Sanitary Sewer Systems (Site)

Rev 2 · Updated Jun 14, 2026 · View history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

NOTE This standard governs the materials, design criteria, fabrication, and installation of the site sanitary sewer collection system from the building service tie-in point to the point of connection at the public sewer main or on-site treatment facility. (1.1)
NOTE The system covered includes gravity sewer mains and service laterals, sanitary manholes, cleanouts, service wye and tee connections, pipe bedding and trench backfill, and sanitary lift stations with their wet wells, pumps, valve vaults, force mains, and controls. (1.2)
NOTE Where the public sewer extension within the right-of-way is governed by the authority having jurisdiction (AHJ) standard details, those details govern that segment and this standard governs the on-site portion only. (1.3)
NOTE The following are outside the scope of this standard. (1.4)
  • Interior building drain, waste, and vent (DWV) piping above or at the foundation wall, covered by Sanitary Waste And Vent Piping.
  • Storm drainage collection, catch basins, storm mains, and detention, covered by Storm Drainage.
  • Site earthwork, trench excavation, and backfill compaction independent of utility pipe, covered by Earthwork.
  • Site utility coordination and dry utilities (water main, gas, electric, telecom), covered by Site Utilities.
  • Wastewater treatment plant (WWTP) process equipment and structures.
  • Public right-of-way sewer extensions subject to municipal standard drawings, which follow the AHJ standard details.
NOTE Site sanitary work is intrinsically a coordination problem before it is a piping problem. (1.5)
NOTE The invert elevation at the public sewer tap fixes the entire downstream geometry of the on-site system: every upstream invert, manhole rim, and minimum-cover constraint flows backward from that one elevation. The need for a lift station, the achievable pipe slopes, and the conflict clearances with water main and storm are all decided early, in concert with Site Utilities, Storm Drainage, and Earthwork. Treat the tap invert and the design peak flow as the two anchor values that must be confirmed before pipe materials or structures are selected. (1.6)

2 Referenced Standards

NOTE Materials, design, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited or the authority having jurisdiction adopts a different edition. (2.1)
NOTE Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing. (2.2)
Standard Title
ASTM D3034 Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
ASTM F714 Polyethylene (PE) Plastic Pipe (DR-PR) Based on Outside Diameter
ASTM D3035 Polyethylene (PE) Plastic Pipe (DR-PR) Based on Controlled Outside Diameter
ASTM D2239 Polyethylene (PE) Plastic Pipe (SIDR-PR) Based on Controlled Inside Diameter
AWWA C151 / ANSI A21.51 Ductile-Iron Pipe, Centrifugally Cast
AWWA C150 / ANSI A21.50 Thickness Design of Ductile-Iron Pipe
ASTM C478 Precast Reinforced Concrete Manhole Sections
ASTM C443 Joints for Concrete Pipe and Manholes, Using Rubber Gaskets
ASTM C923 Resilient Connectors Between Reinforced Concrete Manhole Structures, Pipes, and Laterals
ASTM C990 Joints for Concrete Pipe, Manholes, and Precast Box Sections Using Preformed Flexible Joint Sealants
ASTM D3753 Glass-Fiber-Reinforced Polyester Manholes and Wet Wells
ASTM A48 Gray Iron Castings
ASCE/WEF MOP 60 (WEF FD-5) Gravity Sanitary Sewer Design and Construction, Second Edition
Ten States Standards Recommended Standards for Wastewater Facilities (Great Lakes-Upper Mississippi River Board)
NFPA 820 Fire Protection in Wastewater Treatment and Collection Facilities
ANSI/HI 1.1-1.6 Rotodynamic (Centrifugal) Pumps - Nomenclature, Definitions, Application, and Operation
NSF/ANSI 14 Plastics Piping System Components and Related Materials
OSHA 29 CFR 1910.146 Permit-Required Confined Spaces
NOTE ASTM F679 has been withdrawn; its scope for large-diameter PVC gravity sewer pipe was consolidated into ASTM D3034, which now covers 3 in. through 60 in. (2.3)
NOTE Any reference, submittal, or product data citing F679 for sewer pipe shall be updated to D3034. Citing the withdrawn standard creates submittal-review confusion and a potential non-compliance finding by the reviewing utility. (2.4)
NOTE The Ten States Standards are a state-adopted design-criteria floor, not an ASTM or ASCE numbered product standard. (2.5)

