NOTEThis Standard covers low-voltage (600 V and below) pulse-width-modulated variable frequency drives furnished as individually mounted, enclosed units for adjustable-speed control of three-phase AC induction and permanent-magnet motors. (1.1)
NOTECovered applications include process pumps, process fans, compressors, conveyors, mixers, water and wastewater treatment equipment, and general industrial, institutional, and municipal motor loads specified under the electrical division rather than embedded in a mechanical or process equipment specification. (1.2)
NOTEThe scope spans drives from fractional horsepower through at least 500 HP, in wall-mount and floor-mount configurations, NEMA 1 through NEMA 4X enclosures, indoor and outdoor installations, and both variable-torque and constant-torque duty ratings. (1.3)
1.4Each drive provided under this Standard shall be a complete adjustable-speed power drive system listed to UL 61800-5-1, including its converter, DC link, inverter, control, enclosure, and integral accessories.
1.5The work of this Standard includes input protection, harmonic mitigation, optional bypass arrangements, fieldbus and network communication, output filtering for motor cable compatibility, and field acceptance testing.
NOTEHVAC fan and pump drives specified under the mechanical division are excluded and are governed by HVAC Variable Frequency DrivesHVAC Variable Frequency DrivesResolves to the current edition.sync/hvac-variable-frequency-drives. (1.6)
NOTEVFD units furnished as plug-in bucket contents within a motor control center assembly are excluded; the MCC assembly, bus structure, and compartment construction are governed by Motor Control CentersMotor Control CentersResolves to the current edition.sync/motor-control-centers, which defers drive performance back to this Standard. (1.7)
NOTEMedium-voltage drives operating above 600 V are excluded; they fall outside the UL 61800-5-1 low-voltage listing and require a separate medium-voltage drive specification. (1.8)
NOTEDrives integral to factory-packaged process equipment — packaged pump skids, chillers, and compressor packages — are excluded and are governed by the respective equipment specification. (1.9)
NOTEConductors and cables between the drive output and the motor terminals are excluded; their sizing, insulation class, and shielding are governed by Conductors And CablesConductors and CablesResolves to the current edition.sync/conductors-and-cables. (1.10)
NOTEFeeder and branch-circuit panelboard distribution upstream of the drive is excluded and is governed by PanelboardsPanelboardsResolves to the current edition.sync/panelboards. (1.11)
2Referenced Standards
2.1Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard
Title
UL 61800-5-1
Adjustable Speed Electrical Power Drive Systems — Electrical, Thermal and Energy Safety Requirements
UL 508A
Industrial Control Panels
NFPA 70
National Electrical Code (Articles 409 and 430)
NEMA ICS 7
Adjustable-Speed Drives
NEMA 250
Enclosures for Electrical Equipment (1000 Volts Maximum)
NEMA MG 1
Motors and Generators (Part 31 — Definite-Purpose Inverter-Fed Motors)
IEEE 519
Standard for Harmonic Control in Electric Power Systems
IEC 61800-3
Adjustable Speed Electrical Power Drive Systems — EMC Requirements and Test Methods
IEC 61800-5-2
Adjustable Speed Electrical Power Drive Systems — Functional Safety Requirements
IEC 61800-9-2
Adjustable Speed Electrical Power Drive Systems — Energy Efficiency Indicators for Power Drive Systems
NETA ATS
Standard for Acceptance Testing Specifications for Electrical Power Equipment and Systems
ASHRAE 90.1
Energy Standard for Buildings Except Low-Rise Residential Buildings
ASCE 7
Minimum Design Loads and Associated Criteria for Buildings and Other Structures
NOTEUL 508C, the historical listing standard for power conversion equipment, was withdrawn and superseded by UL 61800-5-1 effective February 28, 2020. (2.3)
2.4Specifications and submittals shall reference UL 61800-5-1 and shall not cite UL 508C.
NOTEThe three IEC 61800 parts referenced above have no ANSI or UL equivalent for EMC categories, functional-safety integrity levels, or power drive system efficiency classes, and US drive manufacturers publish these designations in their North American catalog data; they are cited here for that reason. (2.5)
3Submittals
3.1Action Submittals
3.1.1The Contractor shall submit the following action submittals for review before fabrication or release of the drives:
Product data sheets for each drive, including catalog rating, listing, efficiency class, and accessory complement.
Wiring and interconnection diagrams showing power, control, and network terminations.
Drive schedule correlating each tag to motor nameplate data, duty type, enclosure type, and mitigation and bypass options.
