NOTEThis Standard covers water vapor retarders and water vapor barriers installed in direct contact with soil or granular fill beneath concrete slabs-on-grade. (1.1)
NOTEIt addresses material selection (single-ply polyethylene sheet, multi-layer reinforced laminate, and bituminous sheet), determination of the ASTM E1745 performance class, the elevated requirements for true vapor barriers serving moisture-sensitive occupancies, placement sequence, lap and seam construction, penetration sealing, repair before concrete placement, and coordination with the concrete pour. (1.2)
NOTEThis Standard applies wherever the finished slab will receive moisture-sensitive flooring, coatings, or adhesives, will be climate-controlled, or where code requires floor dampproofing. (1.3)
NOTEResilient flooring, sheet vinyl, wood, carpet tile with moisture-sensitive adhesives, epoxy and urethane coatings, and most adhered finishes fail when slab moisture vapor migrates upward unchecked. ASTM F710 requires an effective vapor retarder in direct contact with the underside of any slab that will receive resilient flooring, and IRC R506.2.3 requires a Class A retarder beneath residential slabs on ground. The under-slab membrane is the primary, permanent line of moisture control because it cannot be added after the slab is placed. (1.4)
NOTEThis Standard does not cover the following adjacent scopes. (1.5)
NOTEEach excluded item is owned by another standard and is called out here to fix the boundary at bid time: (1.6)
Structural design of the slab itself (thickness, reinforcement, joints) and granular sub-base design and compaction — see Slab On GradeSlab-on-GradeResolves to the current edition.sync/slab-on-grade and Site Rough GradingSite Grading and Subgrade PreparationResolves to the current edition.sync/site-rough-grading.
Concrete mix design, placement, curing, and finishing — see Cast In Place ConcreteCast-in-Place ConcreteResolves to the current edition.sync/cast-in-place-concrete.
Waterproofing membranes on the exterior face of below-grade walls, and occupied below-grade slabs subject to hydrostatic pressure — those are wall and plaza waterproofing assemblies, not under-slab vapor control.
Above-slab vapor control layers that are part of a flooring system (sheet or liquid-applied moisture-mitigation coatings over a cured slab) — those belong with the flooring assembly, e.g. Epoxy FlooringEpoxy Floor CoatingsResolves to the current edition.sync/epoxy-flooring.
Generic vapor retarders used in wall or roof assemblies — see Vapor RetardersVapor RetardersResolves to the current edition.sync/vapor-retarders.
NOTETerminology used in this Standard is defined by permeance, not by trade habit. (1.7)
NOTEThe terms "vapor barrier" and "vapor retarder" are frequently used interchangeably in the field, which creates ambiguity at bid time. This Standard fixes the meanings: (1.8)
Vapor retarder: a membrane with a water vapor permeance less than or equal to 0.1 perms (after conditioning), meeting ASTM E1745 Class A, B, or C.
Vapor barrier: a membrane with a water vapor permeance less than or equal to 0.01 perms, the threshold ACI 302.2R associates with slabs receiving moisture-sensitive flooring.
Permeance is measured per ASTM E96/E96M and reported in U.S. perms.
NOTEWhere this Standard refers to "the membrane," it means the under-slab vapor retarder or vapor barrier sheet, whichever class the Contract Documents require. (1.9)
2Referenced Standards
2.1Materials, products, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited in the Contract Documents.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard
Title
ASTM E1745-17
Plastic Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
ASTM E1643
Selection, Design, Installation, and Inspection of Water Vapor Retarders Used in Contact with Earth or Granular Fill under Concrete Slabs
ASTM E1993
Bituminous Water Vapor Retarders Used in Contact with Soil or Granular Fill under Concrete Slabs
ASTM E96/E96M
Water Vapor Transmission of Materials
ASTM E154
Water Vapor Retarders Used in Contact with Earth Under Concrete Slabs, on Walls, or as Ground Cover
ASTM F710
Preparing Concrete Floors to Receive Resilient Flooring
ASTM F2170
Determining Relative Humidity in Concrete Floor Slabs Using in situ Probes
ACI 302.1R
Guide for Concrete Floor and Slab Construction
ACI 302.2R
Guide for Concrete Slabs that Receive Moisture-Sensitive Flooring Materials
IBC
International Building Code (Section 1805.2.2, Floors Below Grade)
IRC
International Residential Code (Section R506.2.3, Vapor Retarder)
3Submittals
3.1Action Submittals
3.1.1The Contractor shall submit the following action submittals for review before delivering material to the site:
Product data for the proposed membrane, seam tape, pipe boots, and mastic, including manufacturer, product designation, nominal thickness, and material type.