3 Submittals

3.1 Action Submittals

NOTE The Contractor shall submit the following action submittals for review and approval before any sanitary sewer material is ordered or installed: (3.1.1)
  • Product data for all gravity pipe, fittings, and joints, including material, stiffness class or DR, and NSF/ANSI 14 certification.
  • Product data for force main pipe, fittings, restraints, and air/vacuum release valves.
  • Shop drawings for each manhole, including barrel and cone sections, base, frame and cover, steps, and pipe-penetration connectors.
  • Manufacturer data and certified performance curves for each lift station pump, with the duty point and run-out point marked.
  • Lift station package shop drawings showing wet well, valve vault, piping, level controls, control panel, and access hatches.
  • Electrical and controls shop drawings for the lift station, including the NFPA 820 hazardous-area classification, enclosure NEMA ratings, and conduit seals.
  • Bedding and backfill gradation data with the source and AASHTO classification of the granular bedding material.
  • A proposed testing plan and sequence for low-pressure air, deflection (mandrel), and force main pressure testing.
Action submittals required before fabrication and installationcheckbox
Gravity pipe, fittings, and joint product data (with NSF/ANSI 14)
Force main pipe, fittings, restraints, and air/vacuum valve data
Manhole shop drawings (sections, base, frame/cover, steps, connectors)
Pump certified performance curves with duty and run-out points
Lift station package shop drawings
Lift station electrical and controls shop drawings
Bedding and backfill gradation with AASHTO classification
Testing plan and sequence

3.2 Closeout Submittals

NOTE The Contractor shall submit the following closeout submittals before final acceptance of the sanitary sewer system: (3.2.1)
  • Record drawings showing as-built horizontal alignment, invert elevations at each structure, and lateral tie-in stations and depths.
  • Certified test reports for all low-pressure air, deflection, and pressure tests, including any re-tests after remediation.
  • Manhole vacuum or exfiltration test reports where required by the AHJ.
  • Lift station startup and commissioning report, including pump drawdown test, alternation verification, and alarm function test.
  • Operation and maintenance manuals for the lift station pumps, controls, and valves.
  • Manufacturer warranties for pumps, controls, and pipe materials.
Closeout submittals required before final acceptancecheckbox
Record drawings with inverts, alignment, and lateral tie-ins
Certified pipe test reports (air, deflection, pressure)
Manhole vacuum or exfiltration test reports
Lift station startup and commissioning report
Lift station O&M manuals
Manufacturer warranties

4 Quality Assurance

NOTE The Contractor shall employ installers experienced in the placement, jointing, and testing of buried gravity and pressure sewer pipe of the materials and sizes specified. (4.1)
4.1.1Pipe and fittings of a given material shall be supplied by a single manufacturer for the project unless the Engineer approves an alternate in writing.
4.1.2PVC and HDPE pipe compounds shall carry NSF/ANSI 14 certification where required by the authority having jurisdiction.
4.1.3The lift station pumps, controls, and wet well of a packaged station shall be furnished by a single supplier with single-source responsibility for the integrated package.
4.1.4Confined-space entry for manholes and wet wells during construction and testing shall comply with OSHA 29 CFR 1910.146.
NOTE I/I prevention is the quality measure that matters most over the life of the system. (4.2)
NOTE Inflow and infiltration (I/I) is groundwater and stormwater entering the sewer through defective joints, cracked structures, and unsealed pipe penetrations. Excess I/I consumes hydraulic capacity, drives up treatment cost, and is the most common reason a utility rejects or conditionally accepts a new collection system. The single highest-leverage I/I defense is a properly installed flexible boot connector at every pipe-to-manhole penetration; mortared penetrations crack with settlement and are the dominant infiltration path. The testing requirements in this standard exist primarily to verify I/I integrity before backfill makes remediation destructive. (4.3)