IEEE 519 harmonic analysis demonstrating compliance at the designated point of common coupling.
Short-circuit current rating (SCCR) documentation for each enclosed drive assembly.
Seismic anchorage calculations and certification for floor-mounted enclosures where required by the seismic design category.
Action submittals required before fabricationcheckbox
☑ Product data sheets (rating, listing, efficiency)
☑ Shop drawings (enclosure, layout, nameplates)
☑ Wiring and interconnection diagrams
☑ Drive schedule (motor data, duty, enclosure)
☑ IEEE 519 harmonic analysis
☑ SCCR documentation
☐ Seismic anchorage calculations and certification
3.2Informational Submittals
3.2.1The Contractor shall submit the following informational submittals for the record:
Manufacturer certification of UL 61800-5-1 listing for each drive.
Manufacturer certification of NEMA MG 1 Part 31 output compatibility analysis, including motor cable length limits and any required output filtering.
Ambient temperature and altitude derating documentation for the installed site conditions.
Functional safety certification for drives furnished with Safe Torque Off, where specified.
Informational submittals required for the recordcheckbox
☑ UL 61800-5-1 listing certification
☑ NEMA MG 1 Part 31 output compatibility analysis
☑ Derating documentation (ambient and altitude)
☐ Functional safety (STO) certification
3.3Closeout Submittals
3.3.1The Contractor shall submit the following closeout submittals before final acceptance:
Field acceptance test reports per NETA ATS, including insulation resistance and functional verification.
As-left parameter records for each drive, listing every adjusted setting.
Operation and maintenance manuals, including troubleshooting and fault-code references.
Manufacturer warranty documentation.
Closeout submittals required before final acceptancecheckbox
☑ NETA acceptance test reports
☑ As-left parameter records
☑ Operation and maintenance manuals
☑ Warranty documentation
4Quality Assurance
4.1Each drive shall be listed by a Nationally Recognized Testing Laboratory to UL 61800-5-1.
4.2Each drive shall bear the listing mark of the Nationally Recognized Testing Laboratory that listed it.
4.3The manufacturer shall regularly produce adjustable-speed drives of the type and rating specified, with a documented production history of not less than five years.
4.4The drive shall be designed and rated in accordance with NEMA ICS 7 for adjustable-speed drives.
4.5Where the drive is furnished as an enclosed industrial control panel, the assembly shall comply with the applicable construction and marking requirements of NEC Article 409 and UL 508A.
4.6Field test personnel shall be qualified to perform acceptance testing in accordance with NETA ATS.
5Ratings and Performance
5.1Voltage and Horsepower
5.1.1The drive system voltage and horsepower or kW rating shall match the connected motor nameplate, accounting for service factor where the motor is operated continuously above nameplate.
5.1.2Each drive shall be rated for continuous operation at the connected motor full-load current at the installed ambient and altitude.
5.1.3The drive system voltage shall be as indicated in the datasheet.
System voltagerange
V
208240480600
Per drawings — one-line diagram (deferred by default)
5.1.4The drive continuous output rating shall be as indicated in the datasheet.
Drive continuous output ratingrange
HP
0.5500
Per drawings — motor and drive schedule (deferred by default)
5.1.5The maximum rated output frequency shall be as indicated in the datasheet.
Maximum rated output frequencyrange
Hz
30506090120200400
NOTE60 Hz is the North American norm for a motor operated at its nameplate base speed and is the datasheet default; 50 Hz base-speed motors and over-speed applications running above base frequency are both real selections, and a drive operated above base frequency delivers constant horsepower with falling torque. (5.1.6)
5.2Duty Type and Overload
5.2.1The drive overload rating shall match the load torque characteristic. Variable-torque loads (centrifugal pumps and fans) require only modest overload; constant-torque and high-starting-torque loads (conveyors, positive-displacement pumps, compressors, mixers) demand sustained and instantaneous overload margin.
NOTEApplying a variable-torque-rated drive to a constant-torque load causes nuisance overload trips or drive damage under high starting torque. (5.2.2)
5.2.3The duty type shall be confirmed against the actual load torque characteristic before the drive is sized.
5.2.4A drive serving a variable-torque load shall provide not less than 110% of rated output current for 60 seconds.
5.2.5A drive serving a constant-torque load shall provide not less than 150% of rated output current for 60 seconds.
5.2.6A drive serving a high-starting-torque load shall provide not less than 150% of rated output current for 60 seconds and 175% instantaneous current.
5.2.7The duty type shall be as indicated in the datasheet.
