title: Steam and Condensate Piping
…151 unchanged lines
## Examination {toc}
−### Welds shall be examined to the extent and by the methods required by the governing code for the pressure class. {note}
+### Welds shall be examined to the extent and by the methods required by the governing code for the pressure class.
### Welds on systems governed by ASME B31.1 shall be visually examined, with radiographic or other volumetric examination performed to the percentage required by B31.1 for the design conditions.
…53 unchanged lines
## Slope {toc}
−### Steam mains and condensate return lines must drain by gravity to their drip and collection points; insufficient slope leaves condensate standing in the main, which is then carried into the pipe as a slug on the next pressure change. {note}
+### Steam mains and condensate return lines must drain by gravity to their drip and collection points; insufficient slope leaves condensate standing in the main, which is then carried into the pipe as a slug on the next pressure change.
### Steam supply mains shall slope a minimum of 1/4 in. per 10 ft (1:480) in the direction of steam flow.
…38 unchanged lines
## Pipe Schedule {toc}
−### The schedule must be matched to the pressure class and verified against the code pressure-design rules; the defaults below are the 80% case and do not relieve the engineer of the wall-thickness calculation for high-pressure service. {note}
+### The schedule must be matched to the pressure class and verified against the code pressure-design rules; the defaults below cover ordinary service and do not relieve the engineer of the wall-thickness calculation for high-pressure service.
### Low-pressure steam piping 2 in. and smaller shall be Schedule 40, joined by thread or flange.
…52 unchanged lines
## Flanges {toc}
−### Flange class must be rated for both the design pressure and the design temperature; carbon-steel ratings derate with temperature, so a flange that passes a pressure check at ambient may be under-rated at the operating temperature. {note}
+### Flange class must be rated for both the design pressure and the design temperature; carbon-steel ratings derate with temperature, so a flange that passes a pressure check at ambient may be under-rated at the operating temperature.
### Flanges shall conform to ASME B16.5 and shall be rated for the design pressure and temperature of the connected service.
…109 unchanged lines
## Condensate Receiver and Pump Set {toc}
−### A duplex pump set with an alternator keeps condensate moving when one pump fails and is standard for any return that cannot tolerate an outage; the receiver volume must buffer the condensate load between pump cycles. {note}
+### A duplex pump set with an alternator keeps condensate moving when one pump fails and is standard for any return that cannot tolerate an outage; the receiver volume must buffer the condensate load between pump cycles.
### The condensate pump set shall be duplex.
…108 unchanged lines
## Isolation Valves {toc}
−### Isolation valves must carry the pressure-temperature rating of the service, which for steam means a B16.34 rating verified at the design temperature, not just the design pressure. {note}
+### Isolation valves must carry the pressure-temperature rating of the service, which for steam means a B16.34 rating verified at the design temperature, not just the design pressure.
### Isolation valves shall conform to ASME B16.34 and shall be rated for the design pressure and temperature of the service.
…33 unchanged lines
# Expansion Compensation {toc}
−## General {toc}
+## Steam pipe grows roughly 3/4 in. per 100 ft at 100 psig; unrelieved thermal growth cracks flanges, shears bolts, and pulls supports loose, so every run must be analyzed and compensated. {note}
−### Steam pipe grows roughly 3/4 in. per 100 ft at 100 psig; unrelieved thermal growth cracks flanges, shears bolts, and pulls supports loose, so every run must be analyzed and compensated. {note}
+## Thermal expansion of each pipe run shall be calculated for the temperature change from installation to operating temperature.
−### Thermal expansion of each pipe run shall be calculated for the temperature change from installation to operating temperature.
+## Expansion compensation shall be provided by expansion loops, bellows expansion joints, or slip-type expansion joints, with anchors and guides arranged to direct the movement.
−### Expansion compensation shall be provided by expansion loops, bellows expansion joints, or slip-type expansion joints, with anchors and guides arranged to direct the movement.
+## Expansion loops shall be the preferred method of compensation where space permits, as they require no moving seals.
−### Expansion loops shall be the preferred method of compensation where space permits, as they require no moving seals.
−
```datasheet
label: Expansion Compensation Method
…24 unchanged lines
# Insulation Requirements {toc}
−## General {toc}
+## This standard specifies the insulation requirements by service - operating temperature, minimum thickness, and jacket - and delegates material specification and field application detail to [[sync/mechanical-insulation]]. {note}
−### This standard specifies the insulation requirements by service - operating temperature, minimum thickness, and jacket - and delegates material specification and field application detail to [[sync/mechanical-insulation]]. {note}
+## Steam and condensate piping shall be insulated to not less than the minimum thickness required by ASHRAE 90.1 Table 6.8.3-1 for the service operating temperature.
