Lighting Controls
Corpus sync: neutrality remakes, note hygiene, datasheet relocation, transformer-split cross-refs
Showing changes from Rev 3
to Rev 4
in Lighting Controls.
---
title: Lighting Controls
…18 unchanged lines
## A lighting installation that meets every photometric and power-density target but lacks compliant controls shall not be accepted, because it does not pass plan review.
−## The control system shall be specified as outcomes the system is to achieve rather than as a particular manufacturer's product family. {note}
+## The control system shall be specified as outcomes the system is to achieve rather than as a particular manufacturer's product family.
## Where lighting on the egress path is switched, dimmed, or otherwise controlled, the control of that lighting shall be overridden to full output on loss of normal power through equipment listed to UL 924, in accordance with NFPA 70 (National Electrical Code) Article 700.
…81 unchanged lines
- "Training records for the Owner's operating staff"
- "Initial automatic test result for self-testing emergency control devices"
−default: [Operation and maintenance data for each device and the network controller, As-built control drawings, sequences, and final zone/device schedule, Signed functional-test (acceptance-test) documentation, Final programmed settings recorded for restoration, Training records for the Owner's operating staff]
+default:
+ - "Operation and maintenance data for each device and the network controller"
+ - "As-built control drawings, sequences, and final zone/device schedule"
+ - "Signed functional-test (acceptance-test) documentation"
+ - "Final programmed settings recorded for restoration"
+ - "Training records for the Owner's operating staff"
```
…610 unchanged lines
## Spare power packs and relays are the highest-value spare because they switch load and fail more often than sensors; a spare network controller or gateway should be furnished for a networked system whose product line may change, since a controller mismatch can require reprogramming the whole system. {note}