 hours
Per drawings
8.1.1 Fire-resistance-rated gypsum board assemblies shall be constructed in strict conformance with a tested fire-resistance design.
NOTE The fire-resistance rating of an assembly is a property of the entire system as tested — substituting a different board type, changing framing gauge or spacing, altering fastener patterns, changing insulation, or modifying perimeter conditions can invalidate the rating, and the tested design is the contract, not the fire-resistance rating number in isolation. (8.1.2)
8.1.3 Tested fire-resistance designs shall be obtained from UL Fire-Resistance Directory (UL assemblies) or from GA-600 (Gypsum Association designs), both of which are accepted by the International Building Code.
8.1.4 The design number shall be listed in the partition type schedule on the drawings and in the submittal.
8.1.5 The Contractor shall verify that the proposed materials conform to every requirement of the design number, including proprietary requirements if any, before procurement.
8.2 Common Fire-Resistance-Rated Assembly Configurations
NOTE One-hour rated partitions in commercial construction are typically achieved with a single layer of 5/8-inch Type X gypsum board on each side of 25-gauge steel studs at 16 or 24 inches on center, with runners anchored to the structure. (8.2.1)
NOTE The joint treatment and fastener pattern are as specified in the design number. (8.2.2)
NOTE Two-hour ratings commonly require two layers of 5/8-inch Type X board on one or both sides, or one layer of Type C board on each side of a specific framing configuration. (8.2.3)
NOTE Area separation walls and shaft walls use 1-inch shaftliner panels captured in H- or I-studs combined with Type X face layers. (8.2.4)
Single layer
Double layer
Per design number — asymmetric layers
Per drawings
Single layer
Double layer
Per design number
Per drawings
NOTE The specific fire resistance of a gypsum board assembly depends primarily on the number and type of gypsum board layers on the fire-exposed side, because gypsum calcination — the release of chemically bound water from the gypsum dihydrate — is what absorbs heat and delays temperature rise on the unexposed side; the gypsum dehydration process consumes approximately 850 BTU per pound of gypsum at temperatures between 212 °F and 400 °F, providing a substantial thermal sink, and once the calcination front passes through the board thickness, protection is lost rapidly. (8.2.5)
8.3 Perimeter and Head-of-Wall Conditions for Rated Assemblies
NOTE The head-of-wall joint at the top of a fire-resistance-rated partition is among the most frequently cited deficiencies in construction inspections. (8.3.1)
NOTE A gap or an improperly filled joint at the top of a rated partition creates a direct air path that negates the fire rating. (8.3.2)
○ Fixed top — partition at structure, joint sealed with rated sealant
● Deflection head — slip track with rated flexible joint per design number
Per drawings
8.3.3 The head-of-wall condition — whether the partition runs to a fixed deck or to a deflection head — shall be detailed on the drawings and shall be executed as shown.
8.3.4 Where a deflection head detail is used, the joint between the top of the gypsum board and the underside of the deck or ceiling above shall be filled with a listed intumescent sealant or equivalent fire-rated flexible joint system that accommodates the design deflection movement while maintaining the fire rating throughout the life of the building.
8.3.5 The Contractor shall confirm that the selected head-of-wall detail has been tested or evaluated for the deflection amount indicated on the drawings.
NOTE Consult
Firestopping for penetrations through the assembly; this standard governs only the assembly itself and its perimeter conditions.
(8.3.6) 8.4 Shaft-Wall and Chase-Wall Assemblies
NOTE Shaft walls enclose elevator shafts, stair shafts, mechanical chases, and other vertical openings that penetrate multiple floors. (8.4.1)
8.4.2 They must provide both the required fire resistance — typically two hours for commercial buildings per IBC requirements for elevator and stair shafts — and the structural capacity to span floor-to-floor without framing on both sides of the panel, because the inside of the shaft is not accessible for framing after construction.
NOTE Shaft walls use 1-inch shaftliner panels installed horizontally between I-shaped or C-H steel studs anchored to the floor and ceiling runners, with Type X face layers applied to the stud faces on the accessible side. (8.4.3)
○ C-H stud (shaftliner panels in channel, Type X face layers at studs)
○ I-stud area separation wall
● Not applicable
Per drawings
8.4.4 Any damage to shaftliner panels during installation — cracking, crushing of the edge, or improper fit in the stud channel — shall cause rejection and replacement of the affected panel, because damaged panels may not carry the design lateral load or maintain the fire-resistance rating.
