+title: Metal Roof Panels
+category: Building Envelope
+toc_depth: 3
+description: >
+ When to use: Standing seam (mechanically seamed or snap-lock), batten-seam, and exposed-fastener (through-fastened) metal roof panel systems on new and re-roof commercial, institutional, agricultural, and residential buildings; structural (over-purlin) and architectural (over solid deck) substrates; steel, aluminum, zinc, and copper panels.
+ Not intended for: Vertical and soffit metal wall cladding (see metal-wall-panels), low-slope single-ply or built-up membrane roofing (see membrane-roofing), or custom-fabricated flashing, gutters, copings, and trim as a stand-alone scope (see sheet-metal-flashing-and-trim).
+---
+
+# Scope {toc}
+
+## This standard covers the materials, performance, fabrication, and installation of preformed and field-formed metal roof panel systems, including the panels, concealed or exposed attachment, underlayment, sealants, and integral closures. The panel system types within scope are mechanically seamed standing seam, snap-lock standing seam, batten-seam, and exposed-fastener through-fastened profiles. Both structural systems spanning open framing or purlins and architectural systems over a continuous solid deck are within scope. {note}
+
+## The metal roof panel system shall be furnished as a complete assembly from a single manufacturer, including panels, clips, fasteners, sealants, closures, and matching flashing and trim components.
+
+## The panel system shall be installed weathertight and structurally complete, including all accessories required for a finished installation whether or not each item is specifically called out.
+
+## Panel-integrated flashing, eave, rake, ridge, valley, and penetration trim are within scope. This standard does not cover the following, which are coordinated with this section but specified elsewhere: {note}
+
+- Stand-alone custom sheet metal work, gutters, copings, and trim furnished as a separate scope — see [[syncs/sheet-metal-flashing-and-trim]].
+- Roof thermal insulation and air/vapor control layers — see [[syncs/building-thermal-insulation]].
+- Vertical metal wall cladding and matching wall panels — see [[syncs/metal-wall-panels]].
+
+# Referenced Standards {toc}
+
+## The following standards are referenced in this section; the edition adopted by the authority having jurisdiction governs where a conflict exists. {note}
+
+| Standard | Title |
+|----------|-------|
+| ASTM A653 | Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process |
+| ASTM A792 | Standard Specification for Steel Sheet, 55% Aluminum-Zinc Alloy-Coated by the Hot-Dip Process |
+| ASTM B209 | Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate |
+| ASTM B370 | Standard Specification for Copper Sheet and Strip for Building Construction |
+| ASTM B69 | Standard Specification for Rolled Zinc |
+| ASTM D1970 | Standard Specification for Self-Adhering Polymer Modified Bituminous Sheet Materials Used as Steep Roofing Underlayment for Ice Dam Protection |
+| ASTM E108 | Standard Test Methods for Fire Tests of Roof Coverings |
+| ASTM E1514 | Standard Specification for Structural Standing Seam Steel Roof Panel Systems |
+| ASTM E1592 | Standard Test Method for Structural Performance of Sheet Metal Roof and Siding Systems by Uniform Static Air Pressure Difference |
+| ASTM E1646 | Standard Test Method for Water Penetration of Exterior Metal Roof Panel Systems by Uniform Static Air Pressure Difference |
+| ASTM E2140 | Standard Test Method for Water Penetration of Metal Roof Panel Systems by Static Water Pressure Head |
+| UL 580 | Standard for Tests for Uplift Resistance of Roof Assemblies |
+| UL 790 | Standard Test Methods for Fire Tests of Roof Coverings |
+| UL 1897 | Uplift Test for Roof Covering Systems |
+| FM 4471 | Approval Standard for Class 1 Panel Roofs |
+| SMACNA Architectural Sheet Metal Manual, 7th Edition | Architectural Sheet Metal Manual (7th Edition) |
+| NRCA Roofing Manual | Metal Panel and SPF Roof Systems |
+| IBC Section 1507.4 / IRC Section R905.10 | Metal Roof Panels |
+| ASCE 7 | Minimum Design Loads and Associated Criteria for Buildings and Other Structures |
+
+# Submittals {toc}
+
+## Action Submittals {note}
+
+### The Contractor shall submit the following action submittals for review and approval before fabrication:
+
+- Product data for each panel profile, including base metal, gauge or thickness, coating, finish, seam type, and coverage width.
