Packaged Rooftop Units
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 5
to Rev 6
in Packaged Rooftop Units.
---
title: Packaged Rooftop Units
…154 unchanged lines
- "Electrical data and wiring diagram"
- "Unit controller data and point list"
+constraint: all_of
```
…27 unchanged lines
- "Refrigerant handling certifications"
- "Field service reports during the warranty period"
+constraint: all_of
```
…38 unchanged lines
- "Warranty documentation correlated to serial numbers"
- "Spare parts receipt"
+constraint: all_of
```
…5 unchanged lines
```datasheet
−label: Minimum Manufacturer Experience
+label: Manufacturer Experience
type: range
unit: years
…3 unchanged lines
step: 1
default: 5
+constraint: min
```
…87 unchanged lines
```datasheet
−label: Minimum Outdoor Temperature for Mechanical Cooling Operation
+label: Lowest Outdoor Temperature for Mechanical Cooling Operation
type: range
unit: °F
…2 unchanged lines
max: 65
setpoints: [-20, -10, 0, 10, 20, 30, 40, 50, 55, 65]
+constraint: max
```
…69 unchanged lines
setpoints: [2, 2.5, 3, 4, 5, 6, 7.5, 8.5, 10, 12.5, 15, 17.5, 20, 25, 30, 35, 40, 50, 60, 70, 75, 80, 90, 100, 110, 120, 130, 150]
default: deferred
+constraint: exact
```
…15 unchanged lines
```datasheet
−label: Minimum Full-Load Energy Efficiency Ratio (EER)
+label: Full-Load Energy Efficiency Ratio (EER)
type: range
unit: EER
…4 unchanged lines
step: 0.1
default: derived
+constraint: min
```
### The integrated energy efficiency ratio shall be not less than the value indicated in the datasheet.
```datasheet
−label: Minimum Integrated Energy Efficiency Ratio (IEER)
+label: Integrated Energy Efficiency Ratio (IEER)
type: range
unit: IEER
…4 unchanged lines
step: 0.1
default: derived
+constraint: min
```
### Heat pump units rated under AHRI 340/360 shall have a heating coefficient of performance at 47°F outdoor not less than the value indicated in the datasheet.
```datasheet
−label: Minimum Heat Pump Heating Coefficient of Performance at 47°F
+label: Heat Pump Heating Coefficient of Performance at 47°F
type: range
unit: COP
…4 unchanged lines
step: 0.1
default: derived
+constraint: min
```
…9 unchanged lines
```datasheet
−label: Minimum Seasonal Energy Efficiency Ratio (SEER2)
+label: Seasonal Energy Efficiency Ratio (SEER2)
type: range
unit: SEER2
…4 unchanged lines
step: 0.1
default: derived
+constraint: min
```
### Heat pump units rated under AHRI 210/240 shall have a heating seasonal performance factor not less than the value indicated in the datasheet.
```datasheet
−label: Minimum Heating Seasonal Performance Factor (HSPF2)
+label: Heating Seasonal Performance Factor (HSPF2)
type: range
unit: HSPF2
…4 unchanged lines
step: 0.1
default: derived
+constraint: min
```
…110 unchanged lines
```datasheet
−label: Largest Permitted Minimum Cooling Capacity Step
+label: Smallest Cooling Capacity Step
type: range
unit: '%'
…2 unchanged lines
max: 100
setpoints: [10, 15, 20, 25, 33, 50, 100]
+constraint: max
```
…18 unchanged lines
default:
- "Crankcase heater on each compressor"
+constraint: all_of
```
…3 unchanged lines
```datasheet
−label: Minimum Number of Independent Refrigerant Circuits
+label: Number of Independent Refrigerant Circuits
type: range
unit: circuits
…2 unchanged lines
max: 4
setpoints: [1, 2, 3, 4]
+constraint: min
```
…83 unchanged lines
step: 5
default: deferred
+constraint: exact
```
…25 unchanged lines
```datasheet
−label: Maximum Low-Fire Gas Input as a Percentage of Full Input
+label: Low-Fire Gas Input as a Percentage of Full Input
type: range
unit: '%'
…2 unchanged lines
max: 100
setpoints: [10, 20, 25, 33, 40, 50, 65, 100]