NOTE The structural performance of a shaft-wall assembly depends on the mechanical interlock between the shaftliner panel and the steel stud, and on the fastening of the face layer to the stud. (8.4.5)
8.5 Area Separation Walls
NOTE Area separation walls provide fire resistance between separate dwelling units or fire areas in multi-family and mixed-use construction. (8.5.1)
8.5.2 Because area separation walls must survive even if the construction on one side collapses, they are designed as freestanding assemblies using I-studs and shaftliner panels with a continuous gypsum board core that does not rely on the adjacent framing for support.
NOTE Each unit's framing is attached to the area separation wall with a breakaway clip that allows the framing to collapse away from the wall without pulling the wall down. (8.5.3)
9 Acoustic Assemblies
9.1 General Acoustic Requirements
NOTE Acoustic performance of gypsum board partitions is characterized by the Sound Transmission Class (STC) for airborne sound per ASTM E413 and ASTM E90. (9.1.1)
NOTE The STC is a single-number rating derived from laboratory measurements; higher numbers indicate better sound isolation. (9.1.2)
NOTE Field performance measured per ASTM E336 (Field Sound Transmission Class, FSTC) typically runs 3 to 5 STC points below laboratory performance due to flanking paths, construction variations, and penetrations. (9.1.3)
Not rated
STC 35 (basic separation)
STC 40
STC 45
STC 50
STC 55
STC 60+
Per drawings
9.1.4 The Architect shall specify the required STC for each partition type, taking into account the design goal (occupant privacy, program adjacency, HIPAA or similar requirements), the available wall cavity depth, and the acceptable construction cost.
NOTE Specifying STC without specifying the assembly design number or without coordinating framing, insulation, and perimeter sealing leaves the performance undefined, because the Contractor may build a compliant-looking assembly that does not achieve the rated STC when one or more critical details is missing. (9.1.5)
9.2 Acoustic Assembly Design Reference
● GA-600 sound-rated design
○ Published laboratory test report
○ No rating required
Per drawings
9.3 Framing for Acoustic Assemblies
NOTE Standard single-stud construction with gypsum board directly fastened to both sides of the studs provides moderate sound isolation — typically STC 35 to 45 depending on stud depth, board layers, and cavity insulation. (9.3.1)
NOTE Higher STC ratings generally require one of the following approaches: resilient channel on one or both sides to acoustically decouple the board from the framing; double-stud framing with a continuous air gap between the two stud rows and no physical connection between them; or staggered-stud framing on a common base plate with board alternating between the two stud rows. (9.3.2)
NOTE Each approach raises cost and assembly thickness but can achieve STC values above 55 in tested configurations. (9.3.3)
NOTE Regardless of the framing type, acoustic performance depends on eliminating flanking paths — the paths by which sound bypasses the partition through the structure, through penetrations, or through gaps in the perimeter sealing. (9.3.4)
NOTE A well-framed high-STC partition that is not perimeter-sealed, or that has back-to-back electrical boxes in the same stud bay, will perform at STC values far below its laboratory rating, and flanking is the single most common cause of acoustic failures in field measurements. (9.3.5)
9.4 Acoustic Insulation in Cavities
9.4.1 Acoustic insulation shall be installed in the cavity of all acoustically rated partitions.
9.4.2 The insulation type and thickness shall match the tested assembly exactly.
9.4.3 Acoustic mineral fiber or glass fiber batt insulation shall fill the cavity from runner to runner and from stud to stud without compression or gaps.
NOTE Insulation that is compressed, torn, or installed with gaps provides less benefit than fully installed insulation and can actually reduce STC by altering the cavity resonance. (9.4.5)
9.5 Acoustic Sealant
● Yes — ASTM C919 sealant at all perimeter conditions
○ No — not an acoustically rated partition
Per drawings
9.5.1 Acoustic sealant shall be applied to all perimeter conditions of acoustically rated partitions in accordance with ASTM C919.
9.5.2 All gaps and openings at the floor runner, the top runner or head-of-wall joint, and the perimeter of each face of the partition at adjacent walls, columns, and structure shall be sealed with acoustic sealant before applying the final layer of gypsum board.