Duty typeradio
○ Variable torque (110% for 60 s)
○ Constant torque (150% for 60 s)
○ Heavy duty / high starting torque (150% for 60 s, 175% instantaneous)
NOTEThe duty type is a property of the driven machine rather than of the drive, and this Standard covers centrifugal and positive-displacement loads in comparable numbers, so the field carries no default. (5.2.8)
5.3Efficiency
5.3.1The complete power drive system (motor plus drive) shall meet the efficiency provisions applicable to the project under ASHRAE 90.1.
5.3.2The variable-speed control thresholds applied to pumps and fans under ASHRAE 90.1 shall be documented in the action submittal.
5.3.3The drive shall meet not less than the IEC 61800-9-2 power drive system efficiency class indicated in the datasheet.
Minimum power drive system efficiency class (IEC 61800-9-2)radio
○ IE1
● IE2
NOTEIE2 is the datasheet default because it is the class the current generation of general-purpose drives reaches without a cost premium; IE1 remains available for retrofit and replacement-in-kind work where an existing drive family must be matched. (5.3.4)
6Environmental and Service Conditions
6.1Enclosure Type
6.1.1The drive enclosure type shall be selected for the actual installed environment per NEMA 250.
NOTEEnclosure cost, size, and cooling capacity differ substantially between types, so over- and under-specification both carry consequences. Specifying a NEMA 1 drive where the environment exposes it to water spray, washdown, dust, or condensation causes premature failure and warranty dispute. (6.1.2)
6.1.3The enclosure rating shall reflect the worst-case service condition at the device location.
6.1.4The drive enclosure shall be as indicated in the datasheet and shall maintain its rating with all field-installed conduit entries and accessories in place.
Enclosure type (NEMA 250)radio
○ NEMA 1 (indoor, clean)
○ NEMA 12 (indoor, dust and dripping liquid)
○ NEMA 3R (outdoor, rain)
○ NEMA 4 (washdown, hose-directed water)
○ NEMA 4X (corrosive, stainless or nonmetallic)
NOTEThis Standard covers clean indoor electrical rooms, process areas subject to washdown, and outdoor installations in comparable numbers, so no enclosure type is correct for every project and the field carries no default. (6.1.5)
6.1.6The mounting configuration shall be as indicated in the datasheet.
Mounting configurationradio
○ Wall mount
○ Floor mount (freestanding)
Per drawings — electrical plan (deferred by default)
6.2Ambient and Altitude
NOTEStandard drives are rated for a maximum ambient of 40°C at altitudes up to 3300 ft; output current capacity falls at higher ambient and elevation. (6.2.1)
NOTEAbove 3300 ft a typical drive loses approximately 1% of rated current per 330 ft of additional elevation; high-altitude sites are frequently overlooked and require derating or cooling accessories. (6.2.2)
6.2.3The drive shall be rated for the maximum design ambient temperature indicated in the datasheet without exceeding its current rating.
6.2.4Where the ambient exceeds the drive's standard rating, the drive shall be upsized or provided with supplemental cooling.
Maximum design ambient temperaturerange
°C
40455055
NOTE40°C is the standard rating reference for enclosed drives and is the datasheet default; it is a rating basis rather than a measured room temperature, and it is raised only where the installed location is known to run hotter. (6.2.5)
6.2.6The drive shall be derated or otherwise compensated for the installation altitude indicated in the datasheet so that it delivers full motor full-load current at the site elevation.
Installation altituderange
ft
330066001000012000
NOTESite elevation is a project fact rather than a specification choice, and a wrong assumed elevation silently undersizes the drive, so the field carries no default. (6.2.7)
7Input Power and Protection
7.1Input Disconnect and Branch-Circuit Protection
NOTEAdjustable-speed drives are governed by NEC Article 430 Part X; the supply conductors are sized at not less than 125% of the rated drive input current, which differs from a standard motor branch circuit sized on motor full-load current. (7.1.1)
NOTEDrive input overcurrent protection sized on the drive input current rather than the motor full-load current per NEC 430.52 is a common error that leaves the drive either over-fused or under-fused. (7.1.2)
7.1.3The branch-circuit protective device ahead of the drive shall be coordinated to the sizing rule of NEC Article 430 that applies to the installation.
7.1.4Branch-circuit short-circuit and ground-fault protection ahead of the drive shall be selected and sized in accordance with NEC Article 430.
7.1.5A disconnecting means shall be provided for the drive in accordance with NEC Article 430, located within sight of the drive or provided with a lockable disconnect.
