title: Telecommunications Rooms and Pathways
…174 unchanged lines
## At least one Telecommunications Room shall be provided on each floor, and additional rooms shall be provided wherever the maximum horizontal cable run would otherwise be exceeded.
−### The maximum horizontal cable distance from the TR to any work-area outlet is 90 m (295 ft) per ANSI/TIA-568.1-D; this limit, not headcount, determines the maximum floor area a single TR can serve. {note}
−
−### Sizing a TR from headcount without verifying the 90 m cable-run rule leaves wings of the floor out of reach and is a common cause of stranded outlets. {note}
−
```datasheet
label: Maximum Floor Area Served per TR
…6 unchanged lines
```
+### The maximum horizontal cable distance from the TR to any work-area outlet is 90 m (295 ft) per ANSI/TIA-568.1-D; this limit, not headcount, determines the maximum floor area a single TR can serve. {note}
+
+### Sizing a TR from headcount without verifying the 90 m cable-run rule leaves wings of the floor out of reach and is a common cause of stranded outlets. {note}
+
## Telecommunications Rooms serving stacked floors shall be vertically aligned floor-to-floor so that riser sleeves pass straight through the slab.
−### Where TRs are not stacked, riser sleeves must angle through the slab at steep bends that complicate the pull and can violate cable bend-radius limits. {note}
+### Where TRs are not stacked, riser sleeves must angle through the slab at steep bends that complicate the pull and can violate cable bend-radius limits.
## The Telecommunications Room minimum floor area shall be as scheduled, not less than the area required by ANSI/TIA-569-E for the served floor area.
−### TIA-569-E sets a 10 m² (108 sq ft) floor minimum for buildings up to 500 m² of served floor area, scaling upward; the common commercial-office case is approximately 150 sq ft for a single TR serving up to 10,000 sq ft of floor. {note}
−
```datasheet
label: TR Minimum Floor Area
…6 unchanged lines
```
+### TIA-569-E sets a 10 m² (108 sq ft) floor minimum for buildings up to 500 m² of served floor area, scaling upward; the common commercial-office case is approximately 150 sq ft for a single TR serving up to 10,000 sq ft of floor. {note}
+
## The room minimum clear ceiling height shall be as scheduled, not less than 2,440 mm (8 ft).
−### A 9 ft clear height is the common design case because it allows an overhead ladder rack plus the 1 ft of clearance required above the rack tops. {note}
−
```datasheet
label: Minimum Clear Ceiling Height
…6 unchanged lines
```
+### A 9 ft clear height is the common design case because it allows an overhead ladder rack plus the 1 ft of clearance required above the rack tops. {note}
+
## Equipment shall be arranged for either a single-sided or double-sided layout as scheduled, with the front and rear working clearances required by NFPA 70 and NFPA 101 maintained at every rack and cabinet.
…11 unchanged lines
## The room enclosure shall be constructed to the fire-resistance rating required by the IBC for its occupancy and location, and all penetrations of rated assemblies shall be firestopped to maintain that rating.
−## Backboards shall be provided on the room walls to mount terminations, cross-connect hardware, and wall-mount equipment. {note}
+## Backboards shall be provided on the room walls to mount terminations, cross-connect hardware, and wall-mount equipment.
### Most authorities having jurisdiction require listed fire-retardant-treated (FRT) plywood or two coats of fire-retardant paint on all six surfaces; standard untreated plywood is commonly rejected. {note}
…14 unchanged lines
## Backboard wall coverage shall be as scheduled.
−### In an ER, all non-rack walls are commonly lined floor-to-ceiling; in a TR, a single full 4 ft x 8 ft sheet on one wall is the common minimum. {note}
−
```datasheet
label: Backboard Coverage
…6 unchanged lines
```
+### In an ER, all non-rack walls are commonly lined floor-to-ceiling; in a TR, a single full 4 ft x 8 ft sheet on one wall is the common minimum. {note}
+
## Room finishes shall be sealed to limit dust; floors shall receive a sealed or anti-static finish and shall not be carpeted.
…4 unchanged lines
# Pathways {toc}
−## Interior pathways shall be selected, sized, and supported to carry the backbone and horizontal cabling between and within telecommunications spaces without exceeding fill or bend-radius limits. {note}
+## Interior pathways shall be selected, sized, and supported to carry the backbone and horizontal cabling between and within telecommunications spaces without exceeding fill or bend-radius limits.
## The pathway type within and between telecommunications spaces shall be as scheduled and as shown on the drawings.
…19 unchanged lines
## Ladder rack and cable tray fill shall not exceed 50% of the usable cross-sectional area per ANSI/TIA-569-E.
−### Designing to 40% fill rather than the 50% maximum is the common practice because it reserves capacity for moves, adds, and changes over the life of the room. {note}
−
```datasheet
label: Ladder Rack / Cable Tray Design Fill
…6 unchanged lines
```
+### Designing to 40% fill rather than the 50% maximum is the common practice because it reserves capacity for moves, adds, and changes over the life of the room. {note}
+
## Ladder rack and cable tray width shall be as scheduled.
…12 unchanged lines
## Ladder rack and cable tray shall be supported at intervals not exceeding 1.5 m (5 ft) on center.
−### TIA-569-E requires a maximum 5 ft support spacing; general contractors commonly assume support at the structural bay (10 ft o.c.), which generates an RFI to add intermediate hangers. {note}
−
```datasheet
label: Ladder Rack / Tray Support Spacing
…6 unchanged lines
```
+### TIA-569-E requires a maximum 5 ft support spacing; general contractors commonly assume support at the structural bay (10 ft o.c.), which generates an RFI to add intermediate hangers. {note}
+
## J-Hooks and Cable Support {toc}
…2 unchanged lines
## J-hooks shall be installed at a maximum spacing of 1.5 m (5 ft) on center.
−### A 4 ft on-center spacing is the common installed practice because it limits cable sag between supports below the value that distorts the bundle. {note}
−
```datasheet
label: J-Hook Spacing
…6 unchanged lines
```
+### A 4 ft on-center spacing is the common installed practice because it limits cable sag between supports below the value that distorts the bundle. {note}
+
## J-hook depth shall be sized for the installed bundle and shall maintain the cable manufacturer's minimum bend radius at every support.