9.5.3 The sealant shall be a permanently flexible, non-hardening, non-staining type formulated for acoustic applications; conventional caulk that hardens over time shall not be used because hardened sealant transmits vibration rather than isolating it.
9.6 Electrical Boxes in Acoustic Partitions
NOTE Electrical boxes are one of the most reliable sources of acoustic flanking failures in commercial construction. (9.6.1)
NOTE Back-to-back electrical boxes installed in the same stud bay provide a direct acoustic path through the partition because only the thin panel of gypsum board and the box depth separate the two cavities. (9.6.2)
● Boxes offset minimum 24 in — no back-to-back in same bay
○ Boxes offset and provided with acoustic putty pads or covers
○ Not applicable — partition is not acoustically rated
Per drawings
9.6.3 Back-to-back boxes shall not be installed in the same stud bay in any acoustically rated partition.
9.6.4 Boxes shall be offset a minimum of 24 inches horizontally in the partition.
9.6.5 In high-STC applications, all boxes shall be provided with pre-formed acoustic putty pads or listed acoustic box covers that seal the box perimeter and the knockout openings.
10 Accessories and Trim
10.1 General Accessories Requirements
10.1.1 All accessories — corner bead, edge trim, casing bead, control joints, and reveal beads — shall conform to ASTM C1047.
10.1.2 Accessories shall be compatible with the gypsum board and joint compound system.
10.1.3 Accessories of different metals shall not be combined in a way that creates a galvanic couple in a moist environment.
10.1.4 In areas of high humidity, accessories shall be fabricated from hot-dipped galvanized steel, rigid PVC, or rolled zinc alloy to resist corrosion.
10.2 Corner Bead
○ Metal — crimped or nailed attachment
○ Metal — clip-on attachment
● Paper-faced metal
○ Vinyl/PVC
10.2.1 Corner bead shall be installed at all exterior corners of gypsum board assemblies to reinforce the corner edge against impact and to provide a straight, consistent surface for finishing.
NOTE Paper-faced metal corner bead is preferred for standard finish applications because the paper face bonds to the joint compound and reduces the tendency for bead cracking at the nose when the corner is subject to minor impacts; metal corner bead provides the most impact-resistant nose protection and is appropriate in locations where the corner will be subject to physical contact, and vinyl bead is suitable where corrosion resistance is required and impact is limited. (10.2.2)
10.3 L-Bead and Trim Bead
○ Galvanized steel
● Zinc alloy
○ PVC
10.3.1 L-bead (casing bead) shall be installed wherever the gypsum board terminates against a dissimilar material — at door frames, window frames, columns, masonry walls, and at any edge that is not covered by corner bead and cannot be finished as a tapered joint.
NOTE L-bead provides a clean termination line and protects the board edge from damage during and after construction. (10.3.2)
10.4 Reveal and Shadow-Line Beads
10.4.1 Reveal beads and shadow-line beads are installed where a recessed joint or shadow line is desired at partition terminations, at changes in plane, or as a design element at ceiling lines and wall bases.
10.4.2 Reveal and shadow-line beads shall be installed plumb and level, attached per the manufacturer's instructions, and finished to the same level as the adjacent gypsum board.
10.5 Control Joints
● Standard V-groove — 1/4 in reveal
○ Standard V-groove — 1/8 in reveal
○ Flat face (flush profile)
10.5.1 Control joints shall be installed wherever required to prevent cracking caused by differential movement of the gypsum board assembly.
10.5.2 Control joints shall be a listed, pre-formed metal or vinyl section that creates a continuous, sealed break in the gypsum board face — they are not simply a taped joint or a scored break in the board face.
10.5.3 Both wings of the control joint shall be embedded in or attached to the gypsum board surface, and the exposed spine of the joint shall remain free from joint compound so that the joint can move.
NOTE Painting over or filling the control joint spine with compound defeats its purpose and will cause the board to crack at some other location. (10.5.4)
11 Joint Treatment and Finish Levels
11.1 General Joint Treatment Requirements
11.1.1 Joint treatment shall conform to ASTM C840 and GA-216.
11.1.2 Joint compound shall conform to ASTM C475/C475M.
11.1.3 All tapered joints, butt joints, interior angles, fastener heads, and accessory flanges shall receive joint treatment appropriate to the specified finish level.
