title: Pre-Action and Deluge Sprinkler Systems
…165 unchanged lines
### The Contractor shall confirm designer qualification requirements for both the water-side and detection-side disciplines before assigning the design work.
−### The water-side layout shall be prepared by a licensed fire protection engineer or a NICET-certified sprinkler designer, and the detection and releasing design by a person holding NICET certification in fire alarm systems or a licensed engineer, as required by the jurisdiction. {note}
+### The water-side layout shall be prepared by a licensed fire protection engineer or a NICET-certified sprinkler designer, and the detection and releasing design by a person holding NICET certification in fire alarm systems or a licensed engineer, as required by the jurisdiction.
## Closeout Submittals {toc}
…83 unchanged lines
```
−### Where the building's property insurance carrier or the Owner requires FM Global compliance, all components shall be FM-approved in addition to UL-listed.
−
### FM and UL listings are not identical, and cross-zoned detection arrangements accepted under one listing or jurisdiction may not be accepted under another. {note}
…4 unchanged lines
### Internal corrosion is an aggressive problem in pre-action and deluge systems: residual water trapped at low points after testing or a release, combined with the oxygen in the supervisory air (pre-action) or the open atmosphere (deluge), drives microbiologically influenced corrosion (MIC) and oxygen pitting that can perforate the pipe wall over the service life. {note}
+### For pre-action systems the Contractor shall provide one of three corrosion-mitigation approaches: galvanized steel pipe throughout; nitrogen inerting using a listed nitrogen generator that displaces oxygen; or both, where the Owner's risk profile or insurance requirements warrant enhanced protection.
+
```datasheet
label: Corrosion Mitigation Approach
…7 unchanged lines
```
−### For pre-action systems the Contractor shall provide one of three corrosion-mitigation approaches: galvanized steel pipe throughout; nitrogen inerting using a listed nitrogen generator that displaces oxygen; or both, where the Owner's risk profile or insurance requirements warrant enhanced protection.
−
### NFPA 13 recognizes nitrogen inerting as an alternative to galvanized pipe for corrosion control on supervised dry systems, and nitrogen is the default for long-life critical assets such as data centers and freezer warehouses. {note}
…49 unchanged lines
min: 40
max: 250
− setpoints: [100, 125, 150, 175, 200, 250]
+ setpoints: [40, 100, 125, 150, 175, 200, 250]
default: 150
```
…20 unchanged lines
### Hazard classification determines the design density, the design area, and therefore the flow and pressure demand on the water supply. {note}
+### The hazard classification shall be assigned by the designer based on the occupancy descriptions in NFPA 13 Chapter 5 and confirmed with the Owner and the AHJ before the hydraulic design is finalized.
+
```datasheet
label: Predominant Occupancy Hazard Classification
…10 unchanged lines
```
−### The hazard classification shall be assigned by the designer based on the occupancy descriptions in NFPA 13 Chapter 5 and confirmed with the Owner and the AHJ before the hydraulic design is finalized.
−
### Pre-action systems most commonly protect Light Hazard and Ordinary Hazard occupancies, while archives and records storage may be Light Hazard or may invoke the storage rules. {note}
…53 unchanged lines
### The hose stream allowance is the same as for a wet-pipe system at the same hazard classification: 100 gpm for light hazard, 250 gpm for ordinary hazard, and 500 gpm for extra hazard. {note}
+### The hose stream allowance shall be specified to match the hazard classification of the sprinkler or deluge design.
+
```datasheet
label: Hose Stream Allowance
…13 unchanged lines
### Because deluge demand is large with all heads flowing, deluge systems frequently require a fire pump. {note}
+### Water supply data shall be obtained by a hydrant flow test conducted at or near the project site in accordance with NFPA 291, no more than 12 months prior to the date of submittal.
+
```datasheet
label: Water Supply Source
…6 unchanged lines
```
+### Static pressure, residual pressure, and pitot flow shall be recorded.
+
```datasheet
label: Static Pressure at Flow Test
…4 unchanged lines
min: 20
max: 150
− setpoints: [40, 50, 60, 70, 80, 90, 100, 120, 150]
+ setpoints: [20, 40, 50, 60, 70, 80, 90, 100, 120, 150]
default: 70
```
…7 unchanged lines
min: 10
max: 130
− setpoints: [20, 30, 40, 50, 60, 70, 80, 100, 130]
+ setpoints: [10, 20, 30, 40, 50, 60, 70, 80, 100, 130]
default: 50
```
−### Water supply data shall be obtained by a hydrant flow test conducted at or near the project site in accordance with NFPA 291, no more than 12 months prior to the date of submittal.