+- Shop drawings showing panel layout, dimensions, clip and fastener spacing, and the location of factory and field seams.
+- Shop drawings of all flashing, trim, closures, and panel terminations at eave, rake, ridge, hip, valley, transition, and penetration conditions.
+- Color and finish samples for each exposed metal and coating, full color range plus the selected color.
+- Panel samples, minimum 12 in long, of each profile showing the proposed seam, coating, and finish.
+- Manufacturer's signed certification of wind-uplift, water-penetration, and fire classification test compliance for the specific assembly.
+- Structural calculations for clip spacing and panel span signed by a licensed professional engineer where the panels are structural.
+
+```datasheet
+label: Action Submittals
+type: checkbox
+options:
+ - Product data for each panel profile
+ - Panel layout and seam shop drawings
+ - Flashing, trim, and termination shop drawings
+ - Color and finish samples
+ - Panel profile samples (12 in minimum)
+ - Wind, water, and fire test certification
+ - Signed structural calculations (structural panels)
+default:
+ - Product data for each panel profile
+ - Panel layout and seam shop drawings
+ - Flashing, trim, and termination shop drawings
+ - Color and finish samples
+ - Wind, water, and fire test certification
+```
+
+## Informational Submittals {note}
+
+### The Contractor shall submit the following informational submittals before installation begins:
+
+- Manufacturer's installation instructions for the specified panel and clip system.
+- Qualification data for the installer demonstrating manufacturer certification or approval.
+- Sample warranty documents for the finish, weathertightness, and system warranties.
+- Field-formed panel machine certification where panels are roll-formed on site.
+
+```datasheet
+label: Informational Submittals
+type: checkbox
+options:
+ - Manufacturer installation instructions
+ - Installer qualification data
+ - Sample warranty documents
+ - Field roll-forming machine certification
+default:
+ - Manufacturer installation instructions
+ - Installer qualification data
+ - Sample warranty documents
+```
+
+## Closeout Submittals {note}
+
+### The Contractor shall submit the following closeout submittals before final acceptance:
+
+- Executed finish warranty, weathertightness warranty, and system warranty.
+- Maintenance instructions for cleaning, inspection, and minor repair of the finish and seams.
+- Record documents showing as-installed panel layout, clip type, and flashing details.
+- Touch-up coating matching the panel finish for field repair of minor coating damage.
+
+```datasheet
+label: Closeout Submittals
+type: checkbox
+options:
+ - Executed warranties
+ - Maintenance instructions
+ - As-installed record documents
+ - Touch-up coating
+default:
+ - Executed warranties
+ - Maintenance instructions
+ - As-installed record documents
+ - Touch-up coating
+```
+
+# Quality Assurance {toc}
+
+## Qualifications {note}
+
+### The manufacturer shall have produced metal roof panel systems of the type specified for a minimum of five years.
+
+### The installer shall be certified or approved in writing by the panel manufacturer for the specified system.
+
+### Field roll-forming, where used, shall be performed by an operator trained and certified by the roll-forming machine manufacturer. {note}
+
+### Field roll-forming shall be performed by an operator trained and certified for the roll-forming machine in use.
+
+## Mockups {note}
+
+### A mockup demonstrates the seam appearance, finish color, flashing integration, and oil-canning characteristics before full production proceeds. {note}
+
+### The Contractor shall construct a field mockup of the panel system including at least one full seam, one eave, one rake, and one penetration condition.
