1 Scope
NOTE This standard covers factory-assembled terminal heating units that deliver heat to a single zone or localized area using a hydronic coil, a steam coil, or electric resistance elements. Terminal heating units are the workhorses of perimeter and spot heating: they hang in a stairwell, tuck under a storefront, or blow across a loading dock door, each serving its own small load rather than feeding a distribution system. The unit types in scope are propeller unit heaters, blower (cabinet) unit heaters, cabinet unit heaters, fin-tube radiation, convectors, electric baseboard heaters, and electric force-flow heaters, each pairing a heat source (hot water, steam, or electric resistance) with a means of air movement (forced by a fan or natural convection). Units in this standard serve a single thermostatic zone and are controlled by a zone thermostat, an integral aquastat, or a signal from the building automation system. (1.1)
1.2The Contractor shall provide terminal heating units of the types, capacities, and configurations indicated, complete with coils or elements, fans or convection enclosures, controls, mounting hardware, and accessories required for a complete and operable installation.
1.3Where a unit serves an entry, vestibule, or loading dock subject to freezing, the Contractor shall provide the freeze-protection provisions specified herein.
NOTE This standard does not cover the following, which are specified elsewhere: (1.4)
- Central station air handlers, packaged rooftop units, VAV terminal boxes, and gas-fired make-up air units
- Multi-mode fan-coil units (see Fan Coil Units)
- Radiant panels and in-floor radiant systems
- Hydronic supply, return, and condensate piping upstream of each unit's connection (see Hydronic Piping); this standard governs the unit, its control valve, and its terminal connections
2 Definitions
NOTE The following terms are used in this standard: (2.1)
- Propeller unit heater: a unit heater using an axial (propeller) fan to draw air across a heating coil and discharge it horizontally or vertically; high airflow, higher noise, lower cost.
- Blower unit heater: a unit heater using a centrifugal fan that develops external static pressure, producing a longer, quieter throw than a propeller unit at higher cost.
- Cabinet unit heater: an enclosed terminal unit with a centrifugal blower, a heating coil, and a filter, intended for occupied spaces where appearance and quiet operation matter.
- Fin-tube radiation: a continuous finned hydronic or steam element in an architectural enclosure that heats a perimeter by natural convection without a fan.
- Convector: a cabinet-enclosed hydronic element that heats by natural convection (no fan), used where a quiet perimeter unit is needed but a continuous fin-tube run is not.
- Force-flow heater: an electric cabinet heater with a centrifugal blower and resistance elements, used for spot heating where no hydronic or steam source is available.
- EWT and LWT: entering water temperature and leaving water temperature — the supply and return temperatures at the coil that set hydronic capacity.
- EAT: entering air temperature — the temperature of the air entering the unit, which together with EWT and airflow sets the unit's heating capacity.
- MBH: thousands of Btu per hour, the customary unit of heating capacity for hydronic and steam terminal units.
3 Referenced Standards
NOTE The following standards are referenced in this document. The edition in force on the project's date of issue for permit governs unless a specific edition is cited. (3.1)
| Standard |
Title |
| UL 1042 |
Electric Baseboard Heating Equipment |
| UL 2021 |
Fixed and Location-Dedicated Electric Room Heaters |
| UL 1995 |
Heating and Cooling Equipment |
| AHRI 410 |
Forced-Circulation Air-Cooling and Air-Heating Coils |
| NFPA 70 (Article 424) |
National Electrical Code — Fixed Electric Space-Heating Equipment |
| NFPA 70 (Article 210) |
National Electrical Code — Branch Circuits |
| ASHRAE 90.1 |
Energy Standard for Sites and Buildings Except Low-Rise Residential Buildings |
| IMC Chapter 14 |
International Mechanical Code — Heating Equipment |
| NFPA 211 |
Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances |
| ASCE 7 |
Minimum Design Loads and Associated Criteria for Buildings and Other Structures |
| AHRI 440 |
Fan-Coil Units |
NOTE There is no single AHRI certification program that exclusively rates hydronic propeller and blower unit heaters; capacity for these units is published by the manufacturer on a Hydronics Institute or proprietary test basis, and the rating basis shall be stated on the submittal. (3.2)
4 Submittals
4.1 Action Submittals
4.1.1The Contractor shall submit the following action submittals for each terminal heating unit type before fabrication or ordering:
- Product data for each unit, including capacity ratings at the scheduled EWT, LWT, EAT, and airflow, and the rating basis (AHRI standard, Hydronics Institute, or proprietary)