5 Gravity Sewer Pipe

5.1 Material selection

NOTE The gravity sewer pipe material shall be selected for the burial depth, soil and groundwater conditions, and utility-conflict clearances of the run. (5.1.1)
NOTE PVC gasketed sewer pipe is the default gravity material for the great majority of site sanitary runs at normal depth. HDPE is selected where fusion-welded leak-free joints, long deflected pulls, or directional drilling are advantageous. Ductile iron is reserved for shallow-cover crossings, restrained-joint conditions, and the rigid segment at the building connection where loading or proximity to other utilities requires it. (5.1.2)
Gravity sewer pipe materialselect
PVC gasketed sewer pipe (ASTM D3034)
HDPE pipe (ASTM F714 / D3035)
Ductile iron pipe (AWWA C151)
5.1.3PVC gravity sewer pipe and fittings shall conform to ASTM D3034 with integral bell-and-spigot gasketed joints meeting ASTM D3212 and elastomeric gaskets meeting ASTM F477.
5.1.4The PVC pipe stiffness class shall be selected for the trench loading and burial depth, with SDR 35 (PS 46) as the standard selection and SDR 26 (PS 115) used at deeper burial or heavier surface loading.
5.1.5HDPE gravity sewer pipe shall conform to ASTM F714 or ASTM D3035, joined by butt-fusion or electrofusion, with a dimension ratio selected for the design condition.
5.1.6Ductile iron pipe shall conform to AWWA C151 with a pressure class and wall thickness designed per AWWA C150, and shall have a cement mortar or polyethylene lining suitable for sewage service.
PVC gravity pipe stiffness classselect
SDR 35 (PS 46)
SDR 26 (PS 115)
5.1.7The nominal gravity sewer pipe diameter shall be sized for the design peak flow at the design slope, with a minimum public-lateral main diameter of 8 in.
Gravity main nominal diameterselect
6
8
10
12
15
18
21
24

5.2 Hydraulic design

NOTE The gravity sewer shall be designed to maintain a self-cleansing velocity of at least 2.0 ft/s when flowing full or half-full at the design peak flow. (5.2.1)
NOTE Self-cleansing velocity keeps solids in suspension so the pipe scours itself rather than accumulating a sediment bed that reduces capacity and generates odor. The minimum slope that achieves 2.0 ft/s depends on pipe diameter and the Manning roughness coefficient; smaller pipe needs a steeper slope. A single flat minimum slope applied across all diameters is wrong in both directions: it is non-conservative for 8 in. pipe and grossly over-steep for 6 in. laterals. Compute the minimum slope per diameter. (5.2.2)
5.2.3The minimum slope for each pipe diameter shall be calculated to achieve a velocity of at least 2.0 ft/s flowing full, using a Manning roughness coefficient appropriate to the pipe material.
5.2.4The Manning roughness coefficient (n) used for design shall be no lower than the value below for the selected pipe material, to avoid an optimistic, under-sloped design.
Manning roughness coefficient (n) for gravity designrange
dimensionless
0.0110.015
0.013
5.2.5The design peak flow shall be computed from the average daily flow multiplied by a peaking factor appropriate to the contributing population or fixture-unit load, plus an infiltration allowance.
Peak flow peaking factor (over average daily flow)range
ratio
24
2.5
5.2.6Maximum spacing between manholes shall not exceed the value below for cleaning and inspection access, unless the AHJ permits a greater spacing for the installed equipment.
Maximum manhole spacingrange
ft
300500
400
5.2.7The minimum cover over the gravity sewer crown shall be maintained per the value below to protect the pipe from surface loading and frost, and shall be coordinated with finish grade profile sheets.
Minimum cover over pipe crownrange
ft
35
3
5.2.8Where the sanitary sewer crosses a water main, the vertical and horizontal separation shall comply with the AHJ separation rule, coordinated with Site Utilities.