+
+### The mockup shall be a minimum of 100 ft² in roof area unless a smaller area is approved by the Architect.
+
+### The approved mockup shall establish the acceptable standard of appearance, including the acceptable degree of oil-canning, for the work.
+
+### The mockup may remain as part of the completed work if it is undisturbed and conforms to the final requirements.
+
+## Oil-Canning {note}
+
+### Oil-canning is a visible waviness in the flat areas of light-gauge metal panels caused by internal stresses, thermal movement, and forming, and is an inherent characteristic of formed metal, not a defect. {note}
+
+### Oil-canning shall not be cause for panel rejection provided the panels conform to the approved mockup and manufacturer tolerances.
+
+### Striations, ribs, or a stiffening rib in the flat pan should be specified where a reduced appearance of oil-canning is desired. {note}
+
+# Performance Requirements {toc}
+
+## Wind Uplift {note}
+
+### Wind uplift is the dominant structural demand on a metal roof; the panel-and-clip assembly must resist the net uplift pressure at field, perimeter, and corner zones determined from the site design wind speed. {note}
+
+### The panel system shall be tested for structural performance under uniform static air pressure difference in accordance with ASTM E1592.
+
+### The tested uplift capacity, including the appropriate safety factor, shall equal or exceed the design wind-uplift pressure computed in accordance with ASCE 7 for the field, perimeter, and corner zones of the roof.
+
+### The design wind-uplift pressures and roof pressure zones for this project are as indicated. [[drawing: roof wind-pressure zone diagram]]
+
+### Where a UL classification is required by the authority having jurisdiction, the assembly shall carry a UL 580 or UL 1897 uplift classification meeting the required class.
+
+### Where the project is FM-insured or an FM-approved assembly is specified, the assembly shall be listed in the FM Approval Guide under FM 4471 at the required Class 1 uplift rating.
+
+```datasheet
+label: Wind Uplift Classification Basis
+type: select
+options:
+ - ASTM E1592 design pressure (project-calculated)
+ - UL 580 Class 30
+ - UL 580 Class 60
+ - UL 580 Class 90
+ - UL 1897
+ - FM 4471 Class 1-60
+ - FM 4471 Class 1-90
+ - FM 4471 Class 1-120
+default: ASTM E1592 design pressure (project-calculated)
+```
+
+```datasheet
+label: Minimum Design Wind-Uplift Pressure (field zone)
+type: range
+unit: psf
+min: 20
+max: 120
+step: 5
+default: 45
+drawing_ref: "roof wind-pressure zone diagram"
+```
+
+## Water Penetration {note}
+
+### Standing seam systems resist water by seam height and geometry; the required test method depends on whether the governing concern is static head (ponding, snow melt) or wind-driven rain. {note}
+
+### The panel system shall show no uncontrolled water penetration when tested under static water pressure head in accordance with ASTM E2140.
+
+### The panel system shall show no uncontrolled water penetration when tested under uniform static air pressure difference in accordance with ASTM E1646.
+
+### Mechanically seamed standing seam systems shall be used on roof slopes below 3:12 where wind-driven water and static head resistance are critical.
+
+## Fire Classification {note}
+
+### Bare metal panels are non-combustible and typically achieve a Class A material rating, but the assembly classification depends on the deck, underlayment, and any insulation below the panel. {note}
+
+### The roof assembly shall carry a fire classification in accordance with ASTM E108 or UL 790 meeting the class required by the authority having jurisdiction.
+
+### Where a UL-listed assembly is specified, the assembly shall carry a UL 790 listing for the required class; a UL 790 listing satisfies ASTM E108 but the reverse is not true. {note}
+
+```datasheet
+label: Roof Fire Classification
+type: select
+options:
+ - Class A
+ - Class B
+ - Class C
+default: Class A
+```
+
+## Thermal Movement {note}
+
+### A long metal panel run expands and contracts significantly with temperature; the clip and seam must accommodate that movement or the panel will buckle and the clip slots will tear. {note}
+
+### The panel system shall accommodate thermal movement resulting from an ambient surface temperature range of -20 °F to 180 °F without buckling, seam separation, fastener fatigue, or noise.
