SynC · SynC Standards
Interior Painting
Contents
- 1Scope
- 2Referenced Standards
- 3Submittals
- 3.1Action Submittals
- 3.2Informational Submittals
- 3.3Closeout Submittals
- 4Quality Assurance
- 4.1Applicator Qualification
- 4.2MPI Listing
- 4.3Single Source
- 4.4Field Mock-Up
- 4.5Pre-Application Conference
- 5Environmental and Service Conditions
- 5.1Interior Conditions During Application
- 5.2Illumination During Application and Inspection
- 5.3Ventilation and Odor Control
- 5.4Substrate Cure and Moisture
- 6Paint Systems on Gypsum Board, Plaster, Concrete, and Masonry
- 6.1System Selection
- 6.2Primer on Gypsum Board
- 6.3Primer on Concrete and Plaster
- 6.4Block Filler on Concrete Masonry
- 6.5Finish on Walls in General Spaces
- 6.6Finish on Walls in Scrubbed and Wet-Service Spaces
- 6.7Mildew Resistance in Humid Spaces
- 6.8Coating of Exposed Overhead Structure
- 7Finish Systems on Metal
- 7.1Ferrous Metal Preparation and Primer
- 7.2Shop and Factory Primers
- 7.3Galvanized Steel and Non-Ferrous Metal
- 7.4Finish Coats on Metal
- 7.5Exposed Mechanical and Electrical Work
- 8Finish Systems on Wood
- 8.1Opaque Finishes on Wood
- 8.2Fastener Holes and Joints in Painted Trim
- 8.3Stains and Clear Finishes
- 9Fire-Retardant Coatings
- 10Sheen and Number of Coats
- 10.1Sheen of Walls
- 10.2Sheen of Ceilings
- 10.3Sheen of Trim, Doors, and Metal
- 10.4Number of Finish Coats
- 11Color
- 12Volatile Organic Compounds and Emissions
- 12.1Volatile Organic Compound Content
- 12.2Emissions Testing
- 13Surface Preparation
- 13.1Cleaning and Repair Common to All Substrates
- 13.2Gypsum Board and Plaster Preparation
- 13.3Concrete and Masonry Preparation
- 13.4Previously Painted Surfaces
- 14Coating Application
- 14.1Application Methods
- 14.2Recoat Times and Film Continuity
- 14.3Sequence With Other Work
- 14.4Touch-Up and Final Cleaning
- 15Testing
- 15.1Film Thickness Verification
- 15.2Adhesion Testing
- 15.3Inspection Hold Points
- 16Delivery, Storage, and Handling
- 17Warranty
- 18Extra Stock
Download
Build a datasheet from this standard
Start a project with this standard already attached — one click, no setup.
Use in a project
1 Scope
NOTE This standard governs the surface preparation, priming, and finishing in the field of interior architectural surfaces, where the coating is selected for appearance, cleanability, and ordinary wear rather than for chemical, immersion, or industrial washdown service. (1.1)
1.2 The furnished work shall comprise the surface preparation, primers, block fillers, finish coats, stains, clear finishes, the filling of fastener holes in trim that receives an opaque finish, touch-up, protection of adjacent work, and the field verification this standard requires, on every interior surface the room finish schedule and the interior elevations identify as field painted or field finished.
NOTE The substrates this standard coats are the following. (1.3)
- Gypsum board finished to its scheduled level under Gypsum Board AssembliesGypsum Board AssembliesResolves to the current adopted revision.sync/gypsum-board-assemblies, and gypsum plaster and veneer plaster
- Cast-in-place and precast concrete, the interior face of tilt-up panels, and concrete masonry
- Hollow metal doors and frames delivered with a factory primer
- Structural steel, stairs, railings, miscellaneous metals, metal fabrications, and gratings delivered shop primed, galvanized, or bare and scheduled for a field finish
- The factory-primed curtains, hoods, and guides of coiling doors and the factory-primed sections of sectional doors at interior openings
- Exposed overhead structure, joists, and deck in spaces without a ceiling
- Exposed piping, ductwork, conduit, and their supports in finished spaces
- Wood trim, paneling, casework, stair parts, and wood doors delivered unfinished, factory sealed, or factory primed for a field finish
- Previously painted and previously finished interior surfaces of any of these substrates
NOTE The boundary with High Performance CoatingsHigh-Performance CoatingsResolves to the current adopted revision.sync/high-performance-coatings is the service, not the resin. A waterborne epoxy on the walls of a restroom, a corridor, a janitor's closet, or a food preparation room that is wiped and scrubbed is architectural painting and is governed here; the same resin in a room that is hosed down, sanitized with chemicals, or exposed to process splash is a high-performance system and is governed there. Where a surface sees chemical splash, immersion, or industrial washdown, the whole system for that surface is selected under that standard. (1.4)
NOTE The shop coat ends at the fabricator's door and the site work begins here. The shop primer on structural steel, stairs, railings, miscellaneous metals, and gratings, the factory primer on hollow metal and on coiling and sectional doors, and the factory primer or sealer on trim, casework, and wood doors are each governed by the standard that furnishes the item. This standard governs everything laid over those coats, and its warranty covers what it lays down and not the coat beneath. (1.5)
NOTE Wood is finished under this standard only where it arrives without its final finish. Woodwork, casework, and wood doors that are finished at the factory are not coated in the field, and where a millwork package splits finishing between the shop and the site, the room finish schedule states which surfaces are finished where. (1.6)
1.7 The Contractor shall obtain from each fabricator, door manufacturer, and woodwork supplier the generic type and product identity of the shop primer, factory primer, or factory sealer on every item scheduled for a field finish before the paint system schedule is submitted.
1.8 Where the standard that governs a substrate imposes a longer cure, a cleaner surface, or a tighter moisture limit than this standard, the more stringent requirement shall govern.
2 Referenced Standards
2.1 Materials, surface preparation, and application shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2 Where referenced standards conflict, the more stringent requirement shall govern unless the Architect directs otherwise in writing.
| Standard | Title |
|---|---|
| MPI Architectural Painting Specification Manual | Master Painters Institute interior system numbers, product categories, Approved Products List, and gloss levels |
| MPI Maintenance Repainting Manual | Master Painters Institute repainting systems and degrees of surface degradation |
| ASTM D16 | Terminology for Paint, Related Coatings, Materials, and Applications |
| GA-214 | Levels of Finish for Gypsum Panel Products |
| SSPC-SP 1 | Solvent Cleaning |
| SSPC-SP 2 | Hand Tool Cleaning |
| SSPC-SP 3 | Power Tool Cleaning |
| SSPC-SP 6/NACE No. 3 | Commercial Blast Cleaning |
| SSPC-SP 11 | Power Tool Cleaning to Bare Metal |
| SSPC-SP 13/NACE No. 6 | Surface Preparation of Concrete |
| SSPC-SP 16 | Brush-Off Blast Cleaning of Coated and Uncoated Galvanized Steel, Stainless Steels, and Non-Ferrous Metals |
| SSPC-PA 2 | Procedure for Determining Conformance to Dry Coating Thickness Requirements |
| ASTM D4258 | Practice for Surface Cleaning Concrete for Coating |
| ASTM D4259 | Practice for Abrading Concrete |
| ASTM D4262 | Test Method for pH of Chemically Cleaned or Etched Concrete Surfaces |
| ASTM D4263 | Test Method for Indicating Moisture in Concrete by the Plastic Sheet Method |
| ASTM D4444 | Test Method for Laboratory Standardization and Calibration of Hand-Held Moisture Meters |
| ASTM D3359 | Test Methods for Rating Adhesion by Tape Test |
| ASTM D7091 | Practice for Nondestructive Measurement of Dry Film Thickness of Nonmagnetic Coatings Applied to Ferrous Metals and Nonmagnetic, Nonconductive Coatings Applied to Non-Ferrous Metals |
| ASTM D523 | Test Method for Specular Gloss |
| ASTM D2244 | Practice for Calculation of Color Tolerances and Color Differences from Instrumentally Measured Color Coordinates |
| ASTM D2486 | Test Methods for Scrub Resistance of Wall Paints |
| ASTM D3273 | Test Method for Resistance to Growth of Mold on the Surface of Interior Coatings in an Environmental Chamber |
| ASTM D3274 | Test Method for Evaluating Degree of Surface Disfigurement of Paint Films by Fungal or Algal Growth, or Soil and Dirt Accumulation |
| ASTM E84 | Test Method for Surface Burning Characteristics of Building Materials |
| ANSI/SDI A250.10 | Test Procedure and Acceptance Criteria for Prime Painted Steel Surfaces for Steel Doors and Frames |
| NFPA 13 | Standard for the Installation of Sprinkler Systems |
| NFPA 80 | Standard for Fire Doors and Other Opening Protectives |
| 40 CFR Part 59, Subpart D | National Volatile Organic Compound Emission Standards for Architectural Coatings |
| OTC Model Rule for Architectural and Industrial Maintenance Coatings | Ozone Transport Commission |
| CARB Suggested Control Measure for Architectural Coatings | California Air Resources Board |
| SCAQMD Rule 1113 | Architectural Coatings |
| CDPH Standard Method v1.2 | Standard Method for the Testing and Evaluation of Volatile Organic Chemical Emissions from Indoor Sources Using Environmental Chambers |
| 40 CFR Part 745 | Lead-Based Paint Poisoning Prevention in Certain Residential Structures |
| 29 CFR 1926.62 | Lead in Construction |
NOTE The MPI manual assigns a product number to each generic coating type that passes a defined set of performance tests, and an interior system number to each combination of substrate, primer, and finish, so a coating can be specified by performance class without naming a manufacturer. The Approved Products List names the products from competing manufacturers that have passed the tests for each number. The surface preparation standards once published by SSPC and NACE are now maintained by AMPP; the SP numbers remain in use and are cited here. (2.3)
3 Submittals
3.1 Action Submittals
3.1.1 The submittals listed below shall be reviewed and returned before any coating material is ordered or applied.
- Product data for every primer, block filler, finish, stain, and clear finish, stating the generic resin type, the MPI product number where one applies, the substrates the product is published for, the wet and dry film thickness per coat, the spreading rate, the recoat times, the application temperature and humidity limits, the scrub resistance by ASTM D2486 of each wall finish, and the volatile organic compound content in grams per liter
- Paint system schedule assigning to every interior substrate and room finish designation the surface preparation, the primer, the finish, the number of coats, the sheen, and the MPI interior system number where one applies
- Color drawdowns of every color and sheen scheduled, at the number of coats the schedule requires, not smaller than 8 in. by 10 in.