−### Steam and condensate piping shall be insulated to not less than the minimum thickness required by ASHRAE 90.1 Table 6.8.3-1 for the service operating temperature.
+## Insulation material shall be selected for the surface operating temperature of the service.
−### Insulation material shall be selected for the surface operating temperature of the service.
−
```datasheet
label: Insulation Material
…65 unchanged lines
## Underground Pre-Insulated Systems {toc}
−### A buried steam line that takes on water fails fast through corrosion of the carrier pipe; the conduit system must keep the carrier dry and be testable for leaks before backfill. {note}
+### A buried steam line that takes on water fails fast through corrosion of the carrier pipe; the conduit system must keep the carrier dry and be testable for leaks before backfill.
### The pre-insulated conduit system shall be furnished by a single manufacturer as a complete system, including straights, fittings, anchors, and field joint closures.
…66 unchanged lines
# Installation {toc}
−## General {toc}
+## Field practice on steam piping is unforgiving: a missed drip leg, a back-pitched run, or an unrelieved expansion turns into water hammer or a cracked joint in service. {note}
−### Field practice on steam piping is unforgiving: a missed drip leg, a back-pitched run, or an unrelieved expansion turns into water hammer or a cracked joint in service. {note}
+## Piping shall be installed to the slopes, drip-leg locations, anchor and guide locations, and pressure class shown on the drawings and specified herein.
−### Piping shall be installed to the slopes, drip-leg locations, anchor and guide locations, and pressure class shown on the drawings and specified herein.
+## Eccentric reducers shall be installed flat-on-bottom on horizontal steam mains so condensate is not trapped at the reduction.
−### Eccentric reducers shall be installed flat-on-bottom on horizontal steam mains so condensate is not trapped at the reduction.
+## Branch connections from a steam main shall be taken from the top of the main so condensate is not carried into the branch.
−### Branch connections from a steam main shall be taken from the top of the main so condensate is not carried into the branch.
+## Dirt pockets and drip legs shall be installed so they can be cleaned and so the trap can be removed without cutting the pipe.
−### Dirt pockets and drip legs shall be installed so they can be cleaned and so the trap can be removed without cutting the pipe.
−
## Cleaning {toc}
…18 unchanged lines
# Warranty {toc}
−## Warranty {toc}
+## The Contractor shall warrant the steam and condensate piping system against defects in materials and workmanship for a period of not less than one year from the date of substantial completion.
−### The Contractor shall warrant the steam and condensate piping system against defects in materials and workmanship for a period of not less than one year from the date of substantial completion.
+## Manufactured components, including steam traps, condensate pumps, PRV stations, and expansion joints, shall carry the manufacturer's standard warranty, which shall be transferred to the Owner.
−### Manufactured components, including steam traps, condensate pumps, PRV stations, and expansion joints, shall carry the manufacturer's standard warranty, which shall be transferred to the Owner.
+## Defects in welds, joints, or components discovered within the warranty period shall be repaired or replaced at no cost to the Owner, including restoration of insulation disturbed by the repair.
−### Defects in welds, joints, or components discovered within the warranty period shall be repaired or replaced at no cost to the Owner, including restoration of insulation disturbed by the repair.
−
# Spare Parts {toc}
−## Spare Parts {toc}
+## Steam traps and strainer screens are the routine wear items; a small on-hand stock keeps a failed trap from being left blowing steam while a replacement is procured. {note}
−### Steam traps and strainer screens are the routine wear items; a small on-hand stock keeps a failed trap from being left blowing steam while a replacement is procured. {note}
+## The Contractor shall furnish spare steam trap internals or complete spare traps for each trap type and size used, in the quantity scheduled.
−### The Contractor shall furnish spare steam trap internals or complete spare traps for each trap type and size used, in the quantity scheduled.
+## The Contractor shall furnish spare strainer screens for each strainer type and size used.
−### The Contractor shall furnish spare strainer screens for each strainer type and size used.
+## The Contractor shall furnish spare gaskets for each flange size used at removable connections.
−### The Contractor shall furnish spare gaskets for each flange size used at removable connections.
−
```datasheet
label: Spare Steam Traps Furnished (per type/size)
…5 unchanged lines
default: 1
```