−
−### Static pressure, residual pressure, and pitot flow shall be recorded.
−
### The designer shall plot the supply curve and confirm that the system demand including hose stream falls below the supply curve with the safety margin required by NFPA 13.
…7 unchanged lines
### When a detector operates, the releasing control unit energizes the release solenoid (or trips a pneumatic actuator), the pre-action valve opens, and water fills the piping up to the still-closed sprinklers; water then discharges only when a sprinkler subsequently opens from heat. {note}
+### The single interlock provides one layer of protection against accidental discharge: a physically broken sprinkler or fitting in a room with no fire releases supervisory air and signals a trouble condition, but it does not admit water, because no detector has operated.
+
+### Single-interlock systems are limited by NFPA 13 to no more than 1,000 automatic sprinklers controlled by any single pre-action valve.
+
```datasheet
label: Maximum Sprinklers per Pre-Action Valve
…3 unchanged lines
min: 100
max: 1000
− setpoints: [250, 500, 750, 1000]
+ setpoints: [100, 250, 500, 750, 1000]
default: 1000
```
−### The single interlock provides one layer of protection against accidental discharge: a physically broken sprinkler or fitting in a room with no fire releases supervisory air and signals a trouble condition, but it does not admit water, because no detector has operated.
−
−### Single-interlock systems are limited by NFPA 13 to no more than 1,000 automatic sprinklers controlled by any single pre-action valve.
−
### Because water arrives on detection before the sprinklers open, the single-interlock system does not take the 30 percent design-area penalty.
…35 unchanged lines
### The choice of detection device depends on the speed of detection required, the environment (temperature, dust, airflow, ceiling height), and the hazard. {note}
+### Detection devices shall be selected and spaced for the hazard and the protected environment in accordance with NFPA 72.
+
```datasheet
label: Releasing Detection Type
…10 unchanged lines
```
−### Detection devices shall be selected and spaced for the hazard and the protected environment in accordance with NFPA 72.
−
### Detection devices shall be of a type listed for releasing service.
…4 unchanged lines
### Cross-zoning guards against an accidental release from a single faulty or transient detector signal, which is exactly the failure mode that pre-action and deluge systems exist to prevent. {note}
+### For releasing service, where cross-zoned (coincidence) logic is used, two separate detection zones or two separate detectors shall operate before a release signal is issued.
+
```datasheet
label: Detection Releasing Logic
…7 unchanged lines
```
−### For releasing service, where cross-zoned (coincidence) logic is used, two separate detection zones or two separate detectors shall operate before a release signal is issued.
−
### On a single-interlock pre-action system, cross-zoned detection alone releases the valve.
…29 unchanged lines
### On electric release, the releasing control unit energizes or de-energizes the solenoid to vent the priming chamber and allow the valve to open. {note}
+### The valve type — single-interlock or double-interlock pre-action, or deluge — shall be specified for the system's hazard and release configuration.
+
```datasheet
label: Valve Type
…8 unchanged lines
```
+### The valve release method — electric, pneumatic, or both — shall be specified and shall be compatible with the selected valve type.
+
```datasheet
label: Valve Release Method
…6 unchanged lines
```
+### The pre-action or deluge valve size shall be specified to match the hydraulic design of the system.
+
```datasheet
label: Valve Size
…34 unchanged lines
### Pre-action systems shall be maintained under supervisory air or nitrogen so that the loss of pressure from an opened sprinkler or damaged pipe is detected.
−### Deluge systems are open to atmosphere and are not air-supervised. {note}
```datasheet
…8 unchanged lines
default: "Dedicated air compressor with listed air maintenance device"
```
+### Deluge systems are open to atmosphere and are not air-supervised. {note}
+### Where the supervisory gas is air, an air compressor with a listed air maintenance device shall be provided, and the air maintenance device shall limit the rate of air introduction so that a small leak is not masked by an oversized restoration capacity.