- Stain and clear finish samples on the species, cut, and grade of wood being finished, not smaller than 6 in. by 12 in., stepped to show the stain, the sealer, and each clear coat
- Test reports and listings for a fire-retardant coating, where the Fire-Retardant Coatings article applies
Action Submittals Requiredcheckbox
☑ Product data for every coating product
☑ Paint system schedule by substrate
☑ Color drawdowns of every color and sheen
☐ Stain and clear finish samples on the project wood
☐ Fire-retardant coating test reports
3.1.2 The Architect's acceptance of a drawdown or a wood finish sample shall establish the color and sheen standard for the surfaces it represents, and no material shall be tinted in bulk before the drawdown for that color is accepted.
3.2 Informational Submittals
3.2.1 The Contractor shall submit the following for record, without waiting for return, before the corresponding work begins.
- Applicator qualification statement listing the comparable projects the Applicator Qualification article requires
- The coating manufacturer's written confirmation that each field system is compatible with the shop primer, factory primer, or factory sealer identified on each item it will cover
- The manufacturer's certification of the volatile organic compound content of every product against the regulatory basis selected under Volatile Organic Compound Content, and the emissions test documentation where the Emissions Testing article requires it
- Safety data sheets for every product
- The record of substrate moisture and pH readings taken under Substrate Cure and Moisture
- The record of mock-up acceptance, where a mock-up is required
Informational Submittals Requiredcheckbox
☑ Applicator qualification statement
☑ Primer and sealer compatibility confirmations
☑ Volatile organic compound and emissions documentation
☑ Safety data sheets
☐ Substrate moisture and pH record
☐ Mock-up acceptance record
3.3 Closeout Submittals
3.3.1 The Contractor shall submit the following before final acceptance.
- Record paint schedule stating, for every room finish designation, the product and MPI number applied, the color name and tint formula, the sheen, and the number of coats
- The manufacturer's published product warranty for every product that carries one
- The Contractor's warranty under the Warranty section
- Maintenance instructions stating the interval before the film may first be washed, the cleaning methods and cleaning agents each finish tolerates, and the touch-up procedure
- The Owner's signed receipt for the extra stock delivered
Closeout Submittals Requiredcheckbox
☑ Record paint schedule with tint formulas
☑ Manufacturer product warranties
☑ Contractor warranty
☑ Maintenance and cleaning instructions
☑ Extra stock receipt
4 Quality Assurance
4.1 Applicator Qualification
4.1.1 Interior painting shall be performed by an applicator that has completed interior painting of comparable substrates, systems, and extent on not fewer than the number of projects indicated in the datasheet within the five years preceding the bid.
Comparable Projects Completed by the Applicatorrange
Not less than
projects
010
4.2 MPI Listing
4.2.1 Each coating product shall meet the performance of the MPI product category assigned to its position in the paint system schedule, and whether listing on the MPI Approved Products List is required shall be as indicated in the datasheet.
MPI Approved Products Listradio
○ Every product listed on the current MPI Approved Products List for its MPI number
○ Products meeting the MPI performance category, listing not required
NOTE Requiring the listing puts the performance test in MPI's laboratory and leaves the submittal reviewer to check a number against a list, and it limits the bid to the listed products of each manufacturer. Accepting unlisted products that meet the category admits regional and newly introduced products, and it moves the burden of judging the manufacturer's test data onto the submittal review. (4.2.2)
4.3 Single Source
4.3.1 The primer, intermediate, and finish coats within each paint system shall be products of one manufacturer, unless the datasheet permits coats from different manufacturers.
Paint System Sourcingradio
● One manufacturer for every coat of each system
○ Primer and finish from different manufacturers with written compatibility confirmation from both
4.3.2 Where coats from different manufacturers are permitted, the Contractor shall obtain the written confirmation of both manufacturers that the coats are compatible over the specified substrate and preparation, and shall submit it before either coat is applied.
NOTE A manufacturer stands behind the film it formulated as a system and declines a film built on another manufacturer's primer, so a mixed system carries only the Contractor's warranty. Shop primers, factory primers, and factory sealers delivered on items from other trades are outside this rule; their compatibility with the field system is handled under the Shop and Factory Primers article. (4.3.3)
4.4 Field Mock-Up
4.4.1 The mock-up program shall be as indicated in the datasheet.
Mock-Up Programselect
No mock-up required
One mock-up of each paint system
One mock-up of each paint system in each color
One mock-up room finished complete in every system and color it contains
4.4.2 Each wall or ceiling mock-up shall be applied on the actual substrate at a location the Architect designates, over an area not less than indicated in the datasheet, and shall show the full surface preparation, primer, and finish coats at the specified sheen and color.
Mock-Up Arearange
Not less than
ft²
2550100200400
4.4.3 A mock-up of a door, a frame, a run of trim, or a wood finish shall be one complete door leaf with its frame, or not less than 8 ft of trim or one panel, finished on the actual item.
4.4.4 The mock-up shall be viewed under the permanent lighting of the space, or under temporary lighting set at the angle and intensity of the permanent lighting, before acceptance, and the accepted mock-up shall be the standard of appearance and workmanship for the production work.
4.4.5 The accepted mock-up shall remain in place and protected until the work it represents is accepted, and may remain as part of the completed work.
NOTE A drawdown shows a color on a flat card; a mock-up shows it on the wall, at the finish level of the board, under the light that will rake it. No mock-up is the practice where a tenant or an owner repeats a palette it already knows. One mock-up per system settles the appearance of the film and the hide of the joint treatment; one per color adds the color judgment, which matters with deep tones and with colors that meet at a corner. A complete mock-up room is the practice on a hotel, a residence hall, or a patient unit where one room repeats hundreds of times and the finishes are judged together with the flooring, the casework, and the lighting. Each step adds cost and a hold on the schedule. (4.4.6)
4.5 Pre-Application Conference
4.5.1 Whether a pre-application conference is held before interior painting begins shall be as indicated in the datasheet.
Pre-Application Conferenceradio
○ Conference required before interior painting begins
○ No conference required
4.5.2 Where a conference is required, the Contractor shall convene it with the applicator, the gypsum board finisher, and the installers of the doors, frames, and woodwork to be finished, and the conference shall review the paint system schedule, the finish level of each surface, the shop and factory primers identified, the mock-up program, the conditions the building will be held at, the sequence with flooring, ceilings, and equipment setting, and the inspection hold points.
NOTE The conference is where the level of gypsum board finish, the sheen scheduled over it, and the lighting that will rake it are compared before joint treatment starts rather than after the first coat shows the joints. It is held where gloss or deep-tone finishes, field-finished wood, or several primed substrates from other trades are in the work, and skipped where the scope is flat and eggshell latex on board. (4.5.3)
5 Environmental and Service Conditions
5.1 Interior Conditions During Application
5.1.1 Coatings shall not be applied when the air temperature or the surface temperature is below the minimum indicated in the datasheet, or above the maximum the manufacturer publishes for the product.
Air and Surface Temperature During Applicationrange
Not less than
°F
35404550556065
5.1.2 Coatings shall not be applied when the relative humidity in the space exceeds the value indicated in the datasheet.
Relative Humidity During Applicationrange
Not more than
%
5090
Default: 85 %
5.1.3 The temperature and humidity limits shall be maintained from 24 hours before application begins until the final coat has cured for not less than 48 hours, and the Contractor shall provide the temporary heat, dehumidification, and ventilation needed to hold them where the permanent systems are not operating.
5.1.4 Coatings shall not be applied unless the surface temperature is at least 5°F above the dew point of the air in the space.
5.1.5 Field-applied stains and clear finishes on wood shall not be applied until the space has been held within the temperature and humidity range the Section governing the woodwork requires for its installation, and that range shall be held through the cure of the final coat.
5.1.6 Heaters that exhaust combustion products into the space shall not be used to heat a space while coatings are applied or curing.
NOTE Below its minimum film-forming temperature a waterborne coating does not coalesce: the polymer particles never fuse into a continuous film, and the coat looks acceptable when applied and scrubs off or cracks later. Conventional interior latex holds that minimum at 50°F; formulations rated to 35°F are sold by several manufacturers and are selected where the building will be painted before permanent heat. The upper setpoints serve clear finishes and two-component products whose data sheets ask for a warmer room. High humidity slows the release of water from the film, leaches surfactant to the surface of a fresh latex coat as a sticky or glossy streak, and holds joint compound damp beneath the primer. An unvented direct-fired heater adds water vapor and combustion products to the air, and the film yellows and stays soft. (5.1.7)
5.2 Illumination During Application and Inspection
5.2.1 The illumination at the surface being coated, during surface preparation, application, and inspection, shall be not less than indicated in the datasheet.