+
+### Floating two-piece clips with slotted travel shall be provided for steel panel runs longer than 40 ft and for aluminum panel runs longer than 20 ft.
+
+### Fixed clips may be used only where the panel run is short enough that thermal movement is accommodated within the seam and clip tolerance.
+
+```datasheet
+label: Clip Type
+type: radio
+options:
+ - Fixed clip
+ - Floating two-piece clip (slotted)
+default: Floating two-piece clip (slotted)
+```
+
+# Environmental and Service Conditions {toc}
+
+## The base metal and coating shall be selected for the corrosivity of the service environment, including coastal salt exposure, industrial pollutants, and agricultural ammonia. {note}
+
+## Aluminum or coated aluminum panels should be specified in marine and coastal environments within roughly one mile of salt water where bare and galvanized steel corrode rapidly. {note}
+
+## Aluminum panels shall be specified where the service environment is coastal, marine, or otherwise highly corrosive to steel.
+
+## Bare Galvalume panels shall not be used in environments with standing water, animal confinement, or continuous condensation, where the aluminum-zinc coating degrades. {note}
+
+## Bare Galvalume panels shall not be used in animal-confinement or continuously wet environments.
+
+## Dissimilar metals in contact shall be isolated to prevent galvanic corrosion as specified in the components section.
+
+```datasheet
+label: Service Environment
+type: select
+options:
+ - Standard (inland, low corrosivity)
+ - Industrial (pollutant exposure)
+ - Coastal/marine (salt exposure)
+ - Agricultural (ammonia/confinement)
+default: Standard (inland, low corrosivity)
+```
+
+# Panel System Type and Configuration {toc}
+
+## Seam Type {note}
+
+### The seam type governs minimum slope, water-tightness, and installation method, and is the single most consequential selection in a metal roof specification. {note}
+
+### Mechanically seamed standing seam panels shall be field-seamed with a power seaming tool to fold the panel legs into a continuous, weathertight seam.
+
+### Snap-lock standing seam panels shall engage by mechanical snap action without field seaming and shall be used only on slopes at or above the manufacturer's minimum, typically 3:12.
+
+### Batten-seam panels shall be joined by a separate batten cap engaging the upturned legs of adjacent panels.
+
+### Through-fastened exposed-fastener panels shall be attached with gasketed fasteners driven through the panel into the structure and shall be used only on slopes at or above 3:12.
+
+```datasheet
+label: Seam Type
+type: select
+options:
+ - Mechanically seamed standing seam
+ - Snap-lock standing seam
+ - Batten-seam
+ - Through-fastened (exposed fastener)
+default: Mechanically seamed standing seam
+```
+
+```datasheet
+label: Seam Height (standing seam)
+type: select
+options:
+ - 1 in
+ - 1.5 in
+ - 1.75 in
+ - 2 in
+ - 3 in
+default: 1.75 in
+unit: in
+```
+
+## Structural vs. Architectural Substrate {note}
+
+### A structural panel spans between purlins or open framing and carries its own uplift rating tied to span and purlin spacing; an architectural panel requires a continuous solid deck below it. Substituting one substrate for the other voids the tested rating and is a frequent source of field conflict. {note}
+
+### Structural panel systems shall span between purlins or framing at the spacing for which the panel is tested in accordance with ASTM E1592 and, for steel, ASTM E1514.
+
+### Architectural panel systems shall be installed only over a continuous solid deck with underlayment.
