## Where referenced standards conflict, the more stringent requirement shall govern unless the Architect or Engineer of Record directs otherwise in writing.
## The applicable model code edition is jurisdiction-specific; the Contractor shall confirm the adopted editions of the building code, life-safety code, and accessibility standard with the AHJ before procurement. {note}
+## The applicable model code edition is jurisdiction-specific; the Contractor shall confirm the adopted editions of the building code, life-safety code, and accessibility standard with the AHJ before procurement.
| Standard | Title |
103 unchanged lines
## Signs shall be suitable for the service environment of their installed location, including interior conditioned, wet, vandal-prone, and covered-exterior conditions as applicable.
## Signs in wet or washdown locations — locker rooms, pool enclosures, covered exterior walks — shall use corrosion-resistant substrates and fasteners and shall carry a wet-location rating where the product type requires one. {note}
## Photoluminescent exit signs depend on ambient light to charge; they shall be installed only where the ambient illumination at the sign face is maintained at a minimum of 1 fc during all hours of occupancy.
## A photoluminescent sign in a dim, windowless, or intermittently lit corridor will not charge to its rated luminance and will fail to perform in a power loss; ambient light verification is a precondition of using this product type, not an afterthought. {note}
```datasheet
label: Service Environment
7 unchanged lines
```
+## Signs in wet or washdown locations — locker rooms, pool enclosures, covered exterior walks — shall use corrosion-resistant substrates and fasteners and shall carry a wet-location rating where the product type requires one.
+
+## Photoluminescent exit signs depend on ambient light to charge; they shall be installed only where the ambient illumination at the sign face is maintained at a minimum of 1 fc during all hours of occupancy.
+
+## A photoluminescent sign in a dim, windowless, or intermittently lit corridor will not charge to its rated luminance and will fail to perform in a power loss; ambient light verification is a precondition of using this product type, not an afterthought. {note}
+
# Exit Signs {toc}
8 unchanged lines
## Internally illuminated exit signs shall be illuminated continuously during building occupancy and shall meet the illumination requirements of their UL 924 listing; externally illuminated signs shall be illuminated to not less than 5 fc on the sign face.
## Each illuminated exit sign shall be provided with a backup power source that maintains rated illumination for not less than 90 minutes after loss of normal power and re-energizes to full output within 10 seconds of a power failure.
## The 80% configuration for most projects is an LED internally illuminated exit sign with a red legend, dual 120/277V input, and an integral 90-minute battery; this satisfies nearly all AHJ requirements without special approval and is the default unless project conditions dictate otherwise. {note}
## For sign-face and color selection: IBC does not mandate a legend color and NFPA 101 permits both red and green, but many state amendments and local fire marshals require red — confirm the permitted color with the AHJ before procurement where green is contemplated; double-face signs are used where the sign is viewed from both directions of a corridor or is ceiling- or blade-mounted in an open path, while single-face signs are used against a wall or at a terminal door. {note}
```datasheet
label: Exit Sign Illumination Type
7 unchanged lines
```
+## Each illuminated exit sign shall be provided with a backup power source that maintains rated illumination for not less than 90 minutes after loss of normal power and re-energizes to full output within 10 seconds of a power failure.
+
+## The configuration most projects use is an LED internally illuminated exit sign with a red legend, dual 120/277V input, and an integral 90-minute battery; this satisfies nearly all AHJ requirements without special approval and is the default unless project conditions dictate otherwise. {note}
+
+## For sign-face and color selection: IBC does not mandate a legend color and NFPA 101 permits both red and green, but many state amendments and local fire marshals require red — confirm the permitted color with the AHJ before procurement where green is contemplated; double-face signs are used where the sign is viewed from both directions of a corridor or is ceiling- or blade-mounted in an open path, while single-face signs are used against a wall or at a terminal door. {note}
+
+## The exit sign legend color shall be specified, confirmed with the authority having jurisdiction where a green legend is contemplated.
+
```datasheet
label: Exit Sign Legend Color
5 unchanged lines
```
+## The exit sign face configuration shall be specified based on whether the sign is viewed from one or both directions of travel.
+
```datasheet
label: Exit Sign Face Configuration
5 unchanged lines
```
+## The exit sign input voltage shall be specified to match the building's available power supply.
+
```datasheet
label: Exit Sign Input Voltage
16 unchanged lines
```
+## The exit sign mounting method shall be specified based on the sign's location and orientation within the path of egress.
+
```datasheet
label: Exit Sign Mounting Method
23 unchanged lines
### The "NO EXIT" sign shall have the word "NO" in letters not less than 2 in high and the word "EXIT" in letters not less than 1 in high, with the word "EXIT" below the word "NO".
### No-Exit signs at storage, mechanical, and electrical room doors adjacent to corridors are frequently omitted and are a common source of inspection non-compliance; every door that could be confused for an exit shall be evaluated against this requirement. {note}
+### No-Exit signs at storage, mechanical, and electrical room doors adjacent to corridors are frequently omitted and are a common source of inspection non-compliance; every door that could be confused for an exit shall be evaluated against this requirement.
```datasheet
12 unchanged lines
## Directional indicators shall point toward the nearest exit consistent with the approved egress plan.
## The directional indicator type shall be selected for legibility at the required viewing distance; chevron and arrow indicators are standard, and a running-man pictogram may be added as a supplement where the project's signage palette uses it. {note}
+## The directional indicator type shall be selected for legibility at the required viewing distance; chevron and arrow indicators are standard, and a running-man pictogram may be added as a supplement where the project's signage palette uses it.
