Historical revision. This is editorial revision
1, kept so citations to it stay resolvable. It is not the current text
of this standard — see the current revision.
1.1This standard covers the design and construction requirements for dedicated telecommunications spaces and the interior pathway systems that connect them within a single building.
NOTETelecommunications spaces governed by this standard include the per-floor Telecommunications Room (TR), the building Equipment Room (ER), the Entrance Room or Facility (ERF), and the Main and Intermediate Cross-Connect rooms (MDF/MXC and IDF/IXC). (1.1.1)
NOTEPathway systems governed by this standard include conduit sleeves through walls and floor slabs, cable trays, ladder racks, J-hooks and cable-support hooks, surface raceways, and overhead cable-support systems located within or directly serving those spaces. (1.1.2)
NOTERoom construction elements governed by this standard include enclosure fire-resistance, finishes, backboards, lighting, doors and clearances, dedicated power, and the environmental conditioning serving the spaces. (1.1.3)
1.2Telecommunications spaces and pathways shall be designed and constructed in accordance with ANSI/TIA-569-E and its Addendum 1, the topology requirements of ANSI/TIA-568.1-D, and the applicable provisions of NFPA 70 (NEC) Articles 770 and 800.
NOTEThe following work is excluded from this standard and is governed elsewhere. (1.3)
Horizontal cabling to work-area outlets, cable termination, and labeling - see Structured CablingStructured Cabling SystemsResolves to the current edition.sync/structured-cabling.
Telecommunications bonding and grounding (TMGB, TGB, bonding conductors, busbar sizing and connection) - see Telecommunications BondingTelecommunications Bonding and GroundingResolves to the current edition.sync/telecommunications-bonding.
Cable tray installed in general building spaces outside TR/ER rooms for large cable runs - see Cable TrayCable Tray SystemsResolves to the current edition.sync/cable-tray.
Conduit and raceway systems in general electrical distribution corridors - see Raceways And ConduitRaceways and ConduitResolves to the current edition.sync/raceways-and-conduit.
Electrical switchgear rooms, main electrical distribution rooms, and MV/LV panel rooms - see Electrical RoomsElectrical RoomsResolves to the current edition.sync/electrical-rooms.
Service-entrance conductors and feeder cables entering the building from outside - see Distribution Feeder CablesService and Feeder ConductorsResolves to the current edition.sync/distribution-feeder-cables.
Outside-plant (OSP) pathways - underground ductbanks, aerial, and direct-buried runs between buildings.
Data-center build-outs with raised-floor, precision CRAC cooling, and high-density compute.
Procurement of active network equipment (switches, routers, patch panels as hardware) - covered by IT procurement specifications.
2Referenced Standards
2.1Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard
Title
ANSI/TIA-569-E (Addendum 1, 2022)
Telecommunications Pathways and Spaces
ANSI/TIA-568.1-D
Generic Telecommunications Cabling for Customer Premises
BICSI TDMM
Telecommunications Distribution Methods Manual
ANSI/NECA/BICSI 568
Standard for Installing Commercial Building Telecommunications Cabling
NFPA 70 (Article 800)
National Electrical Code - General Requirements for Communications Systems
NFPA 70 (Article 770)
National Electrical Code - Optical Fiber Cables and Raceways
NFPA 101
Life Safety Code
NFPA 13
Standard for the Installation of Sprinkler Systems
ASHRAE Thermal Guidelines for Data Processing Environments (5th Edition, 2021)
Thermal Guidelines for Data Processing Environments
IBC
International Building Code (current adopted edition)
UL 2043
Fire Test for Heat and Visible Smoke Release for Products Installed in Air-Handling Spaces
NOTETIA-568 governs cabling and TIA-569 governs pathways and spaces; the two numbers are distinct and both apply to this work. (2.3)
NOTEIEEE 569 addresses utility-substation spatial conditions and is not applicable to telecommunications spaces; it is named here only to prevent confusion with ANSI/TIA-569-E. (2.4)
3Submittals
3.1Action Submittals
3.1.1The Contractor shall submit the following action submittals for review prior to fabrication and installation:
Shop drawings showing TR/ER room layouts with rack and cabinet positions, working clearances, and backboard coverage.