+
+### The structural deck or framing arrangement and purlin spacing are as indicated. [[drawing: roof framing plan]]
+
+```datasheet
+label: Substrate Type
+type: radio
+options:
+ - Structural (over purlins/open framing)
+ - Architectural (over solid deck)
+default: Architectural (over solid deck)
+```
+
+## Minimum Slope {note}
+
+### Each seam type has a minimum slope below which wind-driven water and static head overwhelm the seam; specifying a panel below its rated slope is a leak source. {note}
+
+### The installed roof slope shall equal or exceed the minimum slope rated by the manufacturer for the selected seam type and seam height.
+
+### The roof slope for this project is as indicated. [[drawing: roof plan slope arrows]]
+
+```datasheet
+label: Roof Slope
+type: range
+unit: ":12"
+min: 0.25
+max: 12
+step: 0.25
+default: 3
+drawing_ref: "roof plan slope arrows"
+```
+
+## Panel Coverage Width {note}
+
+### Narrower panels reduce oil-canning on wide flat pans but increase the number of seams and the installed cost. {note}
+
+### The panel coverage width shall be uniform across the roof except at edge panels trimmed to fit.
+
+```datasheet
+label: Panel Coverage Width
+type: select
+options:
+ - 12 in
+ - 16 in
+ - 18 in
+ - 24 in
+ - 36 in (through-fastened)
+default: 16 in
+unit: in
+```
+
+# Panel Materials {toc}
+
+## Base Metal {note}
+
+### The base metal sets the corrosion resistance, structural capacity, and cost of the panel; the choice is driven by environment, span, and budget. {note}
+
+### Galvalume steel sheet shall conform to ASTM A792, Grade AZ50 or AZ55 aluminum-zinc coating, where steel panels are specified.
+
+### Galvanized steel sheet shall conform to ASTM A653, G90 coating minimum, where galvanized steel is specified.
+
+### Aluminum sheet shall conform to ASTM B209, alloy 3003, 3004, or 5052, in the temper required for the panel profile.
+
+### Copper sheet shall conform to ASTM B370 in the weight specified.
+
+### Rolled zinc sheet shall conform to ASTM B69 in the thickness and finish specified.
+
+```datasheet
+label: Base Metal
+type: select
+options:
+ - Galvalume steel (ASTM A792 AZ50)
+ - Galvalume steel (ASTM A792 AZ55)
+ - Galvanized steel (ASTM A653 G90)
+ - Aluminum (ASTM B209)
+ - Copper (ASTM B370)
+ - Zinc (ASTM B69)
+default: Galvalume steel (ASTM A792 AZ55)
+```
+
+## Gauge and Thickness {note}
+
+### Heavier gauge increases structural span capability and reduces oil-canning; lighter gauge reduces cost and is appropriate for short architectural runs over solid deck. {note}
+
+### Steel panel gauge shall be selected so that the panel meets the structural and uplift requirements for the design span and pressure.
+
+### The minimum steel panel gauge for structural and high-wind applications shall be 24 ga; 22 ga shall be used where the design span or uplift requires it.
+
+```datasheet
+label: Steel Panel Gauge
+type: select
+options:
+ - 22 ga (0.030 in)
+ - 24 ga (0.024 in)
+ - 26 ga (0.018 in)
+default: 24 ga (0.024 in)
+```
+
+```datasheet
+label: Aluminum Panel Thickness
+type: select
+options:
+ - 0.032 in
+ - 0.040 in
+ - 0.050 in
+default: 0.040 in
+unit: in
+```
+
+## Finish System {note}
+
+### The exterior coating governs color retention, chalk and fade resistance, and warranty length; the PVDF 70% fluoropolymer coating is the architectural standard. {note}
+
+### The exterior finish shall be a 70% polyvinylidene fluoride (PVDF) fluoropolymer coating where a long-term fade and chalk warranty is required.
+
+### A silicone-modified polyester (SMP) finish may be used where a lower-cost finish with a shorter warranty is acceptable.
+
+### The interior (underside) surface of the panel shall receive a manufacturer's standard wash coat or backer finish.
+
+### The dry film thickness of the exterior PVDF finish shall be not less than 0.9 mil over a 0.2 mil to 0.3 mil primer.