- Fan performance data including airflow, external static pressure, motor type, and sound power or NC rating
- Electrical data including voltage, phase, full-load amperes, and minimum circuit ampacity for electric and fan-powered units
- Dimensioned shop drawings showing enclosure, mounting points, connection locations, and required clearances
- Coil data including rows, fin spacing, working pressure, and material of construction
- Control valve, aquastat, thermostat, and BAS interface data
- Color and finish samples for units in occupied or architecturally finished spaces
- Seismic anchorage and bracing calculations for suspended and wall-mounted units in the applicable seismic design category
☑ Product data with rated capacity and rating basis
☑ Fan performance and sound (NC) data
☑ Electrical data (voltage, phase, FLA, MCA)
☑ Dimensioned shop drawings with clearances
☑ Coil construction and working pressure data
☐ Control valve, aquastat, thermostat, BAS interface data
☐ Color and finish samples
☐ Seismic anchorage and bracing calculations
NOTE Capacity ratings shall be submitted at the scheduled entering and leaving water temperatures, not at a generic catalog condition, so that the reviewer can confirm the unit performs at the actual system supply temperature. (4.2)
4.3 Closeout Submittals
4.4The Contractor shall submit the following closeout submittals before substantial completion:
- Operation and maintenance manuals for each unit type
- As-built control sequences and thermostat or BAS point lists
- Startup and test reports including measured airflow and discharge temperature
- Warranty documentation
- Filter size and replacement schedule for cabinet and force-flow units
☑ Operation and maintenance manuals
☑ As-built control sequences and point lists
☑ Startup and test reports
☑ Warranty documentation
☐ Filter size and replacement schedule
4.6The Contractor shall submit the following informational submittals:
- Manufacturer's installation instructions
- Manufacturer's certification of UL or equivalent NRTL listing for each unit
- Field quality-control test plan
☑ Manufacturer's installation instructions
☑ NRTL listing certification
☐ Field quality-control test plan
5 Quality Assurance
5.1Each electric terminal heating unit shall be listed and labeled by a Nationally Recognized Testing Laboratory under the applicable UL standard for its type.
5.2Electric baseboard heaters shall be listed to UL 1042.
5.3Fixed and wall- or ceiling-mounted electric room and unit heaters shall be listed to UL 2021.
5.4Hydronic and steam unit heaters shall be listed to UL 1995 or an equivalent NRTL standard for heating equipment.
NOTE The manufacturer shall have produced terminal heating units of the specified type for not less than five years. (5.5)
NOTE A listing label demonstrates that the unit's electrical construction, element guarding, and over-temperature protection were evaluated by an independent laboratory; an unlisted electric heater is not acceptable for a code-compliant installation. (5.6)
5.7The rating basis stated on the submittal shall match the conditions in the unit schedule; a unit rated only at 180 °F EWT shall not be accepted for a system that operates at a lower supply temperature without a re-rating at the actual EWT.
NOTE The single most common capacity error is rating a hydronic unit at 180 °F EWT when the boiler plant is a condensing system delivering 120 °F to 140 °F; capacity falls sharply at low EWT, and a unit selected at the catalog condition will be undersized. (5.8)
6 Heat Source and Capacity
NOTE The heat source determines coil material, working pressure, control type, and the energy code requirements that apply; it is the first selection to make. (6.1)
6.2The Contractor shall provide the heat source indicated for each unit: hot water, steam, or electric resistance.
● Hot water (hydronic)
○ Low-pressure steam
○ Electric resistance
6.3Hydronic units shall be selected and rated at the scheduled entering water temperature, leaving water temperature, entering air temperature, and airflow.
NOTE The default entering water temperature of 140 °F reflects the prevalence of condensing boiler plants in current practice; specify a higher EWT only where the unit is served by a non-condensing plant confirmed to deliver that temperature. (6.4)
6.5The entering air temperature for a vestibule or loading dock unit shall be selected for the cold-entry condition, not the room setpoint, because the unit must heat air entering near outdoor temperature.
6.6Each unit's scheduled heating capacity at the design condition is determined by the building load and is indicated on the drawings. unit heating schedule Per drawings — unit heating schedule (deferred by default)
6.7For electric units, capacity is set by element wattage rather than water temperature; the wattage is selected to meet the zone load at the design condition.