Illumination at the Surface During Application and Inspectionrange
Not less than
fc
1020305075100
5.2.2 Final inspection of walls and ceilings shall be made under the permanent lighting of the space, or with the daylight condition the space will have, and not under temporary lighting alone.
NOTE A painter cannot hide what cannot be seen, and a film inspected under a string of work lights is inspected at an angle that conceals lap marks, holidays, and joint telegraphing. The lower setpoints are the general construction lighting of a building in progress; the higher ones are what gloss finishes, dark colors, and stain work on wood are applied under. A wall washed by a window or a wall-wash fixture shows every roller lap that a ceiling troffer would hide, which is why the final look is taken under the permanent condition. (5.2.3)
5.3 Ventilation and Odor Control
5.3.1 The Contractor shall ventilate each space during application and until the final coat has dried, at the rate the coating manufacturer publishes, without drawing dust across wet film.
5.3.2 In an occupied building, the Contractor shall isolate the work area from the occupied areas and from the return air path of operating air handling systems while solvent-borne and two-component coatings are applied and until their odor has dissipated.
NOTE Moving air carries the water or solvent out of the film, and a closed room at saturation stops a latex coat from drying at all. A return grille left open in a work area distributes the odor of an alkyd, a shellac primer, or a solvent-borne clear finish through every space the air handler serves. (5.3.3)
5.4 Substrate Cure and Moisture
5.4.1 Concrete, concrete masonry, and portland cement or lime plaster shall have cured not less than the number of days indicated in the datasheet before a coating is applied, unless the coating manufacturer publishes a shorter interval for the product and a moisture test under this article confirms the substrate is within the manufacturer's limit.
Cure of Cementitious Substrates Before Coatingrange
Not less than
days
7142128
5.4.2 Concrete and concrete masonry shall be tested for moisture by ASTM D4263 before coating and shall show no condensation beneath the sheet; where an electronic moisture meter calibrated to ASTM D4444 is used on concrete, masonry, plaster, or gypsum board, the reading shall not exceed the value indicated in the datasheet.
Moisture Reading of Wall and Ceiling Substratesrange
Not more than
%
816
Default: 12 %
5.4.3 The surface pH of concrete, masonry, and plaster shall be tested by ASTM D4262 before priming, and a surface whose pH exceeds the primer manufacturer's published limit shall be allowed to cure further or shall receive an alkali-resistant primer the manufacturer publishes for that pH.
5.4.4 Gypsum board joint compound, skim coats, and patching shall be dry through their full depth, uniform in color with no dark damp areas, before the primer is applied.
5.4.5 Interior wood shall not be primed, stained, or finished when its moisture content, measured with a meter calibrated to ASTM D4444, exceeds the value indicated in the datasheet.
Moisture Content of Wood Before Finishingrange
Not more than
%
615
Default: 12 %
5.4.6 The Contractor shall take moisture readings at not fewer than one location per 1,000 ft² of each cementitious or plaster substrate and at each area that shows a visible damp mark, and shall record the readings.
NOTE Fresh concrete, mortar, and plaster carry free water and a surface alkalinity that attack a film from behind: the water blisters it, and the alkali saponifies an alkyd binder and burns the color out of some pigments. Twenty-eight days is the age at which ordinary cementitious surfaces in a conditioned building have dropped to a pH and a moisture level most primers tolerate; the shorter intervals are used with primers published for young concrete and are confirmed by test rather than by the calendar. Joint compound that is primed damp stays soft, shrinks later, and shows as a recessed or flashing joint. Wood that is finished wet shrinks under the film after the building is conditioned, and the joint lines of trim and the panel edges of doors open as unfinished stripes. (5.4.7)
6 Paint Systems on Gypsum Board, Plaster, Concrete, and Masonry
6.1 System Selection
6.1.1 The paint system for each substrate shall be as indicated in the datasheets of this section and of the Finish Systems on Metal and Finish Systems on Wood sections, and the paint system schedule shall assign a system to every interior surface scheduled for painting.
6.1.2 Each system shall consist of the primer this standard or the manufacturer requires for the substrate, plus the number of finish coats indicated under Number of Finish Coats.
6.1.3 The datasheets set one system for the general spaces of the building and one for its scrubbed and wet-service spaces, and the room finish schedule shall identify which spaces receive each.
NOTE A building's rooms divide, for paint, by how the walls are cleaned. Offices, classrooms, dwelling units, and conference rooms are dusted and occasionally wiped. Restrooms, janitor's closets, food preparation rooms, locker rooms, clinical rooms, and service corridors are scrubbed with detergent and disinfectant and see splash and steam. One finish does not serve both economically, and the two fields below let a project set each once and let the room finish schedule sort the rooms. (6.1.4)
6.2 Primer on Gypsum Board
6.2.1 The primer on new gypsum board shall be as indicated in the datasheet.
Primer on New Gypsum Boardselect
Acrylic latex primer-sealer
Polyvinyl acetate primer-sealer
High-build latex primer-surfacer
NOTE An acrylic latex primer-sealer evens the absorption of face paper and joint compound, holds sheen uniformity under eggshell and higher finishes, and accepts epoxy and enamel finish coats. A polyvinyl acetate primer-sealer seals new board at the lowest cost and is the base under flat and low-sheen latex; under a gloss, an epoxy, or a deep-tone finish it holds out less evenly, and joints show as a difference in sheen. A high-build primer-surfacer is sprayed at several times the film thickness of a sealer, fills the texture difference between paper and compound, and sands; it adds a spray operation and its masking. (6.2.2)
6.2.3 Where the Section governing gypsum board, Gypsum Board AssembliesGypsum Board AssembliesResolves to the current adopted revision.sync/gypsum-board-assemblies on this Project, selects a spray-applied primer-surfacer as the Level 5 surface, the Contractor shall apply a product that the gypsum board manufacturer and the finish paint manufacturer both accept for that use, at the film thickness its manufacturer publishes for a Level 5 surface, before the finish coats.
6.2.4 Where a vapor retarder coating has been applied to the gypsum board ahead of the painting work, the first coat laid over it shall be a product the vapor retarder coating manufacturer identifies as compatible, and the vapor retarder coating shall not be sanded through.
6.2.5 Gypsum board whose face paper has been scuffed or raised by sanding shall be sealed with a primer the manufacturer publishes for damaged paper before joint compound repair and the wall primer are applied.
6.3 Primer on Concrete and Plaster
6.3.1 The primer on concrete, on the interior face of precast and tilt-up panels, and on plaster shall be as indicated in the datasheet.
Primer on Concrete and Plasterradio
○ Alkali-resistant acrylic primer-sealer
○ First coat of the finish material applied as a self-primer
NOTE An alkali-resistant acrylic primer-sealer tolerates a higher surface pH than a finish coat does and evens the absorption of a troweled or formed surface, which is the case on plaster and concrete coated near the end of the cure period. Many acrylic wall finishes are published as self-priming on cured, sound concrete, and the first coat of the finish then serves as the primer and saves a product; the manufacturer's data sheet states the pH and age at which that is permitted. (6.3.2)
6.3.3 Alkyd coatings shall not be applied directly to concrete, concrete masonry, or plaster, because the alkalinity of the substrate saponifies the alkyd binder.
6.3.4 Where the interior face of a precast or tilt-up panel carries a bond breaker, curing compound, or form-release residue, the Contractor shall remove it under the Concrete and Masonry Preparation article before priming, and shall confirm the removal by the water absorption check that article requires.
6.4 Block Filler on Concrete Masonry
6.4.1 Whether concrete masonry receives a block filler shall be as indicated in the datasheet.
Block Filler on Concrete Masonryradio
● Latex block filler before the finish coats
○ No block filler
6.4.2 Block filler shall be applied by roller, or by spray with back-rolling, in the quantity needed to fill the surface voids of the masonry and present a continuous, pinhole-free surface to the coat that follows.
6.4.3 Where a two-component epoxy finish is selected for concrete masonry in scrubbed and wet-service spaces, the block filler shall be an epoxy or epoxy-compatible filler the finish manufacturer publishes for the system.
NOTE Concrete masonry is open-celled, and finish coats applied straight to it sink into the voids and leave pinholes that hold soil and cannot be wiped clean. A block filler closes the texture at a fraction of the finish material's cost per mil. It is omitted where the open texture of the block is the appearance the design wants, where the units are ground-face or prefinished, and in storage and utility rooms where a painted, unfilled wall is accepted. (6.4.4)
6.5 Finish on Walls in General Spaces
6.5.1 The finish coat material on gypsum board, plaster, concrete, and concrete masonry walls and ceilings in general spaces shall be as indicated in the datasheet.
Finish on Walls and Ceilings in General Spacesselect
Vinyl-acrylic latex
100 percent acrylic latex
Scuff-resistant waterborne enamel
6.5.3 Ceilings in general spaces shall receive the same generic finish material as the walls, at the sheen selected under Sheen of Ceilings, unless the paint system schedule assigns a ceiling-grade flat latex of the same resin.
6.6 Finish on Walls in Scrubbed and Wet-Service Spaces
6.6.1 The finish coat material on walls and ceilings in the scrubbed and wet-service spaces the room finish schedule identifies shall be as indicated in the datasheet.