5.3 Service laterals

NOTE Each building service lateral shall connect to the main through a factory-molded wye or tee fitting, or an approved manufactured saddle wye where a field connection to an existing main is required. (5.3.1)
NOTE Field-cored connections made without a proper manufactured saddle fitting are a leading source of I/I and of structural failure at the connection: a hand-cut hole with a mortared-in pipe stub cracks and admits groundwater. Specify a factory wye on new mains and an approved saddle wye fitting only where tying into an existing main. (5.3.2)
5.3.3The service lateral tie-in method shall be one of the approved methods below; hand-cored unmanufactured connections are prohibited.
Service lateral tie-in methodselect
Factory-molded wye on new main
Factory-molded tee on new main
Approved manufactured saddle wye on existing main
5.3.4The service lateral nominal diameter shall be a minimum of 4 in. for a single building service and 6 in. where required by the fixture-unit load.
Service lateral nominal diameterselect
4
6
8
5.3.5The service lateral slope shall be a minimum of 2.0 percent (1/4 in. per ft) toward the main unless a flatter slope is approved by the Engineer for a documented depth constraint.
5.3.6A cleanout shall be provided at the building face, at the property or easement line, and at intervals along the lateral and at each change of direction exceeding 45 degrees. The location of each cleanout shall be shown on the drawings utility plan.

6 Bedding and Backfill

NOTE The pipe bedding and trench backfill class shall be selected to support the pipe, protect the joints, and transfer surface loads without overstressing the pipe wall. (6.1)
NOTE Bedding is the engineered material placed under and around the pipe up to the spring line or pipe crown; it controls pipe deflection and joint integrity far more than the native backfill above it. "Granular fill" with no gradation or AASHTO limit is an open invitation for the contractor to use angular crushed concrete or oversized stone that point-loads and cracks PVC bell joints. Specify the bedding class and the gradation limits explicitly. (6.2)
6.2.1The bedding class shall be selected per the pipe material, manufacturer recommendation, and geotechnical conditions, from the approved classes below.
Pipe bedding classselect
Class B granular (compacted to spring line)
Class C ordinary (shaped bottom, granular haunching)
Concrete cradle or encasement
6.2.2Granular bedding material shall meet a specified gradation and AASHTO classification; crushed concrete and angular oversized aggregate that can damage pipe or joints are prohibited.
Maximum bedding aggregate particle sizerange
in
0.3751
0.75
6.2.3Bedding shall be placed and compacted in lifts under and around the pipe up to the spring line, with the haunch zone fully and uniformly supported.
6.2.4Concrete cradle or encasement shall be used only where indicated for shallow cover, heavy surface loading, or utility crossings profile and crossing details.
6.2.5Trench backfill above the pipe zone shall be placed and compacted per Earthwork, with compaction within paved or trafficked areas meeting the project pavement-subgrade requirement.
6.2.6A detectable marking tape or tracer wire shall be installed in the trench above non-metallic pipe to allow later locating.