11.1.4 Joint treatment shall not be applied when the ambient temperature is below 55 °F, because joint compound does not cure properly at low temperatures and will crack during drying.
11.2 Joint Compound Types
NOTE Joint compound is available in setting-type (chemical-hardening) and drying-type (evaporative-hardening) formulations, each appropriate for different applications. (11.2.1)
NOTE Setting-type compound hardens by a chemical reaction between the gypsum powder and water and reaches full hardness regardless of temperature or humidity — it is appropriate for embedding tape in the first coat, for filling deep voids and back-blocking, and for patching in cold conditions. (11.2.2)
11.2.3 Setting-type compound is harder to sand and must be applied carefully because it cannot be reworked once it begins to set.
NOTE Drying-type compound is used for finish coats because it is lighter, sands more easily, and produces a smoother surface; it cannot be applied in thick coats without shrinkage cracking and is not suitable for embedding tape in high-humidity conditions. (11.2.4)
● Setting-type (chemical hardening)
○ Drying-type (all-purpose or taping compound)
● Drying-type topping compound
○ Drying-type all-purpose compound
○ Setting-type finish compound
11.3 Joint Tape
NOTE Paper joint tape is the standard tape for flat joints and interior angles and produces the flattest finished surface when properly applied. (11.3.1)
NOTE Fiberglass mesh tape has higher tensile strength but requires setting-type compound for adequate bond; it is more appropriate for patching and for joints in wet areas. (11.3.2)
NOTE Paper tape embedded in setting-type compound at the first coat with finish coats of drying-type topping compound is the standard sequence for commercial construction. (11.3.3)
● Paper tape (standard for flat joints)
○ Fiberglass mesh tape (setting compound required)
11.3.4 Joint tape shall conform to ASTM C475/C475M.
11.4 Levels of Finish
NOTE The Gypsum Association GA-214 defines six levels of finish for gypsum board, numbered 0 through 5. (11.4.1)
NOTE The appropriate finish level depends on the final decoration and the lighting conditions at the surface. (11.4.2)
NOTE Specifying the correct finish level is one of the most important decisions in gypsum board specification because it defines the cost and quality of the finishing work, and because disputes over finish quality are among the most common construction disputes on commercial interior projects. (11.4.3)
NOTE **Level 0:** No finishing required. (11.4.4)
NOTE Typically reserved for temporary construction or spaces where the final decoration has not been determined. (11.4.5)
NOTE No tape, compound, or accessories required. (11.4.6)
NOTE **Level 1:** Tape embedded in joint compound at all joints and interior angles. (11.4.7)
NOTE Excess compound and tool marks acceptable. (11.4.8)
NOTE For plenum areas above ceilings, attics, and areas concealed from normal view. (11.4.9)
NOTE Fire-resistance-rated assemblies in concealed locations frequently require Level 1 to confirm that joints are taped. (11.4.10)
NOTE **Level 2:** Tape embedded and covered with a skim coat of compound, fastener heads covered once. (11.4.11)
NOTE Used under tile and where surface appearance is not a consideration — garages, mechanical rooms, warehouse space. (11.4.12)
NOTE Not suitable for paint. (11.4.13)
NOTE **Level 3:** Tape embedded, two coats of compound on joints and angles, one coat on fastener heads, accessories coated. (11.4.14)
NOTE Sanded smooth. (11.4.15)
NOTE Suitable for heavy or medium-texture spray finishes. (11.4.16)
NOTE Not suitable for flat paint or light texture. (11.4.17)
NOTE **Level 4:** Tape embedded, three coats on joints and angles, two coats on fasteners, accessories coated. (11.4.18)
NOTE Sanded smooth. (11.4.19)
NOTE Suitable for flat or low-sheen paints, light textures, and most commercial finishes. (11.4.20)
NOTE This is the standard finish level for commercial office, retail, and institutional applications. (11.4.21)
NOTE **Level 5:** All surfaces receive a skim coat of joint compound or a proprietary compound over the entire board face after Level 4 preparation. (11.4.22)
NOTE The skim coat fills surface texture differences between the compound-covered areas and the raw board face, producing a uniform surface. (11.4.23)
NOTE Required for gloss or semi-gloss paints, critical lighting environments, and high-end residential or hospitality applications. (11.4.24)
NOTE Level 5 is also the correct specification for any application where the lighting angle is severe enough that board-face texture differences will be visible — sidelighting from clerestories, large windows at low angles, or track lighting. (11.4.25)
Level 0 — no finishing
Level 1 — tape only (concealed/plenum)
Level 2 — tape + skim coat (tile base, mechanical)
Level 3 — tape + 2 coats (heavy texture surfaces)
Level 4 — tape + 3 coats (standard commercial paint grade)
Level 5 — tape + 3 coats + skim coat (gloss paint, critical lighting)