Finish on Walls and Ceilings in Scrubbed and Wet-Service Spacesselect
100 percent acrylic latex enamel
Single-component waterborne epoxy
Two-component waterborne epoxy
Not applicable, no scrubbed or wet-service spaces
NOTE A 100 percent acrylic latex enamel at satin or semi-gloss sheds water and takes detergent washing, and it is what restrooms and kitchens in dwelling units and small offices receive. A single-component waterborne epoxy, sold pre-catalyzed, applies like latex with no mixing or pot life and cures to a harder, more stain-resistant and disinfectant-tolerant film; it is the common finish in public restrooms, school and healthcare corridors, and food preparation rooms that are wiped down. A two-component waterborne epoxy cross-links to the hardest and most chemical-tolerant film of the three and is selected for janitor's closets, locker and shower rooms outside the spray zone, commissary kitchens, and animal and clinical rooms cleaned with strong disinfectants; it requires measured mixing, has a pot life, yellows slightly with age, and is more difficult to touch up. (6.6.2)
6.6.3 Where a two-component waterborne epoxy is selected, the primer or first coat on each substrate shall be the product the epoxy manufacturer publishes for that substrate under the epoxy.
6.6.4 Surfaces inside the spray zone of a shower, and surfaces that are continuously wet, shall not be finished with paint under this standard unless the room finish schedule assigns a paint system to them.
NOTE Paint on gypsum board is not a waterproof membrane. A film that sheds splash and steam still passes water at a pinhole or a crack, and the board behind it softens, which is why shower enclosures are tiled or lined and why a painted ceiling over a shower is scheduled deliberately, on a moisture-resistant or cementitious substrate, when it is scheduled at all. (6.6.5)
6.7 Mildew Resistance in Humid Spaces
6.7.1 Whether the finish coats in scrubbed and wet-service spaces are a mildew-resistant formulation shall be as indicated in the datasheet.
Mildew Resistance of Finish Coats in Scrubbed and Wet-Service Spacesradio
○ Mildew-resistant formulation tested by ASTM D3273 and rated by ASTM D3274
○ No mildew-resistance requirement
NOTE A mildew-resistant finish carries a film preservative that slows mold growth on the surface of the paint, and the test makes that claim checkable. It does nothing for mold growing in the board or behind the film, and it does not replace exhaust ventilation. It is waived where an Owner's environmental program excludes biocidal additives. (6.7.2)
6.8 Coating of Exposed Overhead Structure
6.8.1 The finish on exposed overhead structure, joists, deck, and overhead services in spaces without a ceiling, where the room finish schedule identifies them as painted, shall be as indicated in the datasheet.
Finish on Exposed Overhead Structure and Deckselect
Waterborne acrylic dry-fall coating
Alkyd dry-fall coating
Conventional acrylic latex applied by spray
Not applicable, no painted exposed overhead structure
NOTE A dry-fall coating is formulated so that its overspray dries to a dust within the fall distance its manufacturer publishes, commonly 10 ft to 25 ft depending on the product and the room conditions, and can be swept from the floor and from stored goods, which is what makes spraying a deck 20 ft overhead practical. The waterborne acrylic type has little odor, meets every volatile organic compound basis, bonds to galvanized deck, and flash-rusts bare or poorly primed steel unless a rust-inhibitive grade or a primer is used. The alkyd type covers shop-primed joists and light rust in one coat and tolerates a cool building; it carries solvent odor, does not go directly on galvanizing, and is restricted under the strict volatile organic compound bases. A conventional acrylic latex gives a wider choice of sheen and color, including the deep tones of an open ceiling painted out dark, and every surface below has to be masked because its overspray lands wet. (6.8.2)
6.8.3 Dry-fall coatings shall be applied only when the temperature and humidity in the space are within the range the manufacturer publishes for dry-fall performance, and the Contractor shall protect surfaces within the published fall distance as for a conventional coating.
6.8.4 Galvanized deck and galvanized ductwork overhead shall be cleaned of oil and passivation under the Galvanized Steel and Non-Ferrous Metal article before a dry-fall coating is applied, and an alkyd dry-fall coating shall be applied to galvanizing only over a primer the manufacturer publishes for it.
6.8.5 Surfaces that carry or are scheduled to carry spray-applied fire-resistive material or an intumescent fire-resistive coating shall not be painted under this standard except with a topcoat the fire-resistive material's manufacturer lists for use over it.
7 Finish Systems on Metal
7.1 Ferrous Metal Preparation and Primer
7.1.1 Bare ferrous metal, and the bare areas of shop-primed or factory-primed ferrous metal, shall be solvent cleaned to SSPC-SP 1 and then prepared to the grade indicated in the datasheet before priming.
Surface Preparation Grade for Bare Ferrous Metalselect
SSPC-SP 2, Hand Tool Cleaning
SSPC-SP 3, Power Tool Cleaning
SSPC-SP 11, Power Tool Cleaning to Bare Metal
SSPC-SP 6, Commercial Blast Cleaning
NOTE Hand and power tool cleaning remove loose rust, loose mill scale, and loose coating and leave the tight material in place; they are the grades a field crew reaches on a frame, a railing, or a stair stringer inside a building, and they serve an alkyd or acrylic primer that tolerates a tight residue. Power tool cleaning to bare metal removes everything at a weld or a repair and is what an epoxy primer needs where blasting is impractical. Commercial blast cleaning is uncommon inside a building because of its dust and containment; it is selected for bare steel that is delivered unprimed in quantity and prepared before the space is enclosed or finished. (7.1.2)
7.1.3 The field primer on ferrous metal shall be as indicated in the datasheet.
Field Primer on Ferrous Metalselect
Rust-inhibitive alkyd primer
Waterborne acrylic rust-inhibitive primer
Waterborne epoxy primer
7.2 Shop and Factory Primers
7.2.1 Before a finish system is applied over a shop or factory primer, the Contractor shall obtain the field coating manufacturer's written confirmation that the finish system is compatible with that primer, as the Informational Submittals article requires.
7.2.2 Where compatibility cannot be confirmed, the Contractor shall apply a tie coat or barrier primer the finish manufacturer publishes for the purpose over the primer, or shall remove the primer and prime the surface under the Ferrous Metal Preparation and Primer article, as the Architect directs.
7.2.3 Damaged shop or factory primer, field welds, bolted connections, field-cut edges, and bare areas shall be cleaned to the grade selected under Ferrous Metal Preparation and Primer and spot primed with a primer the field coating manufacturer publishes as compatible with both the shop primer and the finish, before the finish coats are applied.
7.2.4 Hollow metal doors and frames delivered with a factory primer to ANSI/SDI A250.10 shall be cleaned of handling soil, sanded smooth where the primer is rough or carries runs, spot primed where the primer is damaged, and finished with the system selected under Finish Coats on Metal.
7.2.5 Hollow metal frames shall be finished on every exposed face, including the rabbets, the stops, and the faces behind the door in its closed position, and a frame set in masonry or at a wet location shall have its factory primer intact before it is finished.
7.2.6 Shop-primed structural steel, stairs, railings, miscellaneous metals, and gratings exposed in a finished space shall have their erection marks, weld spatter, and handling soil removed, and their exposed welds and bolted connections spot primed, before the finish coats.
7.2.7 The interior faces of factory-primed coiling door curtains, hoods, and guides and of factory-primed sectional door sections, where scheduled for a field finish, shall receive the system selected under Finish Coats on Metal over the factory primer, and the film on a coiling curtain shall cure for the interval the coating manufacturer publishes before the door is cycled.
NOTE A shop primer is a shipping coat formulated to be covered. A finish applied over a primer it does not wet, or a strong-solvent finish over a soft primer, lifts or wrinkles at the interface, and when it does the fabricator points to the painter and the painter to the fabricator; the written compatibility confirmation and the identity of the primer on the shop drawings are what make one party answerable. A coiling curtain rolled before the film has hardened blocks, slat against slat, and pulls the coating off both faces. (7.2.8)
7.3 Galvanized Steel and Non-Ferrous Metal
7.3.1 Galvanized steel shall be solvent cleaned to SSPC-SP 1 and then cleaned of its passivating treatment, storage oils, and white rust by the method the primer manufacturer publishes, and shall be given a profile by SSPC-SP 16 where the primer manufacturer requires one, before priming.
7.3.2 The primer on galvanized steel shall be as indicated in the datasheet.
Primer on Galvanized Steelselect
Waterborne acrylic primer formulated for galvanizing
Epoxy primer formulated for galvanizing
Vinyl wash primer
Acrylic direct-to-metal finish applied as its own primer
NOTE New galvanizing carries a passivation treatment and rolling oils that shed ordinary primers, and zinc saponifies an alkyd binder. A waterborne acrylic primer formulated for galvanizing bonds to a cleaned zinc surface without etching, meets every volatile organic compound limit, and is what most manufacturers publish under their latex and waterborne enamel finishes. An epoxy primer formulated for galvanizing is the base under an epoxy finish in the scrubbed and wet-service spaces. A vinyl wash primer etches the zinc chemically and is the traditional base under an alkyd; its solvent content places it outside the strict volatile organic compound bases and makes it unwelcome in an occupied building. Several direct-to-metal acrylics are published as self-priming on cleaned galvanizing and save a coat on ductwork, conduit, and deck. (7.3.3)
7.3.4 Alkyd primers and alkyd finish coats shall not be applied directly to galvanized steel.
7.3.5 Mill-finish aluminum, copper, and other non-ferrous metals scheduled for a field finish shall be solvent cleaned to SSPC-SP 1, abraded where the primer manufacturer requires it, and primed with a bonding primer the finish manufacturer publishes for the metal.