7 Manholes

NOTE Manhole type and material shall be selected for groundwater, hydrogen sulfide exposure, and traffic loading. (7.1)
NOTE Precast reinforced concrete manholes per ASTM C478 are the dominant and default type. Fiberglass manholes per ASTM D3753 are selected where high groundwater, corrosive soil, or sustained hydrogen sulfide (H2S) exposure would attack concrete. H2S generation is most severe downstream of force main discharges and in low-velocity reaches; in those locations a corrosion-resistant manhole or a protective lining is warranted. Traffic loading determines the barrel diameter, base thickness, and frame-and-cover load rating. (7.2)
7.2.1The manhole structure type shall be selected from the approved types below for the service condition.
Manhole structure typeselect
Precast reinforced concrete (ASTM C478)
Fiberglass-reinforced polyester (ASTM D3753)
Polymer concrete
7.2.2Precast concrete manhole sections shall conform to ASTM C478, with the barrel, cone, base, and grade rings designed for the imposed earth and surface loads.
7.2.3The standard manhole inside diameter shall be 48 in. for mains up to 15 in.; a 60 in. inside diameter shall be used for larger mains, deep structures, or where multiple inflows require working room.
Manhole inside diameterselect
48
60
72
7.2.4A manhole shall be provided at every change in pipe size, slope, alignment, or material, at every junction of two or more sewers, and at the upstream end of each main run.

7.3 Joints and pipe connections

NOTE Joints between precast manhole sections shall be sealed with a rubber gasket conforming to ASTM C443 or a preformed flexible butyl sealant conforming to ASTM C990. (7.3.1)
NOTE Both jointing methods are accepted; the choice depends on the manufacturer's section design and the groundwater condition. The joint must remain watertight under external hydrostatic head, which is the I/I path most often overlooked because it is below grade and invisible after backfill. (7.3.2)
7.3.3Each pipe penetration through a manhole wall shall be made with a resilient (flexible boot) connector conforming to ASTM C923; mortared-only penetrations are prohibited.
7.3.4The resilient connector shall be cast into the precast wall or installed in a cored opening, and shall accommodate differential settlement between the pipe and the structure without leaking.
Manhole pipe-penetration connectorselect
Cast-in resilient connector (ASTM C923)
Cored-and-installed resilient connector (ASTM C923)
7.3.5The manhole invert channel shall be formed or shaped to provide a smooth hydraulic flow path matching the pipe inverts, with shelves (benches) sloped to drain toward the channel.

7.4 Frame, cover, and grade adjustment

NOTE The manhole frame and cover shall be gray iron castings conforming to ASTM A48, Class 35B minimum, with a load rating selected for the location. (7.4.1)
NOTE A manhole in or near a trafficked area requires an AASHTO H-20 (HS-20) traffic-rated frame and cover; a non-traffic location in landscaping may use a lighter rating. Covers in flood-prone or high-I/I areas should be solid (no vent holes) and may be gasketed or locking. Specify the rating, lid type, and any locking or insert requirement so the contractor orders the correct casting. (7.4.2)
7.4.3The frame and cover load rating shall be selected for the location from the options below.
Frame and cover load ratingselect
AASHTO H-20 traffic-rated
Non-traffic (landscaped) rated
7.4.4The cover lid configuration shall be selected for the location; solid covers shall be used where inflow through vent holes must be prevented.
Cover lid configurationselect
Solid, non-vented
Vented (pickhole only)
Solid with gasket
Solid locking
7.4.5The frame shall be set to match finish grade using poured-in-place concrete grade rings or precast adjustment rings; the use of excessive stacked shim rings to make up large elevation differences is prohibited.
7.4.6The frame-to-structure and frame-to-grade-ring joints shall be sealed against inflow with butyl sealant or an approved external chimney seal.
7.4.7Manhole steps, where provided, shall be polypropylene-encased steel or aluminum, corrosion-resistant, and spaced to comply with OSHA confined-space access requirements.

8 Lift Stations

NOTE A lift (pump) station shall be provided only where gravity flow to the public main or on-site treatment is not feasible at the design depth and slope. (8.1)
NOTE A lift station introduces ongoing energy cost, mechanical maintenance, and a wet-weather failure mode that gravity sewers do not have, so it is an option of last resort. Confirm during early design whether the site can reach the public main by gravity at acceptable cover and slope; if it cannot, the lift station must be sized and located before the collection-system layout is finalized, because the station footprint, electrical service, and force main routing constrain the whole site. The decision threshold is governed by the tap invert elevation, site grades, and the resulting required excavation depth. (8.2)
8.2.1The need for a lift station shall be established from the tap invert, site grades, and design flow before the gravity collection layout is finalized.
8.2.2Where a lift station is required, the station configuration shall be selected from the approved configurations below.
Lift station configurationselect
Submersible duplex (two pumps, prepackaged)
Submersible triplex (three pumps)
Submersible duplex with standby generator