```datasheet
31 unchanged lines
## The 80% process for tactile signs is photopolymer on an acrylic face, which yields the most accurate Braille, has the widest vendor base, and is cost-effective on projects with 50 or more signs; this is the default unless a more durable substrate is required. {note}
+## The tactile sign substrate and fabrication process shall be specified, considering sign quantity and any durability requirements beyond the default.
+
```datasheet
label: Tactile Sign Substrate / Process
25 unchanged lines
setpoints:
- 70
+ - 100
```
6 unchanged lines
unit: in AFF
setpoints:
+ - 48
- 60
```
3 unchanged lines
### Where a sign carries a pictogram — accessible symbol, restroom, stairway — the pictogram shall be located in a field above the tactile characters, and the pictogram field shall not contain raised characters or Braille.
### The pictogram field shall be sized in accordance with ICC A117.1 so the symbol is legible at the approach distance.
### Tactile signs with pictogram fields use a taller plate, commonly a 6 in x 9 in or 4 in x 8 in format with the pictogram panel above the text and Braille field. {note}
```datasheet
label: Tactile Sign Pictogram
9 unchanged lines
```
+### The pictogram field shall be sized in accordance with ICC A117.1 so the symbol is legible at the approach distance.
+
+### Tactile signs with pictogram fields use a taller plate, commonly a 6 in x 9 in or 4 in x 8 in format with the pictogram panel above the text and Braille field. {note}
+
# Stairway Identification Signs {toc}
33 unchanged lines
## At each area of refuge equipped with two-way communication, instructions for summoning assistance via the two-way communication system, and written identification of the location, shall be posted adjacent to the two-way communication device.
## Doorways and exit access leading to an area of refuge shall be provided with directional signage indicating the location of the area of refuge.
## Areas of refuge in non-sprinklered or partially sprinklered multi-story buildings require both two-way communication and signage at each location; on partial-sprinkler alteration projects this pairing is frequently missed and is a common non-compliance finding. {note}
## The area of refuge instruction sign may be a single combined sign-and-speaker unit, or a separate instruction sign referencing a remote two-way communication device, depending on the communication system provided. {note}
```datasheet
label: Area of Refuge Sign Configuration
6 unchanged lines
```
+## Doorways and exit access leading to an area of refuge shall be provided with directional signage indicating the location of the area of refuge.
+
+## Areas of refuge in non-sprinklered or partially sprinklered multi-story buildings require both two-way communication and signage at each location; on partial-sprinkler alteration projects this pairing is frequently missed and is a common non-compliance finding. {note}
+
+## The area of refuge instruction sign may be a single combined sign-and-speaker unit, or a separate instruction sign referencing a remote two-way communication device, depending on the communication system provided. {note}
+
+## The area of refuge sign mounting method shall be specified based on the wall or surface condition at its location.
+
```datasheet
label: Area of Refuge Sign Mounting
90 unchanged lines
## Tactile signs shall be installed at the heights and locations required by the ADA Standards and shall be located within the door-swing clearance required so the sign is approachable.
## Tactile sign installation shall be coordinated with the door hardware and door swing schedule so the latch-side mounting location is not obstructed by the door in its open position; this coordination is essential and is referenced to [[sync/door-hardware]]. {note}
+## Tactile sign installation shall be coordinated with the door hardware and door swing schedule so the latch-side mounting location is not obstructed by the door in its open position; this coordination is essential and is referenced to [[sync/door-hardware]].
## Exact sign locations, exit locations, and egress directions shall follow the approved egress plan and life-safety drawings [[drawing: egress plan and sign locations]].
## Where the wall assembly receiving a sign is fire-rated, fasteners and any penetrations shall not compromise the rating; coordinate with [[sync/fire-rated-wall-and-floor-assemblies]] for through-penetration conditions. {note}
+## Where the wall assembly receiving a sign is fire-rated, fasteners and any penetrations shall not compromise the rating; coordinate with [[sync/fire-rated-wall-and-floor-assemblies]] for through-penetration conditions.
## Surface preparation and fastener selection for each substrate condition shall follow the manufacturer's printed instructions.
21 unchanged lines
## The manufacturer shall warrant tactile and non-illuminated signs against delamination, fading, and Braille or character separation for the manufacturer's standard warranty period from the date of Substantial Completion.
## Warranty terms for batteries are commonly shorter than for the sign body; the battery warranty period and replacement interval shall be documented in the closeout O&M data so the Owner can plan replacement. {note}
+## Warranty terms for batteries are commonly shorter than for the sign body; the battery warranty period and replacement interval shall be documented in the closeout O&M data so the Owner can plan replacement.
```datasheet
23 unchanged lines
## The Contractor shall furnish to the Owner spare replacement batteries for illuminated exit signs in the quantity scheduled below, of the same type as installed.
## The Contractor shall furnish to the Owner spare tactile signs for the most commonly repeated room types so field damage can be replaced without a new procurement lead time.
## Stocking a small quantity of spare batteries and common tactile signs lets the Owner restore code compliance immediately after damage or battery failure, rather than waiting weeks for replacements; this is inexpensive insurance against an out-of-compliance condition. {note}
```datasheet
label: Spare Exit Sign Batteries Furnished
7 unchanged lines
```
+## The Contractor shall furnish to the Owner spare tactile signs for the most commonly repeated room types so field damage can be replaced without a new procurement lead time.
+
```datasheet
label: Spare Tactile Signs Furnished
6 unchanged lines
- 3
```
+
+## Stocking a small quantity of spare batteries and common tactile signs lets the Owner restore code compliance immediately after damage or battery failure, rather than waiting weeks for replacements; this is inexpensive insurance against an out-of-compliance condition. {note}