Pathway plans and sections showing ladder rack, cable tray, J-hook, and conduit-sleeve routing, sizes, and support spacing.
Product data for racks, cabinets, ladder rack, cable tray, J-hooks, surface raceway, and firestop systems.
Conduit-sleeve schedule listing quantity, size, location, and firestop assembly for each TR-to-TR and floor-penetration link.
Environmental conditioning design data including cooling capacity, setpoints, and 24/7 operating provisions.
Seismic bracing and anchorage details for racks, cabinets, and overhead pathway where required by the Seismic Design Category.
Action Submittalscheckbox
☑ Room layout shop drawings
☑ Pathway plans and sections
☑ Product data (racks, pathway, firestop)
☑ Conduit-sleeve schedule
☐ Environmental conditioning design data
☐ Seismic bracing and anchorage details
3.2Closeout Submittals
3.2.1The Contractor shall submit the following closeout submittals prior to substantial completion:
Record drawings of as-built room layouts, pathway routing, and conduit-sleeve locations.
Firestop inspection records for every penetration through rated wall and floor assemblies.
Environmental conditioning startup, commissioning, and setpoint verification reports.
Operation and maintenance data for the dedicated cooling equipment.
Closeout Submittalscheckbox
☑ Record drawings
☑ Firestop inspection records
☑ Conditioning commissioning reports
☑ O&M data for cooling equipment
3.3Informational Submittals
3.3.1The Contractor shall submit the following informational submittals:
Installer qualifications demonstrating BICSI-credentialed supervision of pathway and space installation.
Manufacturer installation instructions for ladder rack, cable tray, and firestop assemblies.
Field test reports for rack anchorage and overhead-pathway support where seismic bracing is required.
Informational Submittalscheckbox
☑ Installer qualifications
☑ Manufacturer installation instructions
☐ Anchorage and bracing field test reports
4Quality Assurance
4.1The installer shall hold current BICSI credentials or provide supervision by a BICSI-credentialed Registered Communications Distribution Designer (RCDD) for the design and layout of telecommunications spaces and pathways.
4.2Pathway and space installation shall conform to ANSI/NECA/BICSI 568 installation practices, including bend-radius, support-spacing, and fill provisions.
NOTEFirestopping of penetrations through rated wall and floor assemblies is a coordination item among this standard, the fire-protection documents, and the general construction documents, and shall be resolved in shop drawings before any penetration is cut. (4.3)
4.4All firestop systems shall be installed by an applicator trained by the firestop-system manufacturer and shall match a UL-listed assembly for the rating and penetrant involved.
5Room Classification and Sizing
NOTERoom type drives size, structural load, and environmental requirements, and shall be established before any room is laid out. (5.1)
NOTEA Telecommunications Room (TR) is the per-floor space that terminates horizontal cabling and houses floor-serving equipment; an Equipment Room (ER) is the building or campus main space (MDF/MXC); an Entrance Room or Facility (ERF) is where outside-plant cabling enters the building. (5.1.1)
NOTEApplying the TR sizing table to an ER produces an undersized room; TIA-569-E provides separate tables for TR and ER, and the correct table for the room type shall be used. (5.1.2)
5.2The room type shall be classified and sized in accordance with the applicable ANSI/TIA-569-E table for that room type.
Room Typeradio
● Telecommunications Room (TR) - per-floor closet
○ Equipment Room (ER) - building/campus MDF
○ Entrance Room/Facility (ERF) - OSP entrance
○ Intermediate Cross-Connect (IDF/IXC)
5.3At least one Telecommunications Room shall be provided on each floor, and additional rooms shall be provided wherever the maximum horizontal cable run would otherwise be exceeded.