+
+```datasheet
+label: Exterior Finish System
+type: select
+options:
+ - PVDF 70% fluoropolymer (2-coat)
+ - PVDF 70% fluoropolymer (3-coat metallic/mica)
+ - Silicone-modified polyester (SMP)
+ - Anodized aluminum (Class I)
+ - Bare/mill finish
+ - Natural patina (copper/zinc)
+default: PVDF 70% fluoropolymer (2-coat)
+```
+
+## Color and Cool-Roof Compliance {note}
+
+### Not all colors are available in a finish that meets cool-roof solar reflectance thresholds; dark colors usually do not qualify. The color and any reflectance requirement must be reconciled before the palette is locked. {note}
+
+### The panel color shall be selected from the manufacturer's standard PVDF color range unless a custom color is specified.
+
+### Where Energy Star, LEED, or a cool-roof code such as Title 24 applies, the selected color shall meet the required minimum Solar Reflectance Index (SRI).
+
+```datasheet
+label: Cool-Roof Compliance Required
+type: radio
+options:
+ - 'Yes'
+ - 'No'
+default: 'No'
+```
+
+```datasheet
+label: Minimum Solar Reflectance Index (SRI)
+type: range
+unit: SRI
+min: 0
+max: 100
+step: 1
+default: 29
+```
+
+# Components and Accessories {toc}
+
+## Clips and Attachment {note}
+
+### Clips transfer uplift from the panel to the structure and, on long runs, allow the panel to move; clip material and design must suit both the panel metal and the thermal movement demand. {note}
+
+### Clips shall be of the type and material recommended by the panel manufacturer for the specified panel, slope, and design uplift.
+
+### Stainless steel clips shall be used where aluminum panels would otherwise contact a steel structure, to prevent galvanic corrosion.
+
+### Clip spacing shall be as established by the manufacturer's tested assembly for the design uplift at field, perimeter, and corner zones.
+
+```datasheet
+label: Clip Material
+type: select
+options:
+ - Galvanized steel
+ - Aluminum
+ - Stainless steel
+default: Galvanized steel
+```
+
+## Fasteners {note}
+
+### Concealed clip fasteners and exposed panel fasteners both must resist pull-out under uplift and corrosion over the service life; exposed fasteners additionally seal the penetration. {note}
+
+### Concealed fasteners securing clips to the structure shall be corrosion-resistant and sized for the design uplift pull-out load.
+
+### Exposed fasteners on through-fastened panels shall have an integral or bonded EPDM or neoprene sealing washer.
+
+### Fasteners in contact with aluminum or Galvalume panels shall be stainless steel or shall otherwise be compatible to prevent galvanic corrosion.
+
+```datasheet
+label: Exposed Fastener Type (through-fastened)
+type: select
+options:
+ - Self-drilling screw with bonded EPDM washer
+ - Self-tapping screw with bonded EPDM washer
+ - Stainless steel screw with bonded EPDM washer
+default: Self-drilling screw with bonded EPDM washer
+```
+
+## Sealants and Butyl Tape {note}
+
+### Standing seam joints and low-slope conditions rely on a continuous sealant bead inside the seam; the sealant must be compatible with both the coating and the base metal or it can react, lose adhesion, or void the finish warranty. {note}
+
+### Seam sealant and butyl tape shall be the type approved by the panel manufacturer for the specified panel and coating.
+
+### A continuous bead of butyl sealant shall be provided in the standing seam leg of mechanically seamed and low-slope systems.
+
+### Field-applied sealant shall be a non-curing butyl or a low-modulus polyurethane compatible with the panel finish.