+constraint: max
```
### The thermal efficiency of the gas heating section shall be not less than the value indicated in the datasheet.
```datasheet
−label: Minimum Gas Heating Thermal Efficiency
+label: Gas Heating Thermal Efficiency
type: range
unit: '%'
…4 unchanged lines
setpoints: [78, 80, 81, 82, 90, 95, 97]
default: derived
+constraint: min
```
…10 unchanged lines
step: 0.5
default: deferred
+constraint: exact
```
…30 unchanged lines
step: 0.5
default: deferred
+constraint: exact
```
…27 unchanged lines
```datasheet
−label: Minimum Outdoor Temperature for Compressor Heating Operation
+label: Lowest Outdoor Temperature for Compressor Heating Operation
type: range
unit: °F
…2 unchanged lines
max: 45
setpoints: [-25, -15, -5, 0, 5, 10, 17, 25, 35, 45]
+constraint: max
```
…23 unchanged lines
max: 65
setpoints: [10, 20, 25, 30, 35, 40, 45, 50, 55, 65]
+constraint: exact
```
…34 unchanged lines
step: 5
default: deferred
+constraint: exact
```
…8 unchanged lines
step: 5
default: deferred
+constraint: exact
```
…95 unchanged lines
step: 1
default: derived
+constraint: exact
```
…53 unchanged lines
- "Local annunciation at the unit controller"
- "Report to the building automation system"
+constraint: all_of
```
…5 unchanged lines
```datasheet
−label: Minimum Outdoor Airflow
+label: Outdoor Airflow
type: range
unit: cfm
…4 unchanged lines
step: 25
default: deferred
+constraint: min
```
…82 unchanged lines
```datasheet
−label: Minimum Enthalpy Recovery Ratio
+label: Enthalpy Recovery Ratio
type: range
unit: '%'
…4 unchanged lines
step: 5
default: derived
+constraint: min
```
…26 unchanged lines
step: 50
default: deferred
+constraint: exact
```
…8 unchanged lines
step: 0.05
default: deferred
+constraint: exact
```
…88 unchanged lines
setpoints: [208, 230, 460, 575]
default: deferred
+constraint: exact
```
…43 unchanged lines
```datasheet
−label: Maximum A-Weighted Outdoor Sound Power Level
+label: A-Weighted Outdoor Sound Power Level
type: range
unit: dB
…2 unchanged lines
max: 110
step: 1
+constraint: max
```
…29 unchanged lines
max: 50
setpoints: [2, 3, 5, 7.5, 10, 12.5, 15, 20, 25, 30, 40, 50]
+constraint: exact
```
…5 unchanged lines
```datasheet
−label: Minimum Cabinet Panel Thermal Resistance
+label: Cabinet Panel Thermal Resistance
type: range
unit: hr·ft²·°F/Btu
…2 unchanged lines
max: 15
step: 0.5
+constraint: min
```
…15 unchanged lines
```datasheet
−label: Minimum Exterior Finish Salt Spray Exposure
+label: Exterior Finish Salt Spray Exposure
type: range
unit: hours
…2 unchanged lines
max: 3000
setpoints: [500, 750, 1000, 1500, 2000, 2500, 3000]
+constraint: min
```
…79 unchanged lines
max: 4
setpoints: [1, 2, 4]
+constraint: exact
```
…113 unchanged lines
setpoints: [8, 12, 14, 16, 18, 24, 30, 36]
default: deferred
+constraint: exact
```
…22 unchanged lines
```datasheet
−label: Minimum Isolator Static Deflection
+label: Isolator Static Deflection
type: range
unit: in.
…2 unchanged lines
max: 3
setpoints: [0.25, 0.35, 0.75, 1, 1.5, 2, 2.5, 3]
+constraint: min
```
…89 unchanged lines
setpoints: [5, 10, 14, 18, 22, 25, 35, 42, 50, 65, 100]
default: deferred
+constraint: min
```
…103 unchanged lines
- "Compressor lockout and general alarm status"
- "Occupied and unoccupied mode command"
+constraint: all_of
```
…88 unchanged lines
- "Safety device trip verification"
- "Controls point-to-point verification"
+constraint: all_of
```
…157 unchanged lines
- "Filters installed"
- "Service clearances verified clear"
+constraint: all_of
```
…49 unchanged lines
- "Verification of drain pan drainage during cooling operation"
- "Integrated testing with the fire alarm system"
+constraint: all_of
```
…19 unchanged lines
step: 1
default: 10
+constraint: max
```
…48 unchanged lines
setpoints: [1, 2, 3, 5, 10]
default: 1
+constraint: min
```
…7 unchanged lines
setpoints: [0, 1, 2, 3, 5]
default: 1
+constraint: min
```
…25 unchanged lines
setpoints: [1, 2, 3, 5, 10]
default: 5
+constraint: min
```
…15 unchanged lines
setpoints: [1, 5, 10, 15, 20, 25]
default: 10
+constraint: min
```
…19 unchanged lines
setpoints: [1, 2, 3, 5]
default: 1
+constraint: min
```
…24 unchanged lines
- "One complete set of drive belts for every belt-driven fan"
- "One set of every fuse type installed"
+constraint: all_of
```
…7 unchanged lines
## The operation and maintenance manual shall include a filter change schedule derived from the initial and change-out resistances stated in the submittal, and, where a detection system is furnished, the replacement date of each refrigerant detection sensor.