7.3.6 Factory-finished metal, anodized aluminum, stainless steel, chrome, and bronze shall not be field painted unless the Contract Documents direct it.
7.4 Finish Coats on Metal
7.4.1 The finish coat material on hollow metal doors and frames, structural and miscellaneous steel, stairs, railings, galvanized steel, and non-ferrous metal in general spaces shall be as indicated in the datasheet.
Finish on Doors, Frames, and Metalselect
Acrylic latex enamel
Waterborne alkyd enamel
Solvent-borne alkyd enamel
Waterborne acrylic-urethane enamel
Single-component waterborne epoxy
7.4.3 In the scrubbed and wet-service spaces, metal shall receive a finish that the manufacturer of the wall finish selected for those spaces publishes for metal, over the primer that manufacturer publishes for the substrate.
7.4.4 Field paint on stair treads, grating, floor plate, and other walking surfaces shall be applied only where the room finish schedule or the Drawings identify the surface as painted, and shall not reduce the slip resistance the Section governing the walking surface requires.
NOTE Where a metal surface sees chemical splash, immersion, or industrial washdown, its coating system is selected under High Performance CoatingsHigh-Performance CoatingsResolves to the current adopted revision.sync/high-performance-coatings rather than from this datasheet. (7.4.5)
7.5 Exposed Mechanical and Electrical Work
7.5.1 Whether exposed piping, ductwork, conduit, boxes, and their hangers and supports in finished spaces are painted shall be as indicated in the datasheet.
Exposed Mechanical and Electrical Work in Finished Spacesradio
○ Painted to the color the room finish schedule assigns
○ Left in the finish furnished by the installing trade
7.5.2 Where exposed mechanical and electrical work is painted, each material shall be prepared and primed as this standard requires for its substrate: galvanized duct and conduit as galvanized steel, black steel pipe and hangers as ferrous metal, copper as non-ferrous metal, plastic pipe with a bonding primer the manufacturer publishes for the plastic, and insulation jacketing with a primer the finish manufacturer publishes for the jacket.
7.5.3 The following shall not be painted, and shall be masked or removed before adjacent surfaces are coated.
- Automatic sprinklers and their cover plates, which NFPA 13 requires to be replaced where they have been painted in the field
- Fire door, frame, and fire damper labels under NFPA 80, listing marks, and the grade stamps and treatment marks on fire-retardant-treated plywood backboards
- Equipment nameplates, data plates, and factory-finished equipment, panels, and devices
- Valve stems, operators, and moving parts; flexible connections and vibration isolators; and machined, lubricated, and sliding surfaces
- Pipe markers, valve tags, wire markers, and other identification
- Stainless steel, chrome-plated, and anodized surfaces
- Hardware, gasketing, sealant joints designed to move, and the acoustical surface of sound-absorptive ceilings and panels
7.5.4 Walls and ceilings of mechanical, electrical, and communications rooms that are scheduled for painting shall be painted through the finish coat before equipment is set against them, and no coating shall be sprayed in a room after equipment is set.
7.5.5 Interior surfaces of ductwork visible through grilles and diffusers in finished spaces shall be painted flat black to the depth visible from the room, where the reflected ceiling plans or the room finish schedule requires it.
NOTE Painting exposed services to the ceiling color is what makes an open ceiling read as one plane; leaving them in mill and galvanized finishes is the practice in back-of-house and in spaces designed around the exposed materials. Paint on a sprinkler changes its thermal response, paint on a label removes the evidence a fire inspector needs, and paint on a valve stem or a damper linkage binds it. (7.5.6)
8 Finish Systems on Wood
8.1 Opaque Finishes on Wood
8.1.1 The primer under an opaque finish on interior wood and on medium density fiberboard shall be as indicated in the datasheet.
Primer on Interior Wood Under an Opaque Finishselect
Alkyd enamel undercoater
Acrylic latex enamel undercoater
Pigmented shellac primer
NOTE An alkyd enamel undercoater seals the grain, blocks tannin and knot bleed on pine, cedar, and oak better than latex, does not raise the grain, and sands to a powder; it carries solvent odor and is restricted under the strict volatile organic compound bases. An acrylic latex enamel undercoater meets every limit and stays flexible, raises the grain on the first coat so that a sanding is needed, and blocks bleed less completely on resinous species. A pigmented shellac primer blocks knots, sap, water stains, and smoke most completely and dries in minutes; it is brittle, alcohol-borne, and usually confined to spot sealing, and it is selected as the full prime coat on knotty species and on fire- or water-stained renovation work. (8.1.2)
8.1.3 Knots, sap streaks, and resinous areas shall be spot sealed with a pigmented shellac or other stain-blocking sealer before the primer, whichever primer is selected.
8.1.4 Unprimed trim scheduled for an opaque finish shall be back-primed, and its cut ends primed, with the primer selected in the datasheet before the trim is installed.
8.1.5 Factory-primed trim, casework, and doors shall be finished over the factory primer after the compatibility confirmation the Informational Submittals article requires, and field cuts, sanded-through areas, and cut ends shall be spot primed with the primer selected in the datasheet.
8.1.6 The opaque finish coat material on interior wood shall be as indicated in the datasheet.
Opaque Finish on Interior Woodselect
Acrylic latex enamel
Waterborne alkyd enamel
Solvent-borne alkyd enamel
Waterborne acrylic-urethane enamel
NOTE The trade-offs are those stated for the same resins under Finish Coats on Metal, with two differences on wood. Wood moves with the seasons, so the flexibility of an acrylic keeps joint lines closed longer, while the harder alkyd and urethane films resist the blocking of a window stool, a shelf, or a door against its stop. A brushed finish on wide casings and panel doors shows leveling more than a frame does, which favors the alkyd types where a brushed appearance is the standard of the work. (8.1.7)
8.2 Fastener Holes and Joints in Painted Trim
8.2.1 Fastener holes, open grain defects, and minor dents in trim, casework, and doors that receive an opaque finish shall be filled by the Contractor under this standard, after the primer is applied and before the first finish coat, with a non-shrinking filler the finish manufacturer publishes as paintable, and shall be sanded flush and spot primed.
8.2.2 Joints between painted trim and the adjacent painted wall, and open miters and butt joints in painted trim not exceeding 1/16 in., shall be closed with a paintable acrylic latex sealant after priming, and a joint wider than 1/16 in. shall be reported to the Architect as a defect of the trim installation rather than filled.
8.2.3 Fastener holes in wood that receives a stain or a clear finish are filled under the Section that installs the wood, with a filler matched to the finished color; the Contractor shall apply the stain and the first clear coat ahead of that filling and the remaining clear coats after it.
NOTE Filler applied to bare wood loses its binder into the wood, shrinks, and shows as a dimple under the enamel, which is why the primer goes on first. A sealant bead at the wall hides the shadow line of a casing against an uneven wall; it is not a repair for a miter that was cut open. (8.2.4)
8.3 Stains and Clear Finishes
8.3.1 Requirements in this article apply to wood the room finish schedule identifies as field stained, field clear finished, or both.
8.3.2 Wood shall be stained to match the accepted wood finish sample, with a stain of a type the clear finish manufacturer publishes as compatible beneath the clear finish selected.
8.3.3 Species that absorb stain unevenly, including maple, birch, cherry, pine, and fir, shall receive a wash coat or wood conditioner before staining where the accepted sample was prepared with one.
8.3.4 Open-grained species shall receive a paste wood filler before the clear coats where the accepted sample shows a filled-pore finish.
8.3.5 The clear finish material shall be as indicated in the datasheet.
Clear Finish on Interior Woodselect
Waterborne acrylic-polyurethane
Oil-modified polyurethane
Pre-catalyzed lacquer
Penetrating oil finish
NOTE A waterborne acrylic-polyurethane dries clear and stays clear, has little odor, recoats within hours, and meets every volatile organic compound basis; it adds no warmth to the wood, raises the grain on the first coat, and builds a thinner film per coat. An oil-modified polyurethane ambers the wood, builds quickly, and resists water and abrasion on handrails, stools, and counters; it carries solvent odor, recoats overnight, and continues to darken, and it is restricted under the strict bases. A pre-catalyzed lacquer is sprayed, dries in minutes, and gives the smoothest furniture-like film on trim and paneling finished before the space is occupied; it is flammable in application, requires spray ventilation and masking of the room, and resists water and alcohol less than polyurethane. A penetrating oil finish leaves the wood with no surface film, is renewed by wiping on another coat, and marks with water and wear sooner than a film finish. (8.3.6)
8.3.7 The sheen of the final clear coat shall be as indicated in the datasheet.
Sheen of Clear Finishselect
Flat
Satin
Semi-gloss
Gloss
NOTE A flat or satin clear coat hides sanding scratches, brush marks, and the wear of handling; semi-gloss and gloss show the depth of the grain and every flaw in the preparation and the film. Flatting agents settle in the can, and a clear finish that is not stirred through the day dries glossier at the top of the can than at the bottom. (8.3.8)
8.3.9 The clear finish shall be applied in not fewer than the number of coats indicated in the datasheet, counted over the stain and exclusive of any wash coat or filler.
Number of Clear Finish Coatsrange
Not less than
coats
14
Default: 2 coats
8.3.10 Each clear coat except the last shall be sanded with an abrasive not coarser than 220 grit and cleaned of dust before the next coat.
