Roof Hatches and Smoke Vents

Read revision 2

Revision 2 · Aug 26, 2026 +19 −17

Corpus sync: neutrality remakes, note hygiene, datasheet relocation, transformer-split cross-refs
Showing changes from Rev 1 to Rev 2 in Roof Hatches and Smoke Vents.
---
title: Roof Hatches and Smoke Vents
31 unchanged lines
## Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
## Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing. {note}
+## Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
| Standard | Title |
88 unchanged lines
## Manufacturer Qualifications {toc}
### Units shall be the standard catalog product of a manufacturer regularly engaged in the production of factory-fabricated roof hatches and smoke vents. {note}
+### Units shall be the standard catalog product of a manufacturer regularly engaged in the production of factory-fabricated roof hatches and smoke vents.
### Each unit shall be factory cycle-tested for proper operation of the cover, hold-open hardware, and latching before shipment.
20 unchanged lines
```
### Spring-assisted covers on exposed roofs can act as a sail and be damaged by wind uplift when held open; cover opening direction shall be coordinated with building orientation and prevailing wind. {note}
+### Spring-assisted covers on exposed roofs can act as a sail and be damaged by wind uplift when held open; cover opening direction shall be coordinated with building orientation and prevailing wind.
### The cover opening direction shall be oriented so the open cover does not face the prevailing wind on exposed rooftops.
17 unchanged lines
## Energy and Air Barrier Compliance {toc}
### A factory-insulated cover with an R-value below the surrounding roof assembly creates an energy-code deficiency that is commonly missed at permit; cover insulation shall meet or exceed the adjacent roof assembly minimum. {note}
+### A factory-insulated cover with an R-value below the surrounding roof assembly creates an energy-code deficiency that is commonly missed at permit; cover insulation shall meet or exceed the adjacent roof assembly minimum.
### Cover and curb insulation R-value shall equal or exceed the minimum required for the surrounding roof assembly under ASHRAE 90.1 for the project climate zone.
48 unchanged lines
### Equipment hatches require an opening sized for the largest item passed; openings above roughly 48 in. × 96 in. are custom-fabricated. {note}
+### Where the equipment hatch clear opening exceeds the manufacturer's largest standard catalog size, the unit shall be custom-fabricated to the dimensions indicated. [[drawing: equipment hatch opening dimensions]]
+
```datasheet
label: Equipment Hatch Clear Opening
8 unchanged lines
```
### Where the equipment hatch clear opening exceeds the manufacturer's largest standard catalog size, the unit shall be custom-fabricated to the dimensions indicated. [[drawing: equipment hatch opening dimensions]]
## Cover and Curb Material {toc}
50 unchanged lines
```
### Insulation shall be a non-wicking type — rigid polyisocyanurate or encapsulated fiberglass — protected by a metal liner on the cover interior. {note}
+### Insulation shall be a non-wicking type — rigid polyisocyanurate or encapsulated fiberglass — protected by a metal liner on the cover interior.
### The cover insulation shall be enclosed by a metal liner pan and shall not be left exposed on the cover underside.
# Hardware {toc}
## Roof hatch hardware shall permit one-person operation from inside and provide positive holding of the open cover against incidental wind. {note}
+## Roof hatch hardware shall permit one-person operation from inside and provide positive holding of the open cover against incidental wind.
## Hold-Open Hardware {toc}
11 unchanged lines
```
### The hold-open arm shall include a release handle that allows the cover to be closed in a controlled manner without freefall. {note}
+### The hold-open arm shall include a release handle that allows the cover to be closed in a controlled manner without freefall.
### The hold-open mechanism shall require a deliberate manual release to disengage and shall not release under wind load alone.
19 unchanged lines
## Weatherproofing {toc}
### The cover shall close against a continuous compressible gasket to seal the cover-to-curb joint against wind-driven rain. {note}
+### The cover shall close against a continuous compressible gasket to seal the cover-to-curb joint against wind-driven rain.
### The cover-to-curb joint shall be gasketed with a continuous closed-cell or EPDM gasket.
52 unchanged lines
### The prescriptive IBC 910 vent-to-floor-area ratio is 1:100 for storage height 12 ft or less and 1:75 for storage height greater than 12 ft; an engineered NFPA 204 design may establish a different ratio. {note}
+### The vent-to-floor-area ratio basis shall be specified, using the IBC 910 prescriptive ratio for the applicable storage height or an NFPA 204 engineered design.
+
```datasheet
label: Vent-to-Floor-Area Ratio Basis
74 unchanged lines
# Finishes {toc}
## The exposed finish shall be selected for durability in the roof environment and for coordination with the building's architectural treatment. {note}
+## The exposed finish shall be selected for durability in the roof environment and for coordination with the building's architectural treatment.
## Cover Finish {toc}
### Galvanized and stainless covers may be furnished mill-finished; aluminum covers requiring a coordinated color shall receive a factory organic coating. {note}
+### Galvanized and stainless covers may be furnished mill-finished; aluminum covers requiring a coordinated color shall receive a factory organic coating.
### The cover shall be finished as scheduled.
33 unchanged lines
```
### A safety post or self-closing guardrail gate at the ladder shall be provided to protect the open hatch opening. {note}
+### A safety post or self-closing guardrail gate at the ladder shall be provided to protect the open hatch opening.
### A telescoping safety post or guardrail at the hatch opening shall be provided where the hatch serves a fixed ladder.
33 unchanged lines
## Protection and Adjustment {toc}
### Installed units shall be protected from construction traffic and debris until substantial completion. {note}
+### Installed units shall be protected from construction traffic and debris until substantial completion.
### Smoke and heat vents shall not be used as construction access or material hoisting points.
5 unchanged lines
# Delivery, Storage, and Handling {toc}
## Units shall be delivered factory-assembled in protective packaging with listing labels and operating instructions attached. {note}
+## Units shall be delivered factory-assembled in protective packaging with listing labels and operating instructions attached.
### Units shall be stored off the ground, covered, and protected from weather and physical damage until installation.
20 unchanged lines
### The warranty shall cover hardware operation, including hold-open arms, springs, latches, and smoke-vent release mechanisms.
### Warranty service for smoke and heat vents shall include restoration of the listed automatic operation following any covered failure. {note}
+### Warranty service for smoke and heat vents shall include restoration of the listed automatic operation following any covered failure.
# Spare Parts {toc}
## The Contractor shall furnish spare operating components to support post-occupancy maintenance of the installed units. {note}
+## The Contractor shall furnish spare operating components to support post-occupancy maintenance of the installed units.
### The Contractor shall furnish spare fusible links for not less than 10 percent of the installed smoke and heat vents, and not fewer than two of each rating used.
10 unchanged lines
- Spare latch assemblies
```

View current revision