+
```datasheet
label: Air Compressor Restoration Time (pre-action)
…7 unchanged lines
```
+### Where the supervisory gas is nitrogen, a listed nitrogen generator (membrane or pressure-swing adsorption) shall be provided, producing at least 98 percent nitrogen at the valve and purged to the listed purity at the most remote sprinkler.
+
```datasheet
label: Nitrogen Purity at Sprinkler (pre-action, where used)
…3 unchanged lines
min: 90
max: 99
− setpoints: [95, 98, 99]
+ setpoints: [90, 95, 98, 99]
default: 98
```
−### Where the supervisory gas is air, an air compressor with a listed air maintenance device shall be provided, and the air maintenance device shall limit the rate of air introduction so that a small leak is not masked by an oversized restoration capacity.
−
−### Where the supervisory gas is nitrogen, a listed nitrogen generator (membrane or pressure-swing adsorption) shall be provided, producing at least 98 percent nitrogen at the valve and purged to the listed purity at the most remote sprinkler.
−
### Nitrogen is the preferred supervisory gas for data centers and freezer warehouses because it eliminates the oxygen that drives internal corrosion over the long service life of these critical assets. {note}
…24 unchanged lines
### Pre-action systems use closed (automatic) sprinklers in which the thermal element holds the orifice closed until heat opens the individual sprinkler; deluge systems use open sprinklers or directional spray nozzles with no thermal element, every device permanently open and discharging the instant the valve trips. {note}
+### The discharge device type shall be specified as closed sprinklers for pre-action service or open sprinklers or nozzles for deluge service.
+
```datasheet
label: Discharge Device Type
…8 unchanged lines
```
+### The sprinkler or nozzle K-factor shall be specified consistent with the hydraulic demand of the discharge device selected for the system.
+
```datasheet
label: Sprinkler / Nozzle K-Factor
…8 unchanged lines
```
+### Where closed heads are used in pre-action service, the sprinkler thermal response shall be specified as standard or quick response.
+
```datasheet
label: Sprinkler Thermal Response (pre-action closed heads)
…6 unchanged lines
```
+### Where closed heads are used in pre-action service, the sprinkler temperature rating shall be specified based on the anticipated ceiling temperature.
+
```datasheet
label: Sprinkler Temperature Rating (pre-action closed heads)
…16 unchanged lines
### Steel pipe shall conform to ASTM A795 or ASTM A53; ASTM A795 is the purpose-written fire protection standard and is preferred.
−### The galvanized variant is strongly preferred over black for these normally dry systems unless a pre-action system is also nitrogen-inerted, because internal corrosion in cycled wet-dry environments is significantly more aggressive than in continuously wet systems. {note}
```datasheet
…7 unchanged lines
default: "ASTM A795 (galvanized) — preferred"
```
+### The galvanized variant is strongly preferred over black for these normally dry systems unless a pre-action system is also nitrogen-inerted, because internal corrosion in cycled wet-dry environments is significantly more aggressive than in continuously wet systems. {note}
+### Steel pipe shall conform to ASTM A795 or ASTM A53, with ASTM A795 preferred.
+
+### Schedule 40 pipe shall be used for threaded joints in sizes 3 in. and smaller; Schedule 10 listed for dry-system service or Schedule 40 may be used for grooved or welded joints.
+
```datasheet
label: Primary Joining Method
…7 unchanged lines
```
−### Steel pipe shall conform to ASTM A795 or ASTM A53, with ASTM A795 preferred.
−
−### Schedule 40 pipe shall be used for threaded joints in sizes 3 in. and smaller; Schedule 10 listed for dry-system service or Schedule 40 may be used for grooved or welded joints.
−
### Schedule 10 pipe shall not be threaded.
…19 unchanged lines
### Inadequate pitch leaves trapped water that corrodes the pipe and, in cold applications, freezes and ruptures it. {note}
+### System piping shall be pitched to drain back to the valve or to auxiliary drains at low points.
+
+### NFPA 13 requires minimum pitch of 1/2 in. per 10 ft for branch lines and 1/4 in. per 10 ft for mains in steel-pipe systems.
+
```datasheet
label: Minimum Branch Line Pitch
…18 unchanged lines
```
−### System piping shall be pitched to drain back to the valve or to auxiliary drains at low points.
−
−### NFPA 13 requires minimum pitch of 1/2 in. per 10 ft for branch lines and 1/4 in. per 10 ft for mains in steel-pipe systems.