…11 unchanged lines
## Conduit Sleeves and Floor Penetrations {toc}
−## Conduit sleeves shall connect stacked telecommunications spaces vertically and shall pass cabling through rated wall and floor assemblies. {note}
+## Conduit sleeves shall connect stacked telecommunications spaces vertically and shall pass cabling through rated wall and floor assemblies.
## Conduit sleeves shall be a minimum of 4 in (102 mm) nominal inside diameter.
+```datasheet
+label: Conduit Sleeve Nominal Inside Diameter
+type: select
+unit: in
+options:
+ - "4"
+ - "5"
+ - "6"
+default: "4"
+```
+
## A minimum of four conduit sleeves shall be provided per TR-to-TR riser link.
−### Four sleeves is the TIA-569-E minimum; six to eight are common in practice once IT counts the cable types - voice backbone, data backbone, fiber riser, access control, AV, and CATV - that must be segregated. {note}
−
```datasheet
label: Conduit Sleeves per Riser Link
…6 unchanged lines
```
−```datasheet
−label: Conduit Sleeve Nominal Inside Diameter
−type: select
−unit: in
−options:
− - "4"
− - "5"
− - "6"
−default: "4"
−```
+### Four sleeves is the TIA-569-E minimum; six to eight are common in practice once IT counts the cable types - voice backbone, data backbone, fiber riser, access control, AV, and CATV - that must be segregated. {note}
## Conduit sleeves shall be located near a room corner in a grouped pattern, positioned and routed as shown on the drawings. The sleeve layout location is shown at [[drawing: TR riser sleeve location]].
…7 unchanged lines
## Every conduit sleeve through a rated assembly shall be firestopped with a UL-listed firestop sleeve assembly or intumescent collar.
−### Fire-rated floor and wall assemblies require a listed firestop at every penetration; an un-firestopped sleeve defeats the rated assembly and fails inspection. {note}
−
```datasheet
label: Conduit Sleeve Firestop Method
…5 unchanged lines
```
+### Fire-rated floor and wall assemblies require a listed firestop at every penetration; an un-firestopped sleeve defeats the rated assembly and fails inspection. {note}
+
## Surface Raceway {toc}
…48 unchanged lines
# Environmental and Service Conditions {toc}
−## Telecommunications spaces shall be conditioned to maintain the temperature and humidity required for continuous operation of the installed active equipment. {note}
+## Telecommunications spaces shall be conditioned to maintain the temperature and humidity required for continuous operation of the installed active equipment.
### The typical design class for a commercial TR is ASHRAE Class A1, not the wider data-center classes; TIA-569-E Addendum 1 aligns its environmental setpoints with ASHRAE's 5th edition. {note}
…28 unchanged lines
max: 60
step: 5
−setpoints: [45, 50, 55]
+setpoints: [30, 45, 50, 55, 60]
default: 50
```
## Cooling System {toc}
−## A dedicated conditioning unit drives whether the room stays within range when the building system is off; this selection shall be made deliberately and not left to the building HVAC by default. {note}
+## A dedicated conditioning unit drives whether the room stays within range when the building system is off; this selection shall be made deliberately and not left to the building HVAC by default.
### Building VAV systems are commonly shut down nights and weekends; an interior TR with no exterior wall served only by building HVAC will overheat without 24/7 cooling. {note}
…15 unchanged lines
## The cooling capacity shall be sized against the actual equipment heat load and shall not be less than the scheduled rule-of-thumb allowance per rack or cabinet.
−### The 500 to 750 BTU/hr per rack rule-of-thumb is a starting allowance only; the installed-equipment heat load governs and shall be verified against the IT load schedule. {note}
+### The 500 to 750 BTU/hr per rack rule-of-thumb is a starting allowance only; the installed-equipment heat load governs and shall be verified against the IT load schedule.
```datasheet
…27 unchanged lines
# Lighting {toc}
−## Lighting shall provide a maintained illuminance adequate for terminating and servicing cabling at the rack and backboard. {note}
+## Lighting shall provide a maintained illuminance adequate for terminating and servicing cabling at the rack and backboard.
### A specification that says only "provide lighting" without a maintained illuminance commonly yields a single lamp, forcing the technician to work by flashlight. {note}
…17 unchanged lines
# Power {toc}
−## Telecommunications spaces shall be served by dedicated branch circuits that are not shared with building, lighting, or janitorial loads. {note}
+## Telecommunications spaces shall be served by dedicated branch circuits that are not shared with building, lighting, or janitorial loads.
### Sharing TR outlets with janitor or building circuits causes nuisance tripping and violates NEC best practice for critical loads. {note}
…117 unchanged lines
default: 5
```