7.1.6The integral input disconnect arrangement shall be as indicated in the datasheet.
Integral input disconnectradio
○ None (external disconnect by others)
○ Non-fusible disconnect switch
○ Fusible disconnect switch
○ Molded-case circuit breaker
Per drawings — one-line diagram (deferred by default)
7.1.7The marked short-circuit current rating of the enclosed drive assembly, including integral disconnect, fusing, reactors, and bypass where furnished, shall equal or exceed the available fault current at the point of installation.
Minimum assembly short-circuit current rating (SCCR)range
kA
510141822253035425065100200
NOTEThe required rating is the first standard interrupting rating at or above the available fault current at the drive, which is an output of the project's short-circuit study, so the field carries no default. (7.1.8)
7.2Input Power Quality Accessories
NOTEInput accessories protect the drive from supply transients and reduce conducted disturbances back onto the source; the complement is selected from the supply impedance and the sensitivity of co-located equipment. (7.2.1)
7.2.2Each drive shall be provided with the input power-quality accessories indicated in the datasheet, coordinated with the harmonic mitigation method so that reactors and chokes are not duplicated.
Input power quality accessoriescheckbox
☑ AC line reactor
☐ DC link choke
☐ Input EMC / RFI filter
☐ Transient voltage surge suppressor (TVSS)
8Harmonic Mitigation
NOTEThe drive rectifier draws nonsinusoidal current that injects harmonic distortion onto the supply; without a study and a specified mitigation method, the contractor quotes the cheapest (no mitigation) option, risking utility non-compliance and interference with neighboring loads. (8.1)
8.2The harmonic mitigation method shall be specified by the Engineer of Record and shall not be left to the Contractor to determine in the field.
8.3An IEEE 519 harmonic analysis shall be performed for the installation and shall demonstrate that current and voltage distortion at the designated point of common coupling are within the limits of the standard.
8.4The harmonic mitigation method selected shall achieve the IEEE 519 distortion limits at the point of common coupling under the project's worst-case operating condition.
8.5The point of common coupling for the analysis shall be as indicated on the one-line diagram.
8.6The harmonic mitigation method shall be as indicated in the datasheet.
Harmonic mitigation methodradio
○ None
○ 3% AC line reactor
○ 5% AC line reactor
○ DC link choke
○ Passive harmonic filter
○ Active harmonic filter
○ 12-pulse drive topology
○ 18-pulse drive topology
○ Active front end (regenerative)
NOTEThe mitigation method is an output of the project's IEEE 519 study, and a small drive on a stiff service may legitimately need none while a drive farm on a generator-backed bus may need an active front end, so the field carries no default. (8.7)
8.8Current distortion at the point of common coupling shall not exceed the total demand distortion limit given by IEEE 519 for the short-circuit ratio at that point, and shall not exceed the limit indicated in the datasheet where a more stringent limit is required.
Maximum total demand distortion (current) at PCCrange
%
58121520
8.9Voltage distortion at the point of common coupling shall not exceed the total harmonic distortion limit given by IEEE 519 for the voltage level at that point, and shall not exceed the limit indicated in the datasheet where a more stringent limit is required.
Maximum total harmonic voltage distortion at PCCrange
%
1.52.5358
NOTEBoth distortion limits are read from the IEEE 519 tables for the actual short-circuit ratio and system voltage at the point of common coupling, so neither field carries a default; the datasheet entry records the value the study establishes or a stricter owner limit. (8.10)
9Output and Motor Compatibility
9.1Motor Cable Length and Output Filtering
NOTEA PWM drive produces fast-rising voltage pulses; on long motor cables these pulses reflect at the motor terminals and can double, producing peak voltages that stress the motor insulation. (9.1.1)
NOTENEMA MG 1 Part 31 inverter-duty motors withstand up to 1600 V peak, but non-inverter-duty motors may not, and the threshold cable length depends on the drive switching frequency. (9.1.2)
NOTEFailing to specify a motor cable length limit or output filter is a frequent omission; the resulting reflected-wave overvoltage can exceed the motor insulation rating and cause early winding failure. (9.1.3)
9.1.4The maximum motor cable length and the corresponding output filter shall be established from a NEMA MG 1 Part 31 compatibility analysis for each drive and motor pair.
9.1.5Where the connected motor is not rated for inverter duty, output filtering shall be provided to limit the terminal peak voltage and rate of voltage rise to within the motor insulation withstand.
9.1.6The output filter shall be as indicated in the datasheet.
