title: Shop Painting and Galvanizing of Steel
…25 unchanged lines
## The three families are distinguished as follows, and the choice among them is the central decision of this standard: {note}
−- **Shop prime painting** -- a thin film of primer (zinc-rich, alkyd, epoxy, or urethane) applied over a prepared steel surface, providing barrier and/or sacrificial protection for interior or protected exposures, or a base for later field topcoats.
−- **Hot-dip (batch) galvanizing** -- immersion of the fabricated assembly in molten zinc per ASTM A123, producing a metallurgically bonded zinc coating that provides both barrier and cathodic protection for exterior and corrosive exposures.
−- **Duplex system** -- a paint or powder topcoat applied over a hot-dip galvanized base, used where color, appearance, or aggressive exposure demands more than galvanizing alone.
+- **Shop prime painting** — a thin film of primer (zinc-rich, alkyd, epoxy, or urethane) applied over a prepared steel surface, providing barrier and/or sacrificial protection for interior or protected exposures, or a base for later field topcoats.
+- **Hot-dip (batch) galvanizing** — immersion of the fabricated assembly in molten zinc per ASTM A123, producing a metallurgically bonded zinc coating that provides both barrier and cathodic protection for exterior and corrosive exposures.
+- **Duplex system** — a paint or powder topcoat applied over a hot-dip galvanized base, used where color, appearance, or aggressive exposure demands more than galvanizing alone.
## This standard applies to building structural frames, open-web steel joists, miscellaneous metals (stairs, railings, lintels, embeds), ornamental ironwork, and similar steel assemblies that receive their primary corrosion protection in a fabrication shop. {note}
…3 unchanged lines
## This standard governs only the corrosion-protection coating. The base steel, its fabrication, and its erection are governed elsewhere: {note}
−- Structural frame erection, connections, camber, and AISC tolerances -- [[sync/structural-steel-framing]].
−- Miscellaneous-metals member selection and fabrication tolerances -- [[sync/miscellaneous-metals]] and [[sync/metal-fabrications]].
−- Welding processes, weld inspection, and NDT -- [[sync/welding-requirements]].
−- Field-applied architectural and high-performance topcoats (final colors, gloss, specialty finishes) -- [[sync/high-performance-coatings]].
−- Abatement of existing lead-based paint before recoating -- [[sync/hazardous-material-abatement]].
+- Structural frame erection, connections, camber, and AISC tolerances — [[sync/structural-steel-framing]].
+- Miscellaneous-metals member selection and fabrication tolerances — [[sync/miscellaneous-metals]] and [[sync/metal-fabrications]].
+- Welding processes, weld inspection, and NDT — [[sync/welding-requirements]].
+- Field-applied architectural and high-performance topcoats (final colors, gloss, specialty finishes) — [[sync/high-performance-coatings]].
+- Abatement of existing lead-based paint before recoating — [[sync/hazardous-material-abatement]].
## The following are outside the scope of this standard. {note}
…136 unchanged lines
## The default systems for typical commercial construction are SSPC-SP 6 commercial blast plus an alkyd or epoxy primer at 1.5 mils DFT for interior framing, and ASTM A123 hot-dip galvanizing for exterior miscellaneous metals (railings, lintels, embeds). The selections below depart from those defaults only where exposure or appearance demands it. {note}
+## The corrosion-protection system shall be specified for each steel scope, departing from the default interior and exterior systems only where exposure or appearance demands it.
+
```datasheet
label: Corrosion-protection system
…7 unchanged lines
```
+## The exposure category shall be classified for each steel scope, and it shall govern the corrosion-protection system selected for that scope.
+
```datasheet
label: Exposure category
…11 unchanged lines
## Inorganic zinc-rich primers (silicate binder) provide the strongest bare-steel cathodic protection and qualify many slip-critical connections, but require near-white blast preparation and accept only epoxy or urethane topcoats. Organic zinc-rich primers (epoxy binder) trade a small amount of cathodic performance for easier topcoat compatibility. Alkyd red-oxide primers are the economical choice for interior, protected steel. Epoxy and urethane primers serve intermediate barrier roles where zinc is not required. {note}
+## The shop primer generic type shall be specified, matched to the cathodic protection, surface preparation, and topcoat compatibility required for the application.