NOTEThe maximum horizontal cable distance from the TR to any work-area outlet is 90 m (295 ft) per ANSI/TIA-568.1-D; this limit, not headcount, determines the maximum floor area a single TR can serve. (5.3.1)
NOTESizing a TR from headcount without verifying the 90 m cable-run rule leaves wings of the floor out of reach and is a common cause of stranded outlets. (5.3.2)
Maximum Floor Area Served per TRrange
sq ft
500012000
Default: 10000 sq ft
5.4Telecommunications Rooms serving stacked floors shall be vertically aligned floor-to-floor so that riser sleeves pass straight through the slab.
NOTEWhere TRs are not stacked, riser sleeves must angle through the slab at steep bends that complicate the pull and can violate cable bend-radius limits. (5.4.1)
5.5The Telecommunications Room minimum floor area shall be as scheduled, not less than the area required by ANSI/TIA-569-E for the served floor area.
NOTETIA-569-E sets a 10 m² (108 sq ft) floor minimum for buildings up to 500 m² of served floor area, scaling upward; the common commercial-office case is approximately 150 sq ft for a single TR serving up to 10,000 sq ft of floor. (5.5.1)
TR Minimum Floor Arearange
sq ft
108300
Default: 150 sq ft
5.6The room minimum clear ceiling height shall be as scheduled, not less than 2,440 mm (8 ft).
NOTEA 9 ft clear height is the common design case because it allows an overhead ladder rack plus the 1 ft of clearance required above the rack tops. (5.6.1)
Minimum Clear Ceiling Heightrange
ft
812
Default: 9 ft
5.7Equipment shall be arranged for either a single-sided or double-sided layout as scheduled, with the front and rear working clearances required by NFPA 70 and NFPA 101 maintained at every rack and cabinet.
Equipment Layoutradio
● Single-sided (equipment on one wall/row)
○ Double-sided (equipment on two opposing rows)
6Room Construction and Finishes
6.1The room enclosure shall be constructed to the fire-resistance rating required by the IBC for its occupancy and location, and all penetrations of rated assemblies shall be firestopped to maintain that rating.
NOTEBackboards shall be provided on the room walls to mount terminations, cross-connect hardware, and wall-mount equipment. (6.2)
NOTEMost authorities having jurisdiction require listed fire-retardant-treated (FRT) plywood or two coats of fire-retardant paint on all six surfaces; standard untreated plywood is commonly rejected. (6.2.1)
6.3Backboards shall be 19 mm (3/4 in) A-C grade fire-retardant-treated plywood.
6.4Backboards shall be securely fastened to the wall structure with the finished (A) face exposed and shall be field-painted white or left natural as scheduled.
Backboard Materialradio
● 3/4 in A-C fire-retardant-treated plywood
○ 3/4 in plywood with two coats fire-retardant paint (six surfaces)
6.5Backboard wall coverage shall be as scheduled.
NOTEIn an ER, all non-rack walls are commonly lined floor-to-ceiling; in a TR, a single full 4 ft x 8 ft sheet on one wall is the common minimum. (6.5.1)
Backboard Coverageradio
● One full 4x8 sheet on one wall (TR minimum)
○ One full wall lined floor-to-ceiling
○ All non-rack walls lined floor-to-ceiling (ER)
6.6Room finishes shall be sealed to limit dust; floors shall receive a sealed or anti-static finish and shall not be carpeted.
6.7A bonding busbar location shall be provided on the backboard for connection of rack and pathway bonding conductors.
NOTESizing, connection, and grounding-electrode-conductor requirements for the busbar (TMGB/TGB) are owned by Telecommunications BondingTelecommunications Bonding and GroundingResolves to the current edition.sync/telecommunications-bonding; this standard requires only that the mounting location and backboard space be provided. (6.7.1)
7Pathways
NOTEInterior pathways shall be selected, sized, and supported to carry the backbone and horizontal cabling between and within telecommunications spaces without exceeding fill or bend-radius limits. (7.1)
7.2The pathway type within and between telecommunications spaces shall be as scheduled and as shown on the drawings.