Output filterradio
○ None (bare cable, short run)
○ dV/dt filter
○ Output line reactor
○ Sine-wave filter
NOTEThe filter follows from the compatibility analysis — cable length, carrier frequency, and whether the motor is inverter-duty rated — so no filter selection is correct for every project and the field carries no default. (9.1.7)
9.1.8The maximum unfiltered motor cable length shall be as indicated in the datasheet.
Maximum motor cable length (unfiltered)range
ft
25501002004006001000
NOTEThe cable length limit is a property of the installed run and of the drive and motor pair, so the field carries no default and is filled from the compatibility analysis. (9.1.9)
9.1.10The drive carrier frequency shall be as indicated in the datasheet.
Drive carrier (switching) frequencyrange
kHz
12481216
9.1.11The manufacturer's standard carrier frequency for the drive rating is acceptable; a higher carrier reduces audible motor noise but shortens the permissible cable length and derates the drive, and a lower carrier does the reverse. The as-left carrier frequency shall be recorded in the parameter record submitted at closeout.
9.2Motor Protection
9.2.1The drive shall provide electronic motor overload protection in accordance with NEC Article 430 for the connected motor.
9.2.2The drive shall provide motor thermal protection and shall accept a motor thermistor or thermal switch input where the motor is so equipped.
10Bypass
NOTEA bypass connects the motor directly across the line when the drive is unavailable, preserving operation of life-safety and process-critical loads; it is selected from the criticality of the load. (10.1)
NOTEIn bypass mode the motor runs across the line at full speed, so the drive's electronic overload is out of the circuit — an omission that commonly surfaces at startup. (10.2)
10.3The bypass arrangement shall be as indicated in the datasheet.
○ Automatic bypass (output contactor and transfer logic)
NOTEMost process drives are not bypassed, because bypass operation runs the load at full speed and defeats the reason the drive was installed; bypass is reserved for loads whose continued operation matters more than speed control, so the field defaults to none. (10.4)
10.5Where bypass is provided, a motor running overload relay shall be furnished in the bypass path to protect the motor when it is operated across the line.
10.6Where automatic bypass is provided, an output contactor and transfer logic shall be furnished to transfer the motor between drive and line operation.
11Control and Communication
11.1Control Interface
11.1.1The drive shall provide a control terminal strip for speed reference, start and stop, and fault signaling.
11.1.2The drive shall provide an operator keypad with local and remote control selection and fault display.
11.1.3The drive shall accept the analog speed reference signal indicated in the datasheet.
Analog speed reference inputradio
○ 0-10 VDC
● 4-20 mA
○ 0-20 mA
○ ±10 VDC (bidirectional)
○ None — speed commanded over the network
NOTEA 4-20 mA current loop is the default because it is immune to the voltage drop and induced noise that corrupt a voltage reference over the cable lengths typical of process installations. (11.1.4)
11.1.5The drive shall be furnished with not less than the discrete input and relay output complement indicated in the datasheet.
Discrete (digital) input countrange
inputs
212
Form C relay (digital) output countrange
outputs
16
NOTEThe manufacturer's standard onboard input and output complement is acceptable for a drive under simple start/stop and speed-reference control; an explicit count is entered only where the sequence of operations needs more points than the base drive provides. (11.1.6)
11.2Network Communication
11.2.1The fieldbus protocol shall match the building automation system or SCADA system; specifying a protocol the control system does not speak forces field rewiring or protocol converters after installation.
11.2.2The network protocol shall be coordinated with the building automation or process control contractor before the drives are released for fabrication.
11.2.3The drive shall be furnished with the network communication interface indicated in the datasheet, with all addressing and configuration coordinated with the controlling system.
Network communication protocolradio
○ None
○ Modbus RTU
○ Modbus TCP
○ BACnet MS/TP
○ BACnet/IP
○ PROFIBUS
○ PROFINET
○ EtherNet/IP
○ DeviceNet
○ EtherCAT
NOTEThe protocol is fixed by the controlling system rather than by the drive — BACnet dominates building automation, EtherNet/IP and PROFINET dominate industrial control, and Modbus persists across both — so the field carries no default. (11.2.4)
11.3Functional Safety
NOTEMachinery applications increasingly require a SIL-rated Safe Torque Off function under machinery safety standards and lockout/tagout practice, and retrofitting STO after equipment selection is costly. (11.3.1)
11.3.2The Safe Torque Off requirement shall be established at specification rather than deferred to the drive submittal.