8.3.11 Wood doors delivered unfinished or factory sealed shall be finished on all six surfaces, including the top and bottom edges and every hardware cutout, before or within the interval after hanging that the door manufacturer publishes.
8.3.12 Field-applied topcoats over the factory sealer of casework, paneling, or doors shall be of a type the manufacturer of the sealed item identifies as compatible with its sealer, and the sealed surface shall be scuff sanded before the first field coat.
NOTE A stain is approved on the actual species because the same stain on oak, maple, and cherry gives three colors, and on the actual cut because rift, quarter, and plain-sliced faces take it differently. Two clear coats over a stain is the ordinary film on trim; a third is the practice on handrails, stools, and surfaces that are handled or wetted, and a penetrating oil is counted in applications rather than film coats. A door whose top and bottom edges are left raw takes up moisture through them and warps, and door manufacturers condition their warranties on the six-sided seal. (8.3.13)
9 Fire-Retardant Coatings
9.1 Requirements in this section apply only to the surfaces the room finish schedule or the life safety plans identify as receiving a fire-retardant coating to reach an interior finish classification.
9.2 The flame spread classification the coated surface achieves shall be as indicated in the datasheet.
Interior Finish Classification of Fire-Retardant Coated Surfacesselect
Class A
Class B
Class C
Derived — the interior wall and ceiling finish classification Adopted Building CodeAdopted Building CodeParameterEach project supplies its own value.adopted-building-code requires for the occupancy, the location in the means of egress, and the sprinkler protection of the space (by default)
9.3 The fire-retardant coating shall have been tested by ASTM E84 over the same substrate species, thickness, and construction it is applied to on the Project, and the test report shall state the spreading rate and number of coats at which the classification was achieved.
9.4 The coating shall be applied at not less than the spreading rate and number of coats of the test, the Contractor shall record the area coated and the quantity of material used on each surface, and no topcoat shall be applied over it other than one the test report includes.
NOTE Ordinary paint at ordinary film thickness over gypsum board, plaster, concrete, or masonry does not change the classification of those surfaces, and the model building code exempts thin films applied directly to a wall or ceiling from testing. A fire-retardant coating is a different product: an intumescent paint or varnish that lowers the measured flame spread of a combustible substrate, usually existing wood paneling, a wood ceiling, or exposed plywood, to a class the code requires where replacing the material is not wanted. Its classification belongs to the tested combination of substrate, spreading rate, and topcoat, and a decorative coat laid over it later can void the result. Coatings that give a structural member an hourly fire-resistance rating are a different product again and are governed by FireproofingApplied FireproofingResolves to the current adopted revision.sync/fireproofing. (9.5)
10 Sheen and Number of Coats
10.1 Sheen of Walls
10.1.1 The sheen of finish coats on walls in general spaces shall be as indicated in the datasheet, expressed as the MPI gloss level.
Sheen of Walls in General Spacesselect
G1, flat
G2, velvet
G3, eggshell
G4, satin
G5, semi-gloss
10.1.2 The sheen of finish coats on walls in scrubbed and wet-service spaces shall be as indicated in the datasheet, expressed as the MPI gloss level.
Sheen of Walls in Scrubbed and Wet-Service Spacesselect
G3, eggshell
G4, satin
G5, semi-gloss
G6, gloss
NOTE A flat or velvet finish hides joint treatment, patches, and roller laps, touches up invisibly, and burnishes to a shiny spot where it is rubbed or washed. Eggshell and satin wipe clean and hold up to occasional washing, and they show a joint or a touch-up under raking light. Semi-gloss and gloss take scrubbing and shed water, and they show every ridge in the board finish, which is why the gypsum board standard raises the finish level beneath them. The sheen and the level of board finish are chosen together, and a change in one after joint treatment has started reopens the other. (10.1.3)
10.1.4 Where the sheen selected for a gypsum board surface is G5 or higher, the Contractor shall confirm before priming that the surface was finished to the level the Section governing gypsum board requires for that sheen, and shall report a surface finished to a lower level to the Architect instead of painting it.
10.2 Sheen of Ceilings
10.2.1 The sheen of finish coats on ceilings and soffits in general spaces shall be as indicated in the datasheet, expressed as the MPI gloss level.
Sheen of Ceilingsselect
G1, flat
G2, velvet
G3, eggshell
NOTE A ceiling is lit at a grazing angle by every window and every pendant, and a flat finish is what hides its joints and laps. Velvet and eggshell are selected where a ceiling is wiped, over a serving line or in a corridor with supply diffusers that streak, and in the scrubbed and wet-service spaces the ceiling takes the sheen selected for those walls. (10.2.2)
10.3 Sheen of Trim, Doors, and Metal
10.3.1 The sheen of opaque finish coats on trim, doors, frames, railings, and other metal shall be as indicated in the datasheet, expressed as the MPI gloss level.
Sheen of Trim, Doors, and Metalselect
G3, eggshell
G4, satin
G5, semi-gloss
G6, gloss
G7, high gloss
10.3.2 Gloss shall be measured by ASTM D523 at 60 degrees, and sheen at 85 degrees, against the ranges the MPI gloss levels define.
NOTE Semi-gloss on doors, frames, and trim resists hand soil and washes, and it separates the trim from the wall by sheen where both are one color. Eggshell and satin are selected where the frame is meant to recede into the wall and hide dents and weld grinding. Gloss and high gloss are a design finish on doors and millwork; they demand filled and sanded substrates and a spray or tipped-off application, and they show every defect beneath them. (10.3.3)
10.4 Number of Finish Coats
10.4.1 Each paint system shall consist of its primer plus the number of finish coats indicated in the datasheet.
Number of Finish Coats Over the Primerrange
Not less than
coats
13
Default: 2 coats
10.4.2 Each coat shall be applied at not less than the dry film thickness and not more than the spreading rate the manufacturer publishes for the product.
10.4.3 Where the number of coats indicated does not produce complete hide and uniform color and sheen, the Contractor shall apply additional coats at no change in the Contract Sum until it does.
10.4.4 A primer tinted toward the finish color shall be used under deep, saturated, and accent colors where the finish manufacturer publishes one for the color.
NOTE Two finish coats over a primer build the film the manufacturer's scrub and hide data assume. A single finish coat serves dry-fall work, ceilings in utility spaces, and repainting in the same color over a sound film. A third coat is reached for with deep reds, yellows, and oranges whose pigments hide poorly, and the tinted primer exists to make the third coat unnecessary. Products sold as a paint and primer in one are finish coats with higher build; over new gypsum board they are counted as finish coats, and whether one of them stands in for the primer is settled by the paint system schedule and the manufacturer's data sheet. (10.4.5)
11 Color
11.1 Colors of every painted and finished surface shall be as indicated on the room finish schedule, and the Contractor shall not select or substitute a color.
11.2 Each color shall match the accepted drawdown under the Action Submittals article, and a custom or deep-tone color shall additionally be confirmed on the mock-up, where one is required, before bulk material is tinted.
11.3 Where the Architect and the Contractor disagree whether a cured film matches the accepted drawdown, the color difference measured by ASTM D2244 with a spectrophotometer shall not exceed the value indicated in the datasheet, and where no value is indicated the Architect's determination shall govern.
Color Difference From the Accepted Drawdownrange
Not more than
ΔE
0.54
11.4 Bulk-tinted material of one color from different batches shall be boxed into one container and mixed before application on any continuous surface.
11.5 Unless the room finish schedule assigns another color, access doors, grilles, registers, exposed conduit, and device boxes set in a painted wall or ceiling shall be painted the color and sheen of the surface they are set in, and the edges of a door shall take the color of the face that is visible when the door stands open into the room.
11.6 Safety and identification colors on guard posts, stair nosings, and similar items shall be as the room finish schedule or the Drawings assign them, in the finish system this standard selects for the substrate.
NOTE A tolerance near 0.5 to 1 ΔE is at the limit of what a tinting machine repeats and is bought for a brand color or a color that runs unbroken down a long corridor; about 2 ΔE is the difference a trained eye sees side by side; above 3 ΔE a touch-up shows from across the room. Interior color is judged under the lamp of the space, and a match made in daylight can separate under a warm or a narrow-spectrum source, which is why the drawdown is reviewed under the lighting the room will have. (11.7)
12 Volatile Organic Compounds and Emissions
12.1 Volatile Organic Compound Content
12.1.1 Every coating shall comply with the volatile organic compound limits in force at the project location, and the regulatory basis against which the submittals demonstrate compliance shall be as indicated in the datasheet.
Volatile Organic Compound Limit Basisselect
EPA national architectural coatings rule, 40 CFR Part 59 Subpart D
OTC model rule as adopted by the state
CARB Suggested Control Measure as adopted by the air district
SCAQMD Rule 1113
12.1.2 Where a limit stricter than the selected basis is in force at the project location, the stricter limit shall govern, and the Contractor shall confirm the limits in force before material is ordered.
12.1.3 The product data shall state the volatile organic compound content of each product in grams per liter, less water and exempt compounds, as the selected basis defines it, and shall state the content added by the colorant where the basis counts it.