8.3 Pumps

NOTE Lift station pumps shall be submersible non-clog centrifugal solids-handling pumps, applied and selected per ANSI/HI 1.1-1.6, in a duplex (minimum two-pump) arrangement for redundancy. (8.3.1)
NOTE A single-pump station has no redundancy: a pump failure backs up the entire tributary system. The duplex arrangement allows either pump to meet the design flow alone with the second pump as standby, alternating to equalize wear. Non-clog impellers and a minimum solids-passing sphere are required because raw sewage carries rags and solids that bind narrow passages. (8.3.2)
8.3.3Each pump shall be sized so that one pump alone meets the design peak flow with the second pump on standby, and the pumps shall alternate on successive cycles.
8.3.4Each pump shall pass a minimum spherical solid of 3 in. to handle sewage solids without clogging.
Minimum solids-passing sphere diameterrange
in
2.54
3
8.3.5Pump selection shall be documented with a certified manufacturer performance curve showing the duty point on the system head curve, with the operating point within the manufacturer's preferred operating region.
Pump duty design total dynamic headrange
ft
10120
Per drawings — lift station hydraulic profile (deferred by default)

8.4 Wet well

NOTE The wet well material and effective volume shall be selected to limit pump cycling and to provide emergency storage. (8.4.1)
NOTE Wet well storage volume sets the pump cycle time. Too small a volume causes the pump to start and stop rapidly; frequent starts overheat the motor, accelerate wear, and void the pump warranty. The active volume between the pump-on and pump-off levels must be large enough to hold cycle time within the motor manufacturer's maximum starts-per-hour limit at the design flow. The wet well must also provide reserve storage above the high-level alarm to ride through a short power or pump outage without an overflow. (8.4.2)
8.4.3The wet well shall be sized so that the pump cycle does not exceed the motor manufacturer's maximum permitted starts per hour at any flow condition.
Maximum pump starts per hour (motor limit)range
starts/h
615
10
8.4.4The wet well material shall be selected for groundwater and corrosion conditions from the approved options below.
Wet well materialselect
Precast concrete (lined for corrosion service)
Fiberglass-reinforced polyester (ASTM D3753)
Polyethylene
8.4.5The wet well shall provide emergency storage above the high-water alarm sufficient to ride through a defined outage at design flow without surcharge or overflow.
8.4.6The wet well access hatch shall be an aluminum, traffic- or pedestrian-rated, lockable hatch sized for pump removal and confined-space rescue, located clear of vehicle paths lift station site plan.

8.5 Controls and electrical

NOTE The hazardous-area classification of the wet well and valve vault shall be determined per NFPA 820, and the electrical design shall match that classification. (8.5.1)
NOTE NFPA 820 classifies the wet well interior and connected spaces as hazardous (typically Class I, Division 1 inside the wet well and Division 2 in the connected valve vault) because of the potential for explosive sewer gas. That classification drives the motor and cable ratings, the conduit sealing fittings, and the ventilation design. Omitting the classification from the documents is a frequent cause of electrical-subcontractor RFIs and rework, because the installer cannot select compliant equipment without it. (8.5.2)
8.5.3The level-control system shall provide pump-off, lead-on, lag-on, and high-water alarm setpoints, with redundant high-level detection independent of the primary level sensor.
8.5.4The high-water condition shall trigger both a local audible/visual alarm and a remote alarm (autodialer or SCADA) to notify operations staff.
8.5.5The control panel and electrical enclosures shall carry a NEMA rating suited to their location and the NFPA 820 area classification.
Control panel enclosure NEMA ratingselect
NEMA 4X (outdoor, corrosion-resistant)
NEMA 3R (outdoor, weatherproof)
NEMA 7 (hazardous, Class I Division 1)
8.5.6Standby power provisions shall be provided for the station, by a permanent standby generator, a portable-generator quick-connect receptacle, or an equivalent approved means.
Standby power provisionselect
Permanent standby generator with automatic transfer switch
Portable generator quick-connect receptacle (manual transfer)
No standby power (gravity emergency storage only)