Interior Pathway Typecheckbox
☑ Overhead ladder rack
☐ Cable tray
☑ Conduit sleeves (floor/wall penetrations)
☐ J-hooks / cable-support hooks
☐ Surface raceway
7.3Ladder Rack and Cable Tray
7.4Ladder rack and cable tray shall be galvanized steel or aluminum, sized for the installed cable bundle plus growth.
7.5Ladder rack and cable tray fill shall not exceed 50% of the usable cross-sectional area per ANSI/TIA-569-E.
NOTEDesigning to 40% fill rather than the 50% maximum is the common practice because it reserves capacity for moves, adds, and changes over the life of the room. (7.5.1)
Datasheet
7.6Ladder rack and cable tray width shall be as scheduled.
Ladder Rack / Cable Tray Widthselect
12
15
18
24
7.7Ladder rack and cable tray shall be supported at intervals not exceeding 1.5 m (5 ft) on center.
NOTETIA-569-E requires a maximum 5 ft support spacing; general contractors commonly assume support at the structural bay (10 ft o.c.), which generates an RFI to add intermediate hangers. (7.7.1)
Ladder Rack / Tray Support Spacingrange
ft
35
Default: 5 ft
7.8J-Hooks and Cable Support
7.9J-hooks shall support cable bundles only where ladder rack or tray is not provided, and shall not be used as the primary backbone pathway between rooms.
7.10J-hooks shall be installed at a maximum spacing of 1.5 m (5 ft) on center.
NOTEA 4 ft on-center spacing is the common installed practice because it limits cable sag between supports below the value that distorts the bundle. (7.10.1)
J-Hook Spacingrange
ft
35
Default: 4 ft
7.11J-hook depth shall be sized for the installed bundle and shall maintain the cable manufacturer's minimum bend radius at every support.
J-Hook Depthselect
1-1/2
2
3
7.12Conduit Sleeves and Floor Penetrations
NOTEConduit sleeves shall connect stacked telecommunications spaces vertically and shall pass cabling through rated wall and floor assemblies. (7.13)
7.14Conduit sleeves shall be a minimum of 4 in (102 mm) nominal inside diameter.
7.15A minimum of four conduit sleeves shall be provided per TR-to-TR riser link.
NOTEFour sleeves is the TIA-569-E minimum; six to eight are common in practice once IT counts the cable types - voice backbone, data backbone, fiber riser, access control, AV, and CATV - that must be segregated. (7.15.1)
Conduit Sleeves per Riser Linkrange
each
48
Default: 4 each
Conduit Sleeve Nominal Inside Diameterselect
4
5
6
7.16Conduit sleeves shall be located near a room corner in a grouped pattern, positioned and routed as shown on the drawings. The sleeve layout location is shown at TR riser sleeve location.
NOTEThe common arrangement is four 4 in conduits installed in a 2 x 2 pattern near the room corner so the riser stack does not encroach on rack working clearance. (7.16.1)
7.17Each conduit sleeve shall be furnished with a pull string of not less than 90 kg (200 lb) tensile rating.
NOTEMissing pull strings stop the cabling contractor at the first riser and are a routine cause of schedule delay. (7.17.1)
7.18Every conduit sleeve through a rated assembly shall be firestopped with a UL-listed firestop sleeve assembly or intumescent collar.
NOTEFire-rated floor and wall assemblies require a listed firestop at every penetration; an un-firestopped sleeve defeats the rated assembly and fails inspection. (7.18.1)
Conduit Sleeve Firestop Methodradio
● Fire-rated sleeve assembly with intumescent insert
○ Foam-and-intumescent collar (re-enterable)
7.19Surface Raceway
7.20Surface raceway shall be provided only where cabling is exposed on finished walls and no concealed pathway is available, and shall maintain the cable bend radius at all fittings.
8Racks and Cabinets
NOTERacks and cabinets shall be 19 in EIA standard, sized for the equipment served plus rack-unit growth, and arranged for the working clearances required by NFPA 70 and NFPA 101. (8.1)
8.2The rack or cabinet type shall be as scheduled.