+
+```datasheet
+label: Seam Sealant
+type: select
+options:
+ - Factory-applied butyl in seam
+ - Field-applied butyl tape in seam
+ - Both factory and field-applied
+default: Factory-applied butyl in seam
+```
+
+## Closures and Trim {note}
+
+### Closures seal the corrugation profile at terminations against wind-driven rain, insects, and birds; trim integrates the panel field with adjacent surfaces. {note}
+
+### Inside and outside closures matching the panel profile shall be provided at eave, ridge, rake, and transition conditions.
+
+### Closures shall be of closed-cell foam, formed metal, or extruded profile compatible with the panel metal and finish.
+
+### Flashing and trim shall be of the same base metal and finish as the panels and shall be detailed to permit thermal movement.
+
+### Flashing and trim detailing should follow the SMACNA Architectural Sheet Metal Manual where a project-specific detail is not provided. {note}
+
+## Isolation of Dissimilar Metals {note}
+
+### Aluminum, copper, and zinc each corrode galvanically when in direct contact with, or in runoff from, a more noble or more active metal; an isolation layer breaks that circuit. {note}
+
+### Aluminum panels and accessories shall be isolated from dissimilar metals with EPDM tape, a non-conductive separator, or a compatible coating.
+
+### Copper and copper runoff shall not be allowed to discharge onto aluminum, zinc, or Galvalume surfaces.
+
+# Underlayment {toc}
+
+## Underlayment under a metal panel sees far higher surface temperatures than under most other roof coverings; standard felt or synthetic underlayment can off-gas and bond to the panel underside, so a high-temperature self-adhered product is required. {note}
+
+## Underlayment over a solid deck beneath metal panels shall be a self-adhered membrane rated for continuous service at the panel underside temperature and complying with ASTM D1970 where used for ice-dam protection.
+
+## The underlayment shall be rated by its manufacturer for a minimum surface temperature of 240 °F.
+
+## Standard organic felt underlayment shall not be used directly beneath metal roof panels. {note}
+
+## Standard organic felt or non-high-temperature synthetic underlayment shall not be installed directly beneath metal roof panels.
+
+## In climate zones requiring ice-dam protection, self-adhered underlayment shall extend from the eave edge to a point at least 24 in inside the interior face of the exterior wall.
+
+## The extent of full-coverage versus eave-only self-adhered underlayment is as indicated. [[drawing: underlayment extent plan]]
+
+```datasheet
+label: Underlayment Type
+type: select
+options:
+ - High-temperature self-adhered (full coverage)
+ - High-temperature self-adhered (eave/valley) plus high-temp synthetic field
+ - High-temperature synthetic (mechanically attached)
+default: High-temperature self-adhered (full coverage)
+```
+
+```datasheet
+label: Underlayment Minimum Temperature Rating
+type: range
+unit: °F
+min: 200
+max: 260
+step: 10
+default: 240
+```
+
+# Installation {toc}
+
+## General {note}
+
+### The panel system shall be installed in accordance with the manufacturer's instructions, the approved shop drawings, and the approved mockup.
+
+### Panels shall be installed straight, true, and in alignment, with seams plumb and parallel.
+
+### Installation should follow the applicable details of the NRCA Roofing Manual for metal panel roof systems where a project detail is not provided. {note}
+
+## Substrate Preparation {note}
+
+### The solid deck or framing shall be inspected for proper slope, attachment, and surface condition before underlayment and panels are installed.
+
+### Defects in the deck or framing that would impair panel installation or performance shall be corrected before work proceeds.
+
+### Underlayment shall be installed lapped to shed water and shall be continuous before panel installation begins.
+
+## Panel Installation {note}
+
+### Mechanically seamed panels shall be field-seamed with the seaming tool specified by the manufacturer to the full seam fold within the manufacturer's allowable time after panel placement.
+
+### Snap-lock panels shall be fully engaged along the entire seam length so the seam is continuously locked.
+
+### Clips shall be fastened to the structure at the spacing established by the tested assembly, with floating clips set to permit the calculated thermal travel.