8.6 Valve vault and force main

NOTE A valve vault separate from the wet well shall house the discharge check valves, isolation valves, and force main connection. (8.6.1)
NOTE Keeping valves out of the wet well keeps maintenance staff out of the hazardous, gas-laden wet well for routine valve work and keeps the valves above the sewage. Each pump discharge needs a check valve to prevent backflow when it stops and an isolation valve to allow servicing one pump while the other runs. (8.6.2)
8.6.3Each pump discharge shall be fitted with a check valve and a downstream isolation valve, accessible from the valve vault without entering the wet well.
8.6.4The force main material shall be selected for the operating pressure, soil, and installation method from the approved options below.
Force main pipe materialselect
HDPE (ASTM D3035, SDR 11)
PVC pressure pipe (AWWA C900)
Ductile iron (AWWA C151, restrained joint)
8.6.5The force main shall be sized to maintain a cleansing velocity between 2 and 8 ft/s at the pump operating flow, avoiding both solids deposition at low velocity and excessive head loss at high velocity.
Force main design velocity at pump flowrange
ft/s
28
5
8.6.6Air/vacuum release valves shall be provided at each high point of the force main to release accumulated air and admit air on draindown; the location and size of each valve shall be shown on the drawings force main profile.
8.6.7The force main connection at its gravity discharge shall enter a manhole at or above the flow line and shall be detailed to dissipate energy and minimize turbulence and odor release.

8.7 Odor control

NOTE Odor control shall be evaluated for any lift station or force main discharge in proximity to occupied buildings, building entries, or parking areas. (8.7.1)
NOTE Hydrogen sulfide released at the wet well vent or at the force main discharge manhole produces odor complaints and corrosion. A station that vents next to a building entry or a parking area is a post-occupancy liability. Passive venting (a carbon-media canister or a tall vent stack) suffices for low-strength or remote stations; an active carbon or chemical scrubber may be warranted where the station is close to occupied space or the wastewater is septic. (8.7.2)
8.7.3The odor control method shall be selected based on the station's proximity to occupied space and the expected hydrogen sulfide load.
Odor control methodselect
Passive vent stack (no media)
Passive carbon-media canister
Active carbon or chemical scrubber

9 Testing

NOTE All gravity sewer testing shall be completed and accepted before final backfill compaction and surface restoration over the tested segment. (9.1)
NOTE Test sequencing is a requirement, not a convenience. A low-pressure air test or deflection test run after the trench is fully backfilled and paved makes any failure expensive to find and destructive to repair. The acceptance tests must be scheduled into the construction sequence so they occur on the open or lightly-backfilled trench, with the spec stating the order explicitly so the test is not skipped. (9.2)
9.2.1Gravity sewer mains shall be tested for leakage by low-pressure air test or hydrostatic exfiltration test, with acceptance criteria stated as allowable leakage per inch of pipe diameter per mile per day.
Gravity sewer leakage test methodselect
Low-pressure air test
Hydrostatic exfiltration test
Hydrostatic infiltration test
Maximum allowable leakagerange
gal/(in-dia mile day)
50200
100
9.2.2Flexible (PVC and HDPE) gravity pipe shall be tested for vertical deflection by a mandrel (go/no-go) test after backfill, with deflection not exceeding 5 percent of the base inside diameter.
Maximum allowable pipe deflectionrange
percent
57.5
5
9.2.3The mandrel deflection test shall be performed no sooner than 30 days after final backfill to capture the deflection that develops after the trench settles.
9.2.4Each manhole shall be tested for watertightness by vacuum test or exfiltration test where required by the authority having jurisdiction.
9.2.5The force main shall be hydrostatically pressure-tested to a test pressure above the maximum operating pressure, with allowable makeup leakage per the pressure-pipe standard.
Force main hydrostatic test pressurerange
psi
50150
Per drawings — force main design pressure (deferred by default)
9.2.6The lift station shall be commissioned with a drawdown test verifying each pump's pumping rate, a verification of pump alternation, and a functional test of every level setpoint and alarm.