NOTE The federal rule is the floor everywhere in the United States and permits alkyd primers, enamels, and clear wood finishes at contents the state rules do not. The Ozone Transport Commission model rule, adopted in most northeastern and mid-Atlantic states, and the California Air Resources Board measure, adopted by most California air districts and by several other states, lower the limits for flats, non-flats, primers, stains, and clear finishes to levels most solvent-borne products do not meet. SCAQMD Rule 1113 is the strictest and is the basis a project outside southern California selects when a green-building rating system or an Owner's indoor air program asks for the lowest-content product lines, which every national manufacturer stocks. The selected basis changes which options in the primer, enamel, and clear finish datasheets above remain procurable. (12.1.4)
12.2 Emissions Testing
12.2.1 Whether wall, ceiling, and trim coatings applied inside the weather barrier are tested for chemical emissions shall be as indicated in the datasheet.
Emissions Testing of Interior Coatingsradio
○ Tested to CDPH Standard Method v1.2 and compliant for the applicable exposure scenario
○ No emissions testing requirement
12.2.2 Where emissions testing is required, the documentation shall be a laboratory report or a third-party certification that names the product, the test method and version, the exposure scenario modeled, and the date of the test.
NOTE Content and emissions are different measurements. Volatile organic compound content, in grams per liter, counts what is in the can and exists to limit outdoor smog formation; an emissions test measures what a cured film releases into a room over 14 days against health-based concentration limits. A product can pass one and fail the other. The emissions requirement is selected for schools, healthcare, and housing, and wherever a green-building rating system the project pursues credits low-emitting materials; several third-party certification marks are issued on the strength of the same method. (12.2.3)
13 Surface Preparation
13.1 Cleaning and Repair Common to All Substrates
13.1.1 Surface preparation of each surface shall be completed and inspected under the Inspection Hold Points article before any primer is applied to it.
13.1.2 Every surface to be coated shall be clean, dry, sound, and free of dust, oil, grease, wax, form-release agent, curing compound, efflorescence, mildew, rust, loose or failing coating, and any other contaminant that would impair adhesion.
13.1.3 The application of a primer to a surface shall constitute the Contractor's acceptance of that surface as a substrate for the system, except for defects that could not be seen before the primer was applied; a defect the primer reveals shall be reported to the Architect before the finish coats.
13.1.4 Mildew shall be killed and removed with a solution the coating manufacturer publishes for the purpose, the surface shall be rinsed and dried, and the source of the moisture that supported it shall be reported to the Architect.
13.1.5 Water stains, smoke, marker, and other stains that would bleed through the finish shall be spot sealed with a stain-blocking primer before the wall primer is applied.
13.1.6 Coating shall not be used to conceal a substrate that is cracked, loose, damp, or out of plane, and the Contractor shall report such a substrate to the Architect rather than paint it.
NOTE Primer reveals what bare board hides: the first coat is the first time the wall has one color and one sheen, and ridges, pocks, and scuffed paper show. The acceptance rule makes the painter look before priming and gives the painter a way to hand back what only the primer could show. (13.1.7)
13.2 Gypsum Board and Plaster Preparation
13.2.1 Sanding dust shall be removed from gypsum board and plaster by vacuuming or by wiping with a damp cloth before priming.
13.2.2 After the primer has dried, the Contractor shall inspect each gypsum board surface under a light held at a grazing angle, and shall mark the pocks, ridges, and scratches the primer has revealed for correction by the Section that finished the board before the finish coats are applied.
13.2.3 Hairline cracks in plaster shall be filled with a patching compound and sanded flush, and a crack wider than 1/16 in. or one that has reopened shall be reported to the Architect before it is filled.
13.2.4 Plaster shall be dry and hard, and a plaster surface that powders under the hand shall be sealed with a penetrating sealer the primer manufacturer publishes for the condition, or reported to the Architect.
13.3 Concrete and Masonry Preparation
13.3.1 Sound concrete and concrete masonry shall be cleaned by the methods of ASTM D4258.
13.3.2 Smooth, dense, or burnished concrete, and concrete carrying a form-release agent, bond breaker, or curing compound, shall be abraded by ASTM D4259 or prepared by SSPC-SP 13 to a uniformly textured, absorbent surface.
13.3.3 The Contractor shall confirm the removal of form-release agents, bond breakers, and curing compounds by observing that water sprinkled on the surface is absorbed rather than beaded, before priming.
13.3.4 Efflorescence shall be removed by dry brushing, and a surface on which it reappears shall not be coated until the source of moisture has been reported to the Architect and corrected.
13.3.5 Fins, mortar smears, and projections shall be removed, and tie holes, bug holes larger than 1/4 in., and spalls shall be filled with a cementitious or polymer-modified patching compound and cured before priming, unless the room finish schedule accepts the as-cast surface.
13.4 Previously Painted Surfaces
13.4.1 Before a previously painted or previously finished surface is recoated, the Contractor shall assess the soundness of the existing coating and test its adhesion by ASTM D3359 at not fewer than three locations per substrate and existing coating type.
13.4.2 The disposition of the existing coating shall be as indicated in the datasheet.
Disposition of Existing Coatingradio
○ Spot preparation of failed areas and overcoat of the sound film
○ Complete removal of the existing coating to the substrate
13.4.3 Loose, peeling, blistered, and cracked coating shall be removed to a sound edge, and the edge shall be feathered by sanding or skim patching so that the repair does not telegraph through the finish.
13.4.4 Sound existing film shall be washed free of soil, grease, and hand oils, and glossy film shall be dulled by sanding or by a deglossing method the manufacturer publishes, before priming.
13.4.5 Where a waterborne finish is to be applied over an existing alkyd or other solvent-borne enamel, the Contractor shall apply a bonding primer the finish manufacturer publishes for the purpose over the dulled film.
13.4.6 Where the existing coating fails the adhesion test at any location, the Contractor shall report the result to the Architect before proceeding, and the Architect shall determine the extent of the surface to be removed.
13.4.7 Existing wall covering shall not be painted over unless the Contract Documents direct it, and where it is removed the adhesive residue shall be washed off and the surface sealed with a primer the manufacturer publishes for the purpose.
13.4.8 In a building constructed before 1978, the existing coating shall be tested for lead before any sanding, scraping, or heat disturbs it, and a coating found to contain lead shall be handled under the hazardous material abatement requirements of the Contract Documents, stated for this Project in Hazardous Material AbatementHazardous Material AbatementResolves to the current adopted revision.sync/hazardous-material-abatement, under 40 CFR Part 745 where the building is target housing or a child-occupied facility, and under 29 CFR 1926.62.
NOTE Overcoating a sound film is what nearly all interior repainting does. Complete removal is selected where the film has built up through many repaintings until it cracks and loses the profile of the trim, where adhesion fails across the surface, or where a stain or clear finish is to replace paint on wood. Latex laid directly over an old gloss alkyd without a bonding primer is the most common interior repaint failure: the new film peels in sheets at the first scrape. (13.4.9)
14 Coating Application
14.1 Application Methods
14.1.1 The application method on walls and ceilings shall be as indicated in the datasheet.
Application Method on Walls and Ceilingsselect
Brush and roller only
Spray permitted, with back-rolling of every coat on walls
Spray permitted without back-rolling
NOTE Roller application leaves the stipple that later touch-up, done by roller, will match, and it needs no masking beyond a drop cloth; it is slower on large areas. Spray with back-rolling lays material down fast, works the first coat into the board and compound, and leaves the roller stipple. Spray without back-rolling is the fastest and leaves a smoother film that a later roller touch-up will not match, and it is the method for dry-fall work, textured ceilings, and unoccupied shell space; it calls for the masking of everything in the room and is rarely acceptable in an occupied building. (14.1.2)
14.1.3 The application method on doors, frames, and trim shall be as indicated in the datasheet.
Application Method on Doors, Frames, and Trimradio
○ Spray permitted
○ Brush and roller only
NOTE Spray gives a door or a frame a film with no brush or roller texture and is the usual method before flooring and hardware are in. Brush and roller are what remains possible once the space is finished or occupied, and with a leveling enamel they give a film whose slight brush texture a later touch-up reproduces. (14.1.4)
14.1.5 The production work shall be applied by the method used on the accepted mock-up.
14.1.6 The first coat on a porous substrate shall be worked into the surface so that it wets the texture rather than bridging it.
14.2 Recoat Times and Film Continuity
14.2.1 Each coat shall dry for not less than the manufacturer's published minimum recoat time at the conditions in the space before the next coat is applied, and where the manufacturer publishes a maximum recoat time the next coat shall be applied within it or the surface shall be abraded as the manufacturer publishes.
14.2.2 Two-component materials shall be mixed in the published ratio, allowed the published induction time, and applied within the published pot life, and material that has exceeded its pot life shall be discarded.
14.2.3 Coatings shall be thinned only with the thinner and to the limit the manufacturer publishes for the application method.
14.2.4 Primer and enamel coats on doors, frames, and trim shall be sanded smooth and cleaned of dust between coats.
14.2.5 The completed film shall be continuous and uniform in color, sheen, and texture, free of runs, sags, holidays, lap marks, flashing, roller tracking, and embedded debris when viewed under the permanent lighting of the space from a distance of 5 ft, at any angle, without supplemental light.
14.2.6 The Contractor shall maintain a wet edge and shall complete each wall or ceiling plane to a corner or other natural break in one continuous operation.
14.2.7 Edges cut in by brush against ceilings, trim, and adjacent materials shall be straight and shall not vary in color or sheen from the rolled field.
14.3 Sequence With Other Work
14.3.1 Walls and ceilings shall receive their primer and first finish coat before finish flooring, wall base, casework, and wall-mounted devices and equipment are installed, and their final coat after that work is in place, unless the Contractor's accepted schedule shows a different sequence.