+
+### Field-cutting of panels shall be performed with tools that do not damage the coating; abrasive saws that throw hot metal filings onto the finish shall not be used. {note}
+
+### Panels shall not be cut with abrasive saws or torches that deposit hot metal particles on the finish.
+
+### Cut edges and minor coating damage shall be touched up with the manufacturer's matching repair coating.
+
+## Penetrations and Terminations {note}
+
+### Penetrations through metal roof panels shall be flashed with manufacturer-approved boots, curbs, or formed flashing detailed to permit panel thermal movement.
+
+### Eave, ridge, hip, valley, and rake terminations shall be closed with matching closures and flashing detailed for weathertightness.
+
+### The location of all roof penetrations and rooftop equipment supports is as indicated. [[drawing: roof penetration plan]]
+
+## Protection {note}
+
+### Installed panels shall be protected from foot traffic, dropped tools, and trade damage until the work is accepted.
+
+### Strippable protective film, where provided on the finish, shall be removed within the time limit set by the finish manufacturer to prevent adhesive staining.
+
+# Delivery, Storage, and Handling {toc}
+
+## Panels shall be delivered in the manufacturer's packaging with labels identifying profile, gauge, finish, and color intact.
+
+## Panels and accessories shall be stored off the ground, on a slope, and covered with a breathable cover to prevent water entrapment and white-rust staining of bare or Galvalume surfaces. {note}
+
+## Bundled panels shall be stored elevated at one end so that any entrapped moisture drains and does not pond between nested panels.
+
+## Panels stored on site shall be kept dry, as trapped moisture between nested panels causes water staining and coating damage. {note}
+
+## Panels shall be handled to prevent bending, denting, and abrasion of the finish, and shall be lifted rather than dragged across one another.
+
+## Coil and panel stock for field roll-forming shall be protected from moisture, dust, and mechanical damage before forming.
+
+# Warranty {toc}
+
+## Three distinct warranties apply to a metal roof: the finish (fade and chalk), the weathertightness of the installation, and the overall system; each has a different obligor and duration. {note}
+
+## The manufacturer shall provide a finish warranty against excessive fade, chalk, and film integrity failure for the period specified.
+
+## The Contractor shall provide a weathertightness warranty against leaks resulting from defective installation for the period specified.
+
+## A manufacturer's weathertightness or system warranty shall be provided where the manufacturer's certified installer performs the work and the manufacturer inspects the installation.
+
+```datasheet
+label: Finish Warranty Term
+type: select
+options:
+ - 20 years
+ - 25 years
+ - 30 years
+ - 35 years
+ - 40 years
+default: 30 years
+```
+
+```datasheet
+label: Weathertightness Warranty Term
+type: select
+options:
+ - 2 years
+ - 5 years
+ - 10 years
+ - 20 years
+default: 5 years
+```
+
+```datasheet
+label: Manufacturer System Warranty
+type: radio
+options:
+ - Required (NDL/no-dollar-limit)
+ - Required (standard)
+ - Not required
+default: Not required
+```
+
+# Spare Parts {toc}
+
+## Spare panels and matching touch-up coating allow future repair with the original profile and color, which can become unavailable after a finish line is discontinued. {note}
+
+## The Contractor shall deliver spare panels of each profile and color used, in the quantity specified, for future repairs.
+
+## The Contractor shall deliver spare clips, fasteners, closures, and sealant matching those installed.
+
+## The Contractor shall deliver touch-up coating matching each finish for field repair of minor coating damage.
+
+```datasheet
+label: Spare Full-Length Panels (per profile/color)
+type: range
+unit: each
+min: 0
+max: 20
+step: 1
+default: 3
+```
+
+```datasheet
+label: Spare Materials to Deliver
+type: checkbox
+options:
+ - Full-length panels
+ - Clips
+ - Fasteners
+ - Closures
+ - Sealant/butyl
+ - Touch-up coating
+default:
+ - Full-length panels
+ - Clips
+ - Fasteners
+ - Touch-up coating
+```