11.3.3Where Safe Torque Off is specified, the drive shall provide a Safe Torque Off function listed to IEC 61800-5-2 at the safety integrity level indicated in the datasheet.
Safe Torque Off (STO) per IEC 61800-5-2radio
○ Not required
○ STO, SIL 2 / PLd
○ STO, SIL 3 / PLe
NOTEThe required integrity level comes from the machinery risk assessment for the driven equipment, and STO is now standard rather than optional on much of the drive market, so the field carries no default. (11.3.4)
11.4Electromagnetic Compatibility
11.4.1The drive installation shall meet the EMC immunity and emission requirements of IEC 61800-3 for the category appropriate to the installation environment.
11.4.2The drive shall meet not less than the IEC 61800-3 emission category indicated in the datasheet.
Minimum IEC 61800-3 EMC categoryradio
○ C1 (first environment, residential)
● C2 (first environment, restricted)
○ C3 (second environment, industrial)
○ C4 (second environment, high power or IT network)
NOTEC2 is the datasheet default because it is the practical minimum wherever the drive shares a service with commercial or institutional loads; C3 and C4 apply to dedicated industrial supplies where no sensitive equipment shares the source, and C1 to the rare drive on a residential service. (11.4.3)
12Source Quality Control
12.1Each drive shall be factory tested before shipment, including a functional power-on test of the control, protection, and communication features.
12.2Drives furnished as factory-assembled combination packages — input reactor, output filter, and bypass in one enclosure — shall be assembled and wired at the factory and shipped as a tested unit.
13Installation
13.1The drive shall be installed in accordance with the manufacturer's published instructions and NEC Articles 409 and 430.
13.2The drive shall be mounted to maintain the manufacturer's required clearances for cooling airflow and service access.
13.3Floor-mounted drive enclosures in applicable seismic design categories shall be anchored and braced in accordance with ASCE 7 and the project structural requirements.
13.4Drive locations shall be as indicated on the electrical plans.
13.5Conduit entry locations shall be as indicated on the approved shop drawings.
13.6Input, output, and control conductors shall be terminated to the manufacturer's torque values, and shielded motor cable shall be terminated to maintain shield continuity.
NOTEOn generator-backed projects, simultaneous starting of multiple drives can exceed the generator kVA rating; this is a frequent commissioning-discovered issue. (13.7)
13.8The drive starting sequence on standby generator power shall be coordinated with the transfer and generator system so that connected drives start within the generator's capability.
14Testing
14.1Field acceptance testing shall be performed in accordance with NETA ATS for adjustable-speed drives.
14.2Insulation resistance of the motor and motor circuit shall be measured and recorded before energizing the drive.
14.3Each drive shall be functionally verified for speed reference response, start and stop, fault and bypass operation, and network communication.
14.4Where an IEEE 519 compliance threshold is specified, harmonic current and voltage distortion shall be measured at the point of common coupling and recorded.
14.5All adjusted parameters shall be recorded as as-left settings and submitted with the test report.
14.6The field acceptance tests to be performed shall be as indicated in the datasheet.
15.1Each drive enclosure shall be provided with an engraved nameplate carrying the content indicated in the datasheet.
Nameplate engraving contentcheckbox
☑ Drive tag / designation
☑ Served equipment designation
☑ Voltage and horsepower
☐ Source feeder designation
15.2Each drive shall bear a permanent warning label identifying the stored-energy hazard and the discharge time before the enclosure may be opened.
16Delivery, Storage, and Handling
16.1Drives shall be delivered in the manufacturer's original packaging, protected from moisture, dust, and physical damage.
16.2Drives shall be stored indoors in a clean, dry, temperature-controlled space within the manufacturer's storage temperature range until installed.
16.3Drives containing electrolytic DC-link capacitors that have been stored longer than the manufacturer's shelf limit shall be reformed in accordance with the manufacturer's instructions before energizing.
17Warranty
17.1The manufacturer shall warrant each drive against defects in materials and workmanship for not less than the period indicated in the datasheet, measured from the date of substantial completion.
Manufacturer warranty periodrange
months
1218243660
18Spare Parts
18.1The Contractor shall furnish the spare parts indicated in the datasheet, packaged and labeled for the served drives:
Spare control and cooling fans of each type used.
Spare input fuses of each rating used, where the drive is fused.
One spare operator keypad where keypads are removable.
This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.
Attribution & reuse notice — keep this with any copy:
"Low-Voltage Variable Frequency Drives." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/low-voltage-variable-frequency-drives — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.