Rack / Cabinet Typeradio
○ Wall-mount open-frame rack (2-post)
● Free-standing open-frame rack (4-post)
○ Enclosed floor-standing cabinet
○ Wall-mount enclosure/cabinet
8.3The rack or cabinet usable height (rack units) shall be as scheduled.
Rack / Cabinet Heightselect
18
42
45
48
8.4Free-standing racks and cabinets shall be anchored to the floor structure by the manufacturer's approved anchorage method.
NOTEUnanchored free-standing racks tip during front-of-rack maintenance; in seismic zones the AHJ may withhold the certificate of occupancy without approved rack anchorage details. (8.4.1)
8.5In IBC Seismic Design Category C and above, racks, cabinets, and overhead pathway shall be seismically braced and anchored in accordance with the structural drawings.
Seismic Bracing Requiredradio
● No (Seismic Design Category A or B)
○ Yes (Seismic Design Category C or above)
9Environmental and Service Conditions
NOTETelecommunications spaces shall be conditioned to maintain the temperature and humidity required for continuous operation of the installed active equipment. (9.1)
NOTEThe typical design class for a commercial TR is ASHRAE Class A1, not the wider data-center classes; TIA-569-E Addendum 1 aligns its environmental setpoints with ASHRAE's 5th edition. (9.1.1)
9.2Temperature
9.3The space shall be maintained within the ASHRAE Class A1 inlet range of 18 °C to 27 °C (64 °F to 80 °F).
9.4The cooling system shall be controlled to a design setpoint as scheduled.
Temperature Design Setpointrange
°F
6480
Default: 72 °F
9.5Humidity
9.6The space shall be maintained within a dew point of 5.5 °C to 15 °C (42 °F to 59 °F) per ANSI/TIA-569-E Addendum 1.
9.7The space relative humidity shall be maintained within the scheduled design band.
Datasheet
9.8Cooling System
NOTEA dedicated conditioning unit drives whether the room stays within range when the building system is off; this selection shall be made deliberately and not left to the building HVAC by default. (9.9)
NOTEBuilding VAV systems are commonly shut down nights and weekends; an interior TR with no exterior wall served only by building HVAC will overheat without 24/7 cooling. (9.9.1)
9.10The space conditioning source shall be as scheduled.
Conditioning Sourceradio
● Dedicated split-system HVAC (24/7 duty)
○ Building HVAC with supplemental cooling
○ Building HVAC only (perimeter room with exterior wall)
9.11A dedicated 24/7 conditioning unit shall be provided where the telecommunications space is an interior room without an exterior wall.
9.12The cooling capacity shall be sized against the actual equipment heat load and shall not be less than the scheduled rule-of-thumb allowance per rack or cabinet.
NOTEThe 500 to 750 BTU/hr per rack rule-of-thumb is a starting allowance only; the installed-equipment heat load governs and shall be verified against the IT load schedule. (9.12.1)
Cooling Allowance per Rack/Cabinetrange
BTU/hr
500750
Default: 750 BTU/hr
9.13Sprinkler Protection
NOTESprinkler coverage shall be coordinated with the fire-protection documents per NFPA 13. (9.14)
NOTESilence on sprinkler type defaults the room to wet-pipe; some owners require pre-action or dry-pipe to protect equipment from incidental discharge, and the requirement shall be stated explicitly. (9.14.1)
9.15The sprinkler system type serving the telecommunications space shall be as scheduled.
Sprinkler System Typeradio
● Wet-pipe (default building system)
○ Pre-action (double-interlock)
○ Dry-pipe
10Lighting
NOTELighting shall provide a maintained illuminance adequate for terminating and servicing cabling at the rack and backboard. (10.1)
NOTEA specification that says only "provide lighting" without a maintained illuminance commonly yields a single lamp, forcing the technician to work by flashlight. (10.1.1)
10.2Lighting shall provide a minimum maintained illuminance of 500 lux (50 fc) at a 760 mm (30 in) work plane above finished floor, measured per BICSI TDMM.