−
### Deluge piping shall drain completely after every operation, because the open piping admits and retains test and discharge water at every low point.
…102 unchanged lines
### Deluge systems, being open to atmosphere, are not air-tested. {note}
+### Pre-action systems shall be air-tested at 40 psi for 24 hours with a pressure loss not exceeding 1.5 psi, in accordance with NFPA 13, after the system is drained from the hydrostatic test and before it is placed in service.
+
```datasheet
label: Air Test (pre-action) Allowable Loss
…6 unchanged lines
```
−### Pre-action systems shall be air-tested at 40 psi for 24 hours with a pressure loss not exceeding 1.5 psi, in accordance with NFPA 13, after the system is drained from the hydrostatic test and before it is placed in service.
−
### Leaks shall be located by soap-bubble or ultrasonic testing and corrected before retest.
…2 unchanged lines
### The trip test confirms the calculated trip-time and water-delivery values in practice. {note}
+### The pre-action or deluge valve shall be trip-tested by operating the detection system (and, for double-interlock systems, also venting the supervisory air) and confirming that the releasing control unit issues the release signal, the solenoid operates, the valve opens, and the alarm signals transmit.
+
+### For pre-action systems the test shall confirm that water reaches the inspector's test connection at the most remote point.
+
+### For double-interlock pre-action and deluge systems the measured water delivery time from operation to discharge shall not exceed 60 seconds, consistent with the dry-pipe water delivery rule.
+
```datasheet
label: Maximum Water Delivery Time at Trip Test
…7 unchanged lines
```
+### Where the field-measured time exceeds the calculated value the cause shall be investigated and corrected.
+
+### The full releasing matrix shall be verified — each initiating device or zone, the cross-zoned logic, each releasing output, and each interlock (HVAC shutdown, damper, equipment power-down) — and the results recorded.
+
```datasheet
label: Trip Test Scope
…9 unchanged lines
```
−### The pre-action or deluge valve shall be trip-tested by operating the detection system (and, for double-interlock systems, also venting the supervisory air) and confirming that the releasing control unit issues the release signal, the solenoid operates, the valve opens, and the alarm signals transmit.
−
−### For pre-action systems the test shall confirm that water reaches the inspector's test connection at the most remote point.
−
−### For double-interlock pre-action and deluge systems the measured water delivery time from operation to discharge shall not exceed 60 seconds, consistent with the dry-pipe water delivery rule.
−
−### Where the field-measured time exceeds the calculated value the cause shall be investigated and corrected.
−
−### The full releasing matrix shall be verified — each initiating device or zone, the cross-zoned logic, each releasing output, and each interlock (HVAC shutdown, damper, equipment power-down) — and the results recorded.
−
## Partial-Flow and Solenoid Tests {toc}
…24 unchanged lines
min: 10
max: 180
− setpoints: [20, 30, 40, 50, 60, 70, 80, 100, 120, 150]
+ setpoints: [10, 20, 30, 40, 50, 60, 70, 80, 100, 120, 150, 180]
default: 50
```
…32 unchanged lines
## Seismic joint failure is especially consequential on these systems because loss of supervisory air or damage to the releasing/pilot lines can produce a trouble condition or, on a single-interlock system already in the released state, an unintended discharge. {note}
+## Hangers shall be listed for fire protection use and installed per NFPA 13 Chapter 17, sized for the water-filled pipe weight because the pipe fills with water during hydrostatic testing and after every release.
+
+## Where the building is in Seismic Design Category C, D, E, or F per ASCE 7 and the IBC, lateral and longitudinal seismic bracing shall be provided per NFPA 13 Chapter 18, with flexible couplings at the prescribed locations.
+
```datasheet
label: Seismic Design Category
…20 unchanged lines
```
−## Hangers shall be listed for fire protection use and installed per NFPA 13 Chapter 17, sized for the water-filled pipe weight because the pipe fills with water during hydrostatic testing and after every release.
−
−## Where the building is in Seismic Design Category C, D, E, or F per ASCE 7 and the IBC, lateral and longitudinal seismic bracing shall be provided per NFPA 13 Chapter 18, with flexible couplings at the prescribed locations.
−
# Delivery, Storage, and Handling {toc}
…99 unchanged lines
## The Owner shall maintain a service agreement with qualified fire protection and fire alarm service contractors, and records of all inspections and tests shall be retained on-site and available to the AHJ.