10 Installation

NOTE Pipe shall be installed to line and grade on a continuously supported, properly bedded trench bottom, with bell ends laid facing upstream. (10.1)
NOTE Sewer pipe is laid uphill against the flow with the bell facing upstream so the spigot of each joint points downstream into the bell, which keeps the joint from being pried open by flow and bedding movement. Line and grade are non-negotiable on a gravity sewer; small grade errors that create bellies (low spots) trap solids and defeat the self-cleansing design. (10.2)
10.2.1Pipe shall be laid to the line and grade shown, with no reverse grade or sag (belly) that would pond flow profile sheets.
10.2.2Each joint shall be made up clean and fully homed per the manufacturer's instructions, with gaskets lubricated only with the manufacturer-approved lubricant.
10.2.3Open trench ends shall be plugged at the end of each work period to prevent entry of debris, animals, and water.
10.2.4Connections to existing live sewers shall be coordinated with the utility owner and shall include flow control (plugging or bypass pumping) to prevent spills.
10.2.5Excavation, trench safety, dewatering, and shoring shall comply with Earthwork and applicable OSHA excavation requirements.

11 Delivery, Storage, and Handling

NOTE Plastic pipe shall be protected from prolonged ultraviolet exposure and supported to prevent deformation during storage. (11.1)
NOTE PVC and HDPE pipe degrade and lose impact strength under sustained sunlight, and they take a permanent set if stored unsupported in tall stacks or over point supports. Gaskets and elastomeric connectors must be kept clean and out of the sun. Castings, pumps, and control panels must be kept dry and undamaged until installation. (11.2)
11.2.1Pipe and fittings shall be stored on level dunnage, stacked no higher than the manufacturer's limit, and shielded from prolonged sunlight.
11.2.2Gaskets, boots, and resilient connectors shall be stored clean, cool, and out of direct sunlight, and shall be inspected for damage before use.
11.2.3Pumps, control panels, and precast structures shall be handled with the manufacturer's lifting points and protected from impact, moisture, and contamination until installed.

12 Warranty

NOTE The Contractor shall warrant the installed sanitary sewer system against defects in materials and workmanship for the project warranty period. (12.1)
12.1.1The Contractor shall warrant the complete installed system, including pipe, structures, and the lift station, against defects in materials and workmanship for a minimum of one year from final acceptance.
12.1.2Lift station pumps and controls shall additionally carry the manufacturer's standard warranty, which shall be transferred to the Owner at acceptance.
12.1.3Any segment failing a leakage, deflection, or pressure test within the warranty period shall be uncovered, repaired or replaced, and re-tested at the Contractor's expense.

13 Spare Parts

NOTE The Contractor shall furnish the spare parts and special tools needed to keep the lift station in service after acceptance. (13.1)
13.1.1The Contractor shall furnish one spare submersible pump of each type and size installed, or the spare-pump quantity required by the AHJ, for the lift station.
13.1.3The Contractor shall furnish the special tools, lifting chains, and guide-rail components required to remove and reinstall a submersible pump without entering the wet well.
Spare parts furnished at acceptancecheckbox
One spare submersible pump of each type and size
Spare check valve flappers and seals
Spare control relays and level sensor
Pump removal tools, lifting chain, and guide-rail components

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Sanitary Sewer Systems (Site)." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/sanitary-sewer-systems — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.