14.3.2 Painting of surfaces that abut a wall covering, and painting of walls that receive wall and corner protection, shall be complete and cured before the wall covering or the protection is installed.
14.3.3 The field finish on trim and woodwork shall be sequenced with the Section that installs it so that back-priming precedes installation, the primer precedes the filling of fastener holes, and the finish coats follow the setting and filling of the trim.
14.3.4 The Contractor shall coordinate with the Section governing gypsum board, before joint treatment begins, the sheen and the lighting condition of each surface against the level of finish scheduled for it.
14.3.5 Hardware, cover plates, escutcheons, grilles, and similar removable items on a surface to be coated shall be treated as indicated in the datasheet.
Treatment of Hardware and Removable Itemsradio
● Removed before painting and reinstalled after the finish has cured
○ Masked in place
14.3.6 Removed items shall be stored with their fasteners, identified by location, and reinstalled where they came from, and door hardware that carries a fire or accessibility function shall be reinstalled and checked for latching and closing by the Section that furnished it.
14.3.7 Door closers, gasketing, hinges on fire-rated doors, and other items the furnishing Section identifies as not to be removed shall be masked in place regardless of the datasheet selection.
NOTE Paint cut around a cover plate leaves an unpainted or ridged outline the first time the plate is changed, and paint bridging a hinge or a strike cracks when the door moves. Masking in place is accepted in repainting of occupied space, where removing and re-keying hardware disrupts more than it saves. (14.3.8)
14.4 Touch-Up and Final Cleaning
14.4.1 After the work of other trades is complete, the Contractor shall touch up abrasions, scratches, and damage to the coated surfaces with the same product, color, and batch used on the surface, applied by the same method.
14.4.2 Where a touch-up is visible under the permanent lighting from 5 ft, the Contractor shall recoat the surface to the nearest corner or natural break.
14.4.3 Touch-up of damage caused by other trades after a surface has been accepted shall be performed by the Contractor, and its cost shall be assigned as the Contract Documents provide for damage to completed work.
14.4.4 The Contractor shall remove spatter, drips, and overspray from every surface not scheduled for coating by a method that does not scratch or dull it, and shall remove its materials, containers, and debris from the site at completion.
14.4.5 The Contractor shall protect floors, glazing, ceilings, casework, equipment, and other finished work in and adjacent to each space while coatings are applied there, and shall repair or replace work it damages at its own cost.
NOTE Flat finishes touch up almost invisibly; eggshell and higher sheens flash, showing the touched-up patch as a brighter or duller shape under raking light, and deep colors show a patch even in flat. That is why the remedy for a visible touch-up is the whole plane, and why the sheen decision is also a maintenance decision. (14.4.6)
15 Testing
15.1 Film Thickness Verification
15.1.1 The coating thickness verification program shall be as indicated in the datasheet.
Coating Thickness Verificationselect
Visual acceptance of hide and uniformity, no thickness measurement
Wet film gauge readings during application on every substrate
Wet film gauge readings plus dry film measurement to SSPC-PA 2 on metal
15.1.2 Where wet film readings are required, the Contractor shall take not fewer than one reading per 500 ft² of each coat on each substrate, shall correlate the readings to the dry film thickness through the product's volume solids, and shall record them.
15.1.3 Dry film thickness on metal, where required, shall be measured with a gauge conforming to ASTM D7091.
15.1.4 Where a measured area is below the dry film thickness the manufacturer publishes for the coat, the Contractor shall apply additional material to that area until it conforms, at no change in the Contract Sum.
15.2 Adhesion Testing
15.2.1 The adhesion testing requirement shall be as indicated in the datasheet.
Adhesion Testing of the Applied Systemselect
Before overcoating every previously painted surface
Only where the existing coating type is unknown or a shop or factory primer's compatibility is unconfirmed
No adhesion testing required
15.2.2 Adhesion of a proposed system shall be tested by ASTM D3359 on a test patch applied over the prepared surface and cured not less than seven days, and a patch that fails shall be reported to the Architect before the system is applied to the rest of the surface.
15.2.3 Adhesion tests shall be performed by the Contractor, and where a test fails, the retest after correction shall be at the Contractor's cost.
NOTE A tape test on a cured patch is the only field method that predicts whether a new film will stay on an old one or on another trade's primer. Testing every previously painted surface suits a renovation with many undocumented films; limiting it to unknown coatings and unconfirmed primers covers the two cases where compatibility is uncertain; waiving it suits new construction where every substrate is bare or carries an identified primer confirmed compatible in writing. (15.2.4)
15.3 Inspection Hold Points
15.3.1 The Contractor shall notify the Architect not less than 48 hours before each of the following stages in each area of the work, and shall not proceed past the stage until the Architect has inspected it or the notice period has expired without a response: completed surface preparation, completed primer, and completed finish.
15.3.2 Work that does not match the accepted mock-up or drawdown, or that shows the defects the Recoat Times and Film Continuity article excludes, shall be corrected by the Contractor by recoating the affected plane to a natural break, at no change in the Contract Sum.
NOTE Preparation and primer defects are invisible once the finish is on, and the hold points are the only moments at which they can be seen without destroying the finish to look. (15.3.3)
16 Delivery, Storage, and Handling
16.1 Coatings shall be delivered to the site in the manufacturer's original sealed containers, labeled with the product name, the MPI number where one applies, the color, the batch number, and the date of manufacture.
16.2 Materials shall be stored in a designated, ventilated space held between 45°F and 90°F, or within the narrower range the manufacturer publishes, protected from freezing and from open flame.
16.3 Waterborne material that has frozen shall not be used, and material that has exceeded the manufacturer's published shelf life shall be removed from the site.
16.4 Flammable and combustible coatings, thinners, and clear finishes shall be stored in the quantities and in the manner the fire code in force at the project location permits for a building under construction or in occupancy.
16.5 Rags and applicators wet with alkyd, oil-based stain, oil-modified polyurethane, or penetrating oil shall be placed at the end of each work period in a closed metal container filled with water or shall be removed from the building.
16.6 Surplus material, wash water, and spent solvent shall be disposed of as the regulations in force at the project location require, and none shall be discharged to a plumbing fixture, a floor drain, or the ground.
NOTE A waterborne coating that freezes breaks its emulsion and cannot be restored by thawing or stirring. Drying oils heat as they cure, and a wad of oily rags in a trash bag insulates that heat until it ignites, which has burned finished buildings in the week before turnover. (16.7)
17 Warranty
17.1 The Contractor shall warrant the interior painting and finishing work against peeling, blistering, flaking, cracking, loss of adhesion, and discoloration or loss of sheen not caused by cleaning outside the maintenance instructions, for not less than the period indicated in the datasheet from the date of Substantial Completion.
Contractor Warranty Period for the Painting Workrange
Not less than
yr
1235
17.2 The Contractor's warranty shall cover the field-applied system, including its adhesion to the shop primer, factory primer, or factory sealer the Contractor confirmed compatible, and shall not cover that primer's or sealer's adhesion to its own substrate, which remains under the warranty of the Section that furnished the item.
17.3 Where the manufacturer publishes a product warranty longer than the Contractor's period, the Contractor shall comply with the manufacturer's application and documentation conditions so that the Owner receives it, and the manufacturer's warranty shall apply in addition to the Contractor's.
17.4 A warranty repair shall restore the surface to match the adjacent work in color and sheen to the nearest corner or natural break, and shall carry a fresh warranty of the original period from the date of the repair or the unexpired remainder of the original period, whichever ends later.
17.5 The Contractor shall bear the cost of removing, protecting, and reinstalling adjacent work disturbed by a warranty repair, and of repairing collateral damage the repair causes.
NOTE One year matches the general correction period of most contracts and covers a full heating and cooling season, which is when damp substrates, incompatible primers, and joint movement show in an interior film. Longer periods are selected where an epoxy or a field-finished wood system is a large investment. Damage by impact, by water from a leak, by substrate cracking, and by cleaning agents the maintenance instructions exclude is outside the warranty. (17.6)
18 Extra Stock
18.1 The Contractor shall deliver to the Owner before final acceptance the quantity of each finish product, in each color and sheen used on the project, indicated in the datasheet, in sealed, labeled, original containers from the batches applied.
Extra Stock of Each Finish Product, Color, and Sheenrange
gal
05
Default: 1 gal
18.2 Each container shall be labeled with the product, the MPI number where one applies, the color name and tint formula, the sheen, the date, and the rooms or finish designations in which it was used.
18.3 The Contractor shall obtain the Owner's signed receipt for the extra stock and shall include it in the closeout submittals.
NOTE A gallon of each color carries most buildings through the move-in damage and the first year of touch-up, and material from the applied batch is the closest match the Owner will have. Latex in a partly filled can skins and spoils within a few years, so the tint formula on the label and in the record paint schedule outlasts the stock itself. Zero is selected where an Owner's facilities group buys to its own standard and does not want stock to store. (18.4)
This standard is written and maintained by SynC and licensed under Creative Commons Attribution 4.0. You may share and adapt it, including commercially, provided you credit SynC Standards, link to the license, and indicate any changes. Each standard is drafted from cited sources under published authoring rules, reviewed before adoption, and corrected in the open. Keep the attribution and notice below with any copy; it carries the warranty notice the license asks you to retain.
"Interior Painting," SynC Standards, revision 9. Licensed under CC BY 4.0 (https://creativecommons.org/licenses/by/4.0/). Source: https://synergyinconstruction.com/standards/general/interior-painting. Reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.