Maintained Illuminancerange
lux
500750
Default: 500 lux
10.3Luminaires shall be LED and shall be positioned to illuminate the front and rear of racks and the full backboard without being blocked by overhead pathway.
NOTETwo 2-lamp LED troffers serve a typical 10 ft x 12 ft TR; larger rooms scale the count to hold the illuminance at the work plane. (10.3.1)
11Power
NOTETelecommunications spaces shall be served by dedicated branch circuits that are not shared with building, lighting, or janitorial loads. (11.1)
NOTESharing TR outlets with janitor or building circuits causes nuisance tripping and violates NEC best practice for critical loads. (11.1.1)
11.2A minimum of two dedicated 20 A, 120 V duplex receptacles shall be provided on each wall of the room.
11.3One dedicated 20 A circuit shall be provided at each rack or cabinet position.
11.4Power receptacles and communications cabling shall maintain the separation required by NFPA 70 Article 800.
Dedicated Duplex Receptacles per Wallrange
each
24
Default: 2 each
Branch Circuit Ratingselect
20
30
12Doors and Access
12.1The room door shall provide a minimum 914 mm (36 in) clear opening and a minimum 2,032 mm (80 in) height.
12.2The door shall be solid-core or hollow-metal and shall be fire-rated to match the enclosure rating where the wall is rated.
12.3The door shall swing out into the corridor where egress and clearance permit.
NOTEAn inswing door reduces usable room area and can conflict with the front-of-rack working clearance; outswing is preferred where the corridor and egress allow it. (12.3.1)
12.4The door hardware shall be as scheduled.
Door Lock Typeradio
○ Keyed cylinder
○ Proximity-card / access-control reader
● Keyed cylinder with access-control reader
Door Swingradio
● Outswing into corridor (preferred)
○ Inswing into room
13Installation
13.1Pathways and spaces shall be installed in accordance with ANSI/NECA/BICSI 568 and the manufacturer's instructions.
13.2Cables routed in pathways that penetrate environmental-air plenums shall be plenum-rated (CMP) in accordance with NFPA 70 Article 800.24.
NOTEA standard TR is not itself a plenum, but where a pathway penetrates into a plenum space the penetrating cable must be plenum-rated. (13.2.1)
13.3Communications cabling and pathways shall maintain the separation from power circuits required by NFPA 70 Article 800.
13.4Optical fiber cables and raceways shall be installed in accordance with NFPA 70 Article 770.
13.5Bend radius shall be maintained at every support, fitting, sleeve, and termination per the cable manufacturer's instructions and ANSI/NECA/BICSI 568.
13.6All penetrations of rated wall and floor assemblies shall be firestopped to the rating of the assembly using a UL-listed system before the work is concealed.
14Testing
14.1Rack and cabinet anchorage shall be field-verified against the approved anchorage details prior to loading equipment.
14.2Where seismic bracing is required, overhead-pathway and rack bracing shall be inspected and documented before the cabling installation proceeds.
14.3Each firestopped penetration shall be inspected and recorded against the listed firestop assembly.
14.4Environmental conditioning shall be commissioned and the temperature and humidity setpoints verified under load before substantial completion.
15Delivery, Storage, and Handling
15.1Racks, cabinets, ladder rack, cable tray, and backboard materials shall be delivered in the manufacturer's original packaging and stored under cover, protected from moisture and physical damage.
15.2Fire-retardant-treated plywood shall be kept dry and shall not be installed if it shows signs of water damage or delamination.
15.3Firestop materials shall be stored within the temperature range stated by the manufacturer and shall not be used past their shelf life.
16Warranty
16.1The Contractor shall warrant pathway and space materials and installation against defects in materials and workmanship for the scheduled warranty period.
Warranty Periodrange
years
15
Default: 1 years
17Spare Parts
17.1The Contractor shall furnish spare J-hooks, mounting hardware, and firestop materials in the scheduled quantity for owner maintenance.