Per drawings
11.4.26 The finish level shall be selected based on the final paint sheen.
11.4.27 When in doubt, the Architect should specify Level 5 for any space where gloss or semi-gloss paint is indicated.
11.4.28 For any surface that will receive wallcovering, Level 4 at minimum is required and Level 5 is recommended, because thin wallcovering printed on non-woven or paper substrates telegraphs every surface variation in the substrate.
NOTE Applying a flat paint over a Level 3 finish may be acceptable, but applying a semi-gloss or gloss paint over a Level 3 or Level 4 finish will show every fastener and joint irregularity under the reflected light. (11.4.29)
11.5 Finish at Fire-Resistance-Rated Assemblies
11.5.1 Where the fire-resistance design number requires a specific joint treatment — typically at minimum the equivalent of Level 1 for concealed rated assemblies — that treatment shall be applied regardless of the finish level specified for the visible face.
11.5.2 Both sides of a rated partition shall receive at minimum the joint treatment required by the design number, even if one side is in a concealed plenum space.
11.6 Texture Finishes
● None — smooth finish
○ Fine orange peel spray
○ Medium orange peel spray
○ Aggregate spray (specify aggregate size)
○ Skip trowel
Per drawings
11.6.1 Where textured finish is indicated — aggregate spray, skip trowel, orange peel, or other applied texture — it shall be applied after Level 3 or Level 4 preparation (as appropriate to the texture type) and shall be uniform in pattern, thickness, and density across the entire surface.
11.6.2 Texture finishes shall not be applied as a substitute for proper Level 4 preparation in applications where flat or low-sheen paint will follow, because the texture will amplify rather than hide joint and fastener irregularities.
12 Installation
12.1 Delivery, Storage, and Handling
12.1.1 Gypsum board shall be delivered to the project in the manufacturer's original packaging with all labels and markings intact.
12.1.2 Board shall be stored flat, on a clean, level surface, and protected from moisture.
12.1.3 Board shall be stored indoors in a dry, climate-controlled environment after the building is enclosed; temporary outdoor storage shall be avoided, and any board that becomes wetted shall be inspected before installation and rejected if the face paper is delaminated or the core is soft.
12.1.4 Steel framing shall be stored off the ground and protected from water that would cause rust.
12.1.5 Light surface oxidation of zinc-coated framing does not impair performance, but heavy rust that pits the metal or reduces the base metal thickness below the ASTM C645 minimum shall cause rejection.
NOTE Board stacked flat on an uneven surface will conform to the irregularity and be permanently bowed, and board stored on edge for extended periods will sag at the center. (12.1.6)
12.2 Board Application — General
12.2.1 Board shall be applied in conformance with ASTM C840, GA-216, and the applicable fire-resistance design number.
12.2.2 All framing members shall be plumb, straight, and at the correct spacing before board is applied, and studs that are twisted, bowed, or misaligned shall be corrected before boarding.
12.2.3 Board shall be applied with the long dimension perpendicular to framing members (horizontal on walls) wherever practical.
12.2.4 Where vertical application is required or where building height exceeds available board lengths, joints shall be staggered from one layer to the next and from one side of the partition to the other in rated assemblies.
12.2.5 Board shall be cut with a sharp utility knife scored and snapped, or with a saw where cut edges will be visible, and cut edges shall be smooth and square.
12.2.6 Board shall be installed with a maximum gap of 1/4 inch at joints and at perimeter conditions for non-rated assemblies; fire-resistance design numbers may impose tighter joint tolerances that shall be met.