7 Unit Type and Configuration
NOTE The unit type matches the air-movement method to the space: propeller and blower units for high-bay and industrial spaces, cabinet units and convectors for occupied rooms, fin-tube and baseboard for perimeter heating. (7.1)
7.2The Contractor shall provide the unit type indicated for each location.
Horizontal propeller unit heater
Vertical propeller unit heater
Horizontal blower (cabinet) unit heater
Cabinet unit heater (occupied space)
Fin-tube radiation
Convector
Electric baseboard heater
Electric force-flow heater
NOTE Match the unit type to the space as follows: (7.3)
- A propeller unit heater moves a large volume of air at low cost but generates substantially more noise than a blower unit and develops no usable external static pressure; it suits mechanical rooms, warehouses, and loading docks but not occupied offices.
- A blower unit heater develops external static pressure, throws air farther, and runs quieter than a propeller unit; it is the choice where the warm air must reach across a large or tall space.
- A cabinet unit heater encloses the blower and coil behind a finished panel with a filter, and is the appropriate selection for vestibules and entries adjacent to occupied space where appearance and quiet operation matter.
- Fin-tube radiation and convectors heat by natural convection without a fan; they are silent and maintenance-light, and are preferred for perimeter heating along glazing and in quiet occupied rooms.
7.4The Contractor shall provide the discharge orientation and throw indicated for each forced-air unit so the heated air reaches the intended part of the space.
● Horizontal throw
○ Vertical (downward) throw
7.5The discharge throw distance shall be coordinated with the space geometry so warm air reaches the occupied or door zone it is intended to serve. unit discharge direction 7.6Forced-air units in occupied or noise-sensitive spaces shall be provided with adjustable discharge louvers or deflectors to direct the airstream away from occupants.
8 Fan and Motor
NOTE The fan motor type sets both the noise of the unit and its compliance with the energy code's part-load fan-control requirements; it is not a free choice on fan-powered units. (8.1)
8.2Fan-powered units shall be provided with the motor type indicated.
○ PSC (permanent split capacitor)
● ECM (electronically commutated)
8.3Where ASHRAE 90.1 requires part-load fan control or variable-speed operation for the unit's motor size, the Contractor shall provide an ECM motor.
NOTE A PSC motor cannot follow a modulating fan-speed signal; installing one on a BAS-controlled unit that the energy code expects to modulate defeats the compliance path and wastes fan energy at part load. ECM motors also enable continuous low-speed operation for freeze protection and quiet night setback, which a single-speed PSC motor cannot provide. (8.4)
8.5The fan and motor assembly shall be selected so the unit's sound rating does not exceed the noise criterion specified for its space.
NOTE Propeller unit heaters commonly produce NC 45 to NC 55; specifying a propeller unit in an open office or a vestibule adjacent to a conference room without an NC limit invites occupant complaints, and a blower or cabinet unit should be selected instead. (8.6)
8.7Fan motors shall be permanently lubricated or provided with accessible lubrication fittings, and shall be serviceable without removing the unit from its mounting.
9 Coil and Element Construction
9.1Hydronic and steam coils shall be constructed of copper tubes with mechanically bonded aluminum or copper fins.
9.2Coils for corrosive or coastal environments shall be provided with copper fins or a protective coating in place of bare aluminum fins, as specified for the service condition.
9.3Each hydronic coil shall be factory pressure-tested and rated for a working pressure not less than the system design pressure.
9.4Steam coils shall be of the steam-distributing (non-freeze) type where they are exposed to entering air below 40 °F, to prevent condensate stratification and coil freeze-up.
NOTE A standard steam coil floods and freezes when cold entering air condenses steam unevenly across the tubes; a steam-distributing coil delivers steam along the full tube length and keeps the entire coil warm. (9.5)
9.6Electric resistance elements shall be of the finned-tubular sheathed type, guarded against contact, and provided with an integral thermal cutout that de-energizes the element on over-temperature.
NOTE The element thermal cutout protects against fire if airflow is blocked or the fan fails; it is a code-required safety device, not an optional accessory. (9.7)
10 Enclosure and Finish
NOTE The enclosure protects the working parts, sets the unit's appearance in occupied space, and determines how well the unit survives a corrosive environment; it is selected for the installed location, not by default. (10.1)
10.2The Contractor shall provide the enclosure construction and finish indicated for each unit's environment.
