Roof Drainage

Revision 4 · SynC Standards Team — Specifier, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 11, 2026 +14 −17

Migrate datasheet deferrals to drawing_ref + default: deferred
Showing changes from Rev 3 to Rev 4 in Roof Drainage.
Tag changes −Plumbing−Roof Drains−Storm Drainage
---
title: Roof Drainage
196 unchanged lines
- "10 inch"
- "12 inch"
- "Per drawings"
default: "Per drawings"
+default: deferred
```
9 unchanged lines
label: Secondary (Overflow) Drainage Method
type: radio
+drawing_ref: true
options:
- "Overflow roof drains with independent piping to a conspicuous discharge"
- "Overflow scuppers through the parapet wall"
- "Combination — overflow drains at interior low points, scuppers at parapet"
- "Per drawings"
default: "Overflow roof drains with independent piping to a conspicuous discharge"
```
24 unchanged lines
label: Roof Drain Body Material
type: radio
+drawing_ref: true
options:
- "Cast iron with corrosion-resistant coating"
- "Cast iron with epoxy or PVC coating (corrosive or coastal environments)"
- "Cast aluminum (weight-sensitive applications)"
- "Per drawings"
default: "Cast iron with corrosion-resistant coating"
```
6 unchanged lines
label: Roof Drain Outlet Connection
type: radio
+drawing_ref: true
options:
- "No-hub outlet (hubless cast iron coupling connection)"
- "Inside-caulk outlet (hub-and-spigot)"
- "Threaded outlet"
- "Per drawings"
default: "No-hub outlet (hubless cast iron coupling connection)"
```
8 unchanged lines
label: Primary Roof Drain Dome / Strainer Type
type: select
+drawing_ref: true
options:
- "Cast iron dome strainer (low-slope roof, non-traffic)"
- "Polyethylene / polymer dome strainer (low-slope roof, non-traffic)"
- "Aluminum dome strainer (low-slope roof, non-traffic)"
- "Flat secured grate (deck, balcony, walkable surfaces)"
- "Per drawings"
default: "Cast iron dome strainer (low-slope roof, non-traffic)"
```
24 unchanged lines
label: Drain Deck Attachment
type: radio
+drawing_ref: true
options:
- "Underdeck clamp to structural deck"
- "Set in poured concrete roof sump"
- "Sump receiver / sump pan for tapered insulation sump"
- "Per drawings"
default: "Underdeck clamp to structural deck"
```
46 unchanged lines
- "To downspout boot at grade, separate from primary downspouts"
- "To a visible point above grade at a building entrance or occupied area"
- "Per drawings"
default: "Through exterior wall to splash block at grade (conspicuous)"
```
39 unchanged lines
label: Interior Storm Piping Material
type: radio
+drawing_ref: true
options:
- "Hubless cast iron (ASTM A888 / CISPI 301)"
- "Hub-and-spigot cast iron (ASTM A74), compression gasket joints"
- "Copper DWV (ASTM B306)"
- "PVC DWV Schedule 40 (ASTM D2665)"
- "Per drawings"
default: "Hubless cast iron (ASTM A888 / CISPI 301)"
```
105 unchanged lines
type: select
unit: ft on center
+drawing_ref: true
options:
- "5 ft on center, plus at each joint and coupling"
- "At each joint and coupling, plus at midspan of lengths exceeding 5 ft"
- "Per drawings"
default: "5 ft on center, plus at each joint and coupling"
```
3 unchanged lines
type: select
unit: ft on center
+drawing_ref: true
options:
- "4 ft on center maximum (PVC)"
- "Per pipe manufacturer for material, size, and temperature"
- "Per drawings"
default: "4 ft on center maximum (PVC)"
```
12 unchanged lines
label: Vertical Leader Support
type: radio
+drawing_ref: true
options:
- "Riser clamp below each floor slab"
- "Riser clamp through floor sleeve with clamping collar"
- "Per drawings"
default: "Riser clamp below each floor slab"
```
8 unchanged lines
label: Vertical Leader Expansion Provision
type: radio
+drawing_ref: true
options:
- "None required (cast iron, within joint and support tolerance)"
- "Expansion joint at leader base or as indicated"
- "Engineered offset / expansion loop per drawings"
- "Per drawings"
default: "None required (cast iron, within joint and support tolerance)"
```
16 unchanged lines
label: Condensation Insulation Extent
type: select
+drawing_ref: true
options:
- "Roof drain bodies and all horizontal conductors in occupied / conditioned spaces"
- "All storm conductors, horizontal and vertical, in occupied / conditioned spaces"
- "Roof drain bodies and sumps only"
- "Per drawings"
default: "Roof drain bodies and all horizontal conductors in occupied / conditioned spaces"
```
41 unchanged lines
- "1/8 inch per foot (1 percent)"
- "1/4 inch per foot (2 percent)"
- "Per drawings"
default: "1/8 inch per foot (1 percent)"
```
12 unchanged lines
label: Cleanout at Base of Each Leader
type: radio
+drawing_ref: true
options:
- "Required at base of every leader"
- "Per drawings"
default: "Required at base of every leader"
```
8 unchanged lines
label: Fire-Rated Penetration Firestop (Plastic Pipe)
type: radio
+drawing_ref: "firestop assembly drawings"
options:
- "Listed intumescent collar / wrap"
- "Listed intumescent sealant with mineral wool backer"
- "Per UL or FM listed assembly as specified on drawings"
default: "Listed intumescent collar / wrap"
```
111 unchanged lines
## The warranty shall not limit the Contractor's obligation to comply with all applicable code requirements and the requirements of this standard. {note}

View current revision