NOTE Horizontal application on walls places tapered edges at the horizontal joints where they are easiest to finish and limits the number of butt-end joints. (12.2.7)
12.3 Fastening
● Self-drilling bugle-head screws (steel framing)
○ Self-drilling pan-head screws (for base layer in multi-layer assemblies)
○ Per design number
Per drawings
8 in o.c. at field, 8 in at edges
12 in o.c. at field, 8 in at edges
16 in o.c. at field, 12 in at edges
Per design number
Per drawings
7 in o.c. nailed / 12 in o.c. screwed
Per design number
Per drawings
12.3.1 Fasteners shall be self-drilling, self-tapping bugle-head screws of the type and length required by ASTM C840 and by the applicable design number.
12.3.2 Fastener length shall be selected to provide a minimum of 5/8-inch engagement into steel framing and to avoid protruding through the framing.
12.3.3 Fasteners shall be driven with a screw gun set to the correct depth so that the fastener head is slightly below the board surface — creating a small dimple — without breaking the face paper.
12.3.4 Fasteners shall be installed beginning from the center of each board and progressing toward the edges, so that the board is pulled into contact with the framing uniformly.
12.3.5 Fasteners at edges shall be placed a minimum of 3/8 inch from the board edge to avoid crumbling the core.
NOTE Fasteners driven too deep break the paper and lose holding power, and fasteners left proud of the surface create ridges that telegraph through the finished joint. (12.3.6)
12.4 Multi-Layer Assembly Installation
12.4.1 In multi-layer assemblies — whether for fire resistance, enhanced acoustic performance, or impact resistance — the base layer shall be fully installed and fastened before the face layer is applied.
12.4.2 Face-layer boards shall be offset from base-layer joints both horizontally and vertically by a minimum of one stud space.
12.4.3 In rated assemblies, the face-layer fastener pattern shall be precisely as specified in the design number, because the face layer is the fire-exposed layer and its fastening is part of the tested configuration.
12.4.4 Adhesive lamination between layers may be used in specific applications to reduce fastener count in face layers and to improve rigidity.
12.4.5 Adhesive application shall conform to the adhesive manufacturer's instructions and to the applicable assembly design.
12.4.6 Adhesive alone shall not be used to attach face layers in fire-resistance-rated assemblies unless the design number specifically includes and describes the adhesive application.
12.5 Ceiling System Installation
● Direct-attached to furring channels on framing
○ Suspended — hanger wire and grid system
○ Direct to structure (concrete deck)
Per drawings
12.5.1 Direct-attached ceiling systems shall have gypsum board applied to furring channels or hat channels at the spacing required by the design number and by ASTM C840.
12.5.2 Suspended ceiling systems shall be designed and installed with a hanger wire grid in accordance with ASTM C754.
12.5.3 Maximum hanger spacing is 4 feet on center perpendicular to carrying channels, and carrying channel maximum span is 4 feet between hangers.
12.5.4 Main runners (carrying channels) shall be spaced at 4 feet on center maximum.
12.5.5 Cross channels (furring channels) shall be spaced at 24 inches on center maximum for 1/2-inch board and 16 inches on center maximum for thinner board.
12.6 Ceiling Load Limits
12.6.1 The weight of gypsum board, insulation, mechanical items, light fixtures, and other finishes shall not exceed the carrying capacity of the framing or furring system.
12.6.2 Additional ceiling elements shall be supported from structural framing or independent hangers, not from the gypsum board framing, unless the ceiling assembly has been specifically designed for combined loads by a structural engineer.
12.6.3 Heavy items attached to gypsum board walls and ceilings — cabinetry, heavy equipment, signage — shall be attached through the gypsum board to the steel framing or to blocking provided behind the board, not to the board itself.
NOTE Gypsum board alone weighs approximately 2.2 pounds per square foot for 1/2-inch board and 2.7 pounds per square foot for 5/8-inch board, and it has very limited load capacity in fastener withdrawal perpendicular to the face. (12.6.4)
13 Control Joints
13.1 When Control Joints Are Required
13.1.1 Control joints shall be installed at the conditions below, consistent with ASTM C840 and GA-216.
9002500
Default: 2400 sq ft
13.1.2 In walls and partitions, control joints shall be installed where the partition runs in an uninterrupted straight plane exceeding 30 linear feet without a change in plane or an opening, where the partition traverses a structural construction joint — expansion joint, seismic joint, or building expansion joint — in the base building structure, at changes in framing direction, and at locations shown on the drawings.