Steel cabinet, baked-enamel finish
Steel cabinet, epoxy powder-coat finish
Stainless steel
Galvanized steel (industrial, unfinished)
10.3Units in car washes, natatoriums, food-service areas, chemical or pharmaceutical spaces, or coastal locations shall be provided with stainless steel or epoxy-coated enclosures and coil protection.
NOTE A standard baked-enamel steel cabinet corrodes within a season in a wash-down or chlorinated environment; the corrosion-resistant enclosure and coil coating must be specified explicitly because it is not the catalog default. (10.4)
10.5Cabinet units in occupied spaces shall be provided with a baked-enamel or powder-coat finish in the color selected from the manufacturer's standard range. architectural finish schedule NOTE Architectural enclosures shall align with adjacent wall finishes and reveals where the unit is exposed in a finished space. (10.6)
11 Electrical
11.1Electric heater voltage shall match the available branch-circuit voltage at the unit; 277 V is common on commercial lighting panels and shall not be assumed to be 240 V or 208 V without confirmation.
120 V / 1Φ
208 V / 1Φ
208 V / 3Φ
240 V / 1Φ
277 V / 1Φ
480 V / 3Φ
NOTE A voltage mismatch — an electric heater ordered for 240 V on a 277 V lighting panel, or the reverse — is among the most common field problems on this equipment and produces a non-functional unit and a change order; the voltage must be coordinated with the serving panel before ordering. (11.2)
11.3Branch-circuit conductors, overcurrent protection, and disconnecting means shall be sized and provided in accordance with NFPA 70 Articles 424 and 210 for the unit's minimum circuit ampacity.
11.4Each electric heater and each fan-powered unit shall be provided with a disconnecting means within sight of the unit or a lockable disconnect at the serving panel, as required by NFPA 70.
11.5Fan-powered hydronic and steam units shall be provided with the fan motor electrical characteristics matching the available circuit.
11.6Internal wiring, terminal blocks, and the control compartment shall be factory-installed and listed as part of the unit.
12 Controls
NOTE The control strategy ties the unit to its zone and to the energy code's thermostat requirements; a simple line-voltage thermostat is no longer universally acceptable. (12.1)
12.2The Contractor shall provide the control method indicated for each unit.
Line-voltage thermostat (on/off)
Low-voltage thermostat with relay
BAS/DDC with two-position valve and end switch
BAS/DDC with modulating (0-10 V) valve
12.3Where ASHRAE 90.1 Section 6.5.6 as adopted requires programmable or BAS-integrated zone control, the Contractor shall not provide a single-setpoint line-voltage thermostat.
NOTE A line-voltage single-setpoint thermostat cannot provide the scheduled setback and programmability that current energy-code editions require; in jurisdictions enforcing ASHRAE 90.1-2019 or later it fails the control requirement and a programmable or BAS-integrated thermostat is required instead. (12.4)
12.5Units integrated with the building automation system shall interface with the controls specified in Building Automation System. 12.6Hydronic units shall be provided with a two-way or two-position control valve with an end switch that interlocks the fan to valve position, so the fan does not run when the coil is cold.
NOTE A fan that runs while the control valve is closed blows unheated air into the space, which feels like a draft and wastes fan energy; the end-switch interlock prevents cold-blow by holding the fan off until the valve opens. (12.7)
NOTE Modulating units served by a variable-speed plant shall be provided with a 0-10 V modulating valve actuator compatible with the BAS, as coordinated with
Hvac Variable Frequency Drives where applicable.
(12.8) 13 Freeze Protection
NOTE Any hydronic or steam unit serving a vestibule, entry, loading dock, or other space exposed to freezing air shall be provided with a freeze-protection strategy; omitting it is a leading cause of coil failure. (13.1)
13.2The Contractor shall provide the freeze-protection method indicated for each unit exposed to freezing conditions.
Low-limit aquastat (fan cutout below setpoint)
Self-regulating heat trace on coil piping
Continuous-circulation provision
Glycol solution in coil loop
13.3A low-limit aquastat shall de-energize the fan whenever the coil water temperature falls below its setpoint, so the unit never blows freezing air and the coil retains warm water.
NOTE Specifying a vestibule or loading dock unit with no aquastat, no heat trace, and no continuous-flow provision leaves the coil to freeze the first time the entry door is propped open in cold weather; the freeze-protection method must be an explicit part of the specification, not an afterthought. (13.4)
13.5Where glycol is used for freeze protection, the solution concentration shall be selected for the design low temperature and the coil capacity shall be re-rated for the glycol solution's reduced heat-transfer performance.