+
```datasheet
label: Shop primer generic type
…8 unchanged lines
```
−## Alkyd topcoats shall not be applied over inorganic zinc-rich primers. {note}
+## Alkyd topcoats shall not be applied over inorganic zinc-rich primers.
## Alkyd films saponify over the alkaline zinc-silicate surface, causing adhesion failure; only epoxy or urethane topcoats are compatible over zinc-rich primers. Because this is a boundary on what is permitted rather than an action, it is stated here as rationale; the corresponding obligation appears as a clause in the Topcoat Systems section. {note}
…87 unchanged lines
```
−## Surfaces left uncoated in the shop must be identified so the applicator does not over-paint connection and weld areas. {note}
+## Surfaces left uncoated in the shop must be identified so the applicator does not over-paint connection and weld areas.
## Standard practice leaves slip-critical faying surfaces, bolt holes, and a band around field welds bare; the specification must state this explicitly to avoid both bare steel where coating is required and over-painting where it is not, each of which generates RFIs. {note}
…145 unchanged lines
## Galvanized surfaces shall be prepared in accordance with ASTM D6386 before painting, or ASTM D7803 before powder coating. {note}
−## Painting directly over fresh galvanizing -- particularly over wet-storage stain (white rust) -- causes rapid delamination. ASTM D6386 requires sweep blasting, weathering, or chemical passivation to provide a sound surface for the topcoat; omitting this preparation is the most common cause of duplex-system failure. {note}
+## Painting directly over fresh galvanizing — particularly over wet-storage stain (white rust) — causes rapid delamination. ASTM D6386 requires sweep blasting, weathering, or chemical passivation to provide a sound surface for the topcoat; omitting this preparation is the most common cause of duplex-system failure. {note}
### Galvanized surfaces to be painted shall be prepared in accordance with ASTM D6386 by sweep blast, weathering, or chemical treatment.
…72 unchanged lines
## Damaged galvanizing, cut edges, copes, and field welds shall be repaired in accordance with ASTM A780. {note}
−## Repair of bare areas is frequently omitted from specifications, leaving cut edges and field-weld zones unprotected after erection. ASTM A780 defines acceptable methods -- zinc-rich paint, zinc solder (zinc-based alloy), or thermal-spray zinc -- and the repaired film thickness must at least match the parent coating. {note}
+## Repair of bare areas is frequently omitted from specifications, leaving cut edges and field-weld zones unprotected after erection. ASTM A780 defines acceptable methods — zinc-rich paint, zinc solder (zinc-based alloy), or thermal-spray zinc — and the repaired film thickness must at least match the parent coating. {note}
### Bare areas not exceeding 1 in.² (25 cm²) shall be repaired with zinc-rich paint per ASTM A780 Method A to a dry film thickness of not less than 3.0 mils.
…52 unchanged lines
# Delivery, Storage, and Handling {toc}
−## Coated and galvanized steel shall be handled and stored to prevent coating damage and wet-storage staining. {note}
+## Coated and galvanized steel shall be handled and stored to prevent coating damage and wet-storage staining.
### Coated members shall be handled with padded slings or other non-marring devices to avoid abrading the coating.
…20 unchanged lines
# Warranty {toc}
−## The Contractor shall warrant the shop-applied coating systems against defective materials and workmanship for the specified period. {note}
+## The Contractor shall warrant the shop-applied coating systems against defective materials and workmanship for the specified period.
### The Contractor shall warrant shop coatings and galvanizing against peeling, blistering, and corrosion attributable to defective materials or workmanship for the specified warranty period from the date of Substantial Completion.
…10 unchanged lines
default: 1 year
```