13.1.3 In ceilings with perimeter relief (floating perimeter), control joints shall be installed where linear dimensions between control joints exceed 50 feet in any direction, or where the total area bounded by control joints exceeds 2,500 square feet.
13.1.4 In ceilings without perimeter relief (gypsum board fixed at perimeter), control joints shall be installed where linear dimensions between control joints exceed 30 feet in any direction, or where the total area bounded by control joints exceeds 900 square feet.
13.2 Control Joint Installation
● Yes — solid backing per GA-234 in all rated assemblies
○ No — non-rated assembly only
Per drawings
13.2.1 Control joints shall be set plumb (on walls) or level (on ceilings) in continuous runs.
13.2.2 The joint shall be held in place by two rows of fasteners in the flanges, one on each side of the spine.
13.2.3 The board face shall be scored along both flanges of the control joint before finishing, so that the compound feathers out to the joint properly.
13.2.4 Joint compound shall be feathered over the flanges but shall not be applied to the spine of the control joint.
13.2.5 Control joints in fire-resistance-rated assemblies shall be installed in conformance with GA-234, Control Joints for Fire-Resistance Rated Assemblies.
13.2.6 The blocking required by GA-234 behind control joints in rated assemblies shall extend the full height of the assembly cavity and shall be attached to the framing on both sides of the joint.
NOTE GA-234 requires solid blocking behind control joints in rated assemblies so that the fire-resistance of the assembly is not compromised by the opening created by the control joint, and a control joint installed in a rated partition without blocking will fail a fire-resistance inspection. (13.2.7)
13.3 Perimeter Relief at Ceilings
NOTE Perimeter relief — a floating ceiling edge that is not fastened to the perimeter wall — allows the ceiling to expand and contract with changes in temperature and humidity without cracking. (13.3.1)
NOTE When perimeter relief is provided, the gypsum board at the ceiling perimeter is not fastened to the wall framing, a control joint bead or casing bead terminates the ceiling board edge, and the joint at the wall is left as a reveal or sealed with a flexible sealant. (13.3.2)
● Yes — floating perimeter (board not fastened to perimeter walls)
○ No — board fastened at perimeter
Per drawings
NOTE Perimeter relief increases the allowable ceiling area between control joints from 900 square feet to 2,500 square feet. (13.3.3)
NOTE In large commercial ceilings, providing perimeter relief is substantially less expensive than installing the additional control joints required without it. (13.3.4)
14 Warranty
14.1 Manufacturer's Warranty
14.1.1 Gypsum board products shall be warranted by the manufacturer against defects in materials and workmanship for a minimum period of one year from the date of delivery.
14.1.2 Fire-resistance-rated products shall be warranted to conform to the referenced ASTM C1396 Type X designation requirements.
14.1.3 Glass-mat products shall be warranted against delamination of the glass-mat facing from the core.
14.2 Installer's Warranty
1 year from substantial completion
2 years from substantial completion
14.2.1 The Contractor shall warrant the gypsum board installation — including all framing, fastening, jointing, and finishing — against defective workmanship for the project warranty period.
14.2.2 Warranty workmanship defects include, but are not limited to, fastener popping, joint ridging, joint cracking, bead delamination, and significant surface cracking caused by inadequate control joints or improper perimeter treatment.
NOTE Normal hairline cracking at joints due to seasonal environmental cycling is not a workmanship defect when control joints have been provided at the required spacing and perimeter treatment has been correctly installed. (14.2.3)
14.3 Conditions Voiding Warranty
14.3.1 Both the manufacturer's and the installer's warranty are voided by subsequent exposure to water damage, by modifications made by others, by application of excessive loads not anticipated in the design, and by building movement that exceeds the designed deflection capacity of the assembly.
14.3.2 The Contractor shall document any conditions observed during installation that may affect the performance or durability of the gypsum board system — such as evidence of water infiltration, inadequate climate control during installation, or structural irregularities — and shall bring them to the Architect's attention before completing the work.