14 Steam Units
NOTE Steam terminal units carry their own hazards — pressure class, condensate removal, and trap selection — that do not apply to hydronic units and must be addressed in the specification. (14.1)
14.2Steam units shall be selected for the steam pressure class of the distribution system they serve.
● Low-pressure steam (≤ 15 psig)
○ High-pressure steam (> 15 psig)
14.3A unit and its coil and valve rated only for low-pressure steam shall not be connected to a high-pressure distribution system; the coil and control valve pressure ratings shall be confirmed against the actual distribution pressure before ordering.
14.4Each steam unit shall be provided with a steam trap selected for the unit's condensate load and the system back-pressure.
● Float-and-thermostatic
○ Thermodynamic
○ Inverted-bucket
NOTE Leaving trap selection entirely to the field without defining the condensate load, back-pressure, and trap type produces chronic trap failures and waterlogged coils; the trap basis shall be defined in the specification. (14.5)
14.6Steam traps shall be installed below the coil outlet with the access and clearance required to service or replace the trap without removing the unit.
15 Installation
15.1Units shall be installed in accordance with the manufacturer's installation instructions and IMC Chapter 14.
15.2Suspended and wall-mounted units shall be installed with the clearances required for filter, motor, and trap access, coordinated with the reflected ceiling plan and adjacent construction. reflected ceiling plan NOTE Cabinet units installed too close to a wall or recessed into a tight pocket cannot be serviced; the access clearances must be coordinated with the architecture before rough-in, because a unit that cannot be opened cannot have its filter or motor changed. (15.3)
15.4Ceiling-suspended propeller and blower units shall be supported and braced against seismic loads in accordance with ASCE 7 for the project's seismic design category.
15.5Seismic bracing for suspended units is delegated-design work in seismic design category C and above; the responsibility for the restraint calculations and details shall be assigned to the Contractor's engineer where the equipment vendor does not provide them.
15.6Hydronic and steam connections shall be made with unions or flanges at the unit so the unit can be isolated and removed without cutting piping.
NOTE Each hydronic unit shall be provided with a means of isolation, balancing, and air venting at the coil so the coil can be served and balanced independently. (15.7)
15.8Filters in cabinet and force-flow units shall be installed accessible for replacement from the front or bottom of the unit without dismantling the enclosure.
15.9Condensate from steam units shall be drained to the return system through the trap; the condensate connection shall be pitched to drain and shall not trap water against the coil.
16 Field Quality Control
16.1After installation, each unit shall be started and tested to confirm it delivers the scheduled airflow and discharge temperature at the design condition.
16.2Startup shall confirm correct fan rotation, valve and damper operation, thermostat or BAS response, and freeze-protection cutout operation where provided.
NOTE The freeze-protection aquastat or low-limit shall be tested by simulating a low coil temperature and confirming the fan de-energizes. (16.3)
16.4Electric units shall be tested to confirm the element thermal cutout de-energizes the element on simulated over-temperature.
NOTE Test results shall be recorded and submitted in the field quality-control report. (16.5)
17 Delivery, Storage, and Handling
17.1Units shall be delivered in the manufacturer's original packaging with model, capacity, and electrical data labels intact.
17.2Units shall be stored indoors, protected from weather, dust, and physical damage, and shall not be installed in the airstream until the building is closed in and clean.
NOTE Units used for temporary construction heating shall have their coils, filters, and motors inspected and filters replaced before final acceptance, and shall not be accepted with construction debris in the coil. (17.3)
18 Warranty
18.1The manufacturer shall warrant each terminal heating unit against defects in materials and workmanship for the period specified, measured from substantial completion.
● 1 year
○ 2 years
○ 5 years
18.2Heating elements and hydronic coils shall be warranted for the period specified, which may exceed the base unit warranty.
○ 1 year
● 5 years
○ 10 years
19 Spare Parts
19.1The Contractor shall furnish the spare parts indicated for the owner's maintenance stock.
19.2The Contractor shall furnish one complete set of replacement filters for each cabinet and force-flow unit.
☑ One spare filter set per cabinet/force-flow unit
☐ One spare fan motor per unit type
☐ One spare control valve per unit type
☐ One spare thermostat per unit type
NOTE Replacement filters shall match the size and rating recorded in the closeout filter schedule so the owner can reorder without re-measuring. (19.3)