Manufacturer's certified test report demonstrating the membrane meets the required ASTM E1745 class for tensile strength, puncture resistance, and permeance, with permeance reported per ASTM E96/E96M.
For true vapor barrier applications, certified permeance test data demonstrating permeance less than or equal to 0.01 perms.
Samples of the membrane and the manufacturer's seam tape.
Shop drawings or manufacturer details for lap construction, penetration boots and collars, perimeter termination, and repair patching.
Statement of compatibility confirming the seam tape, pipe boots, and mastic are produced or approved by the membrane manufacturer for use with the proposed membrane.
3.2.1The Contractor shall submit the following informational submittals:
Manufacturer's printed installation instructions, including lap width, sealing method, and maximum permitted exposure interval before concrete placement.
Field inspection report confirming the membrane was installed and repaired before concrete placement, per ASTM E1643.
For radon-zone projects, coordination documentation confirming the membrane type and penetration sealing are compatible with the sub-slab depressurization system.
Informational Submittalscheckbox
☑ Manufacturer installation instructions
☑ Pre-pour field inspection report (E1643)
☐ Radon system coordination documentation
3.3Closeout Submittals
3.3.1The Contractor shall submit the following closeout submittals:
Post-cure slab relative humidity test results per ASTM F2170 demonstrating the slab meets the flooring or adhesive manufacturer's maximum relative humidity before flooring installation.
Documentation of any membrane repairs performed, with locations.
Closeout Submittalscheckbox
☑ ASTM F2170 relative humidity test results
☐ Membrane repair documentation
4Quality Assurance
4.1The membrane manufacturer shall be a firm regularly engaged in producing under-slab vapor retarders meeting ASTM E1745.
4.2The Installer shall be experienced in installing under-slab vapor retarders and shall follow the membrane manufacturer's printed instructions and ASTM E1643.
4.3A pre-installation conference shall be held before membrane installation to confirm sub-base readiness, lap and sealing method, penetration details, and the planned interval between membrane installation and concrete placement.
NOTEThe interval between installing the membrane and placing concrete is the single most common source of field damage, so it is fixed in advance rather than left to the pour schedule. UV exposure, wind uplift, and construction traffic degrade polyethylene over time, and the membrane is buried and unrepairable once concrete is placed. (4.4)
4.5The membrane shall be inspected for tears, punctures, and open seams immediately before concrete placement.
4.6All defects found during the pre-pour inspection shall be repaired before concrete is placed.
4.7Inspection of the installed membrane shall conform to ASTM E1643.
NOTEWhere the project's structural or geotechnical scope designates the under-slab vapor retarder as an item subject to special inspection, coordinate the inspection and reporting with Special Inspections And TestingSpecial Inspections and Structural TestingResolves to the current edition.sync/special-inspections-and-testing. (4.8)
5Performance and Classification
5.1ASTM E1745 Performance Class
5.1.1The membrane shall meet ASTM E1745 for the performance class required by the Contract Documents.
NOTEASTM E1745 sorts retarders into three classes by tested mechanical performance. All three classes share the same maximum permeance after conditioning (less than or equal to 0.1 perms); the classes differ only in tensile strength and puncture resistance, which govern how well the membrane survives installation traffic, rebar chairs, and the concrete pour. Class A is the default for commercial and institutional construction because the membrane must survive being walked on, having reinforcement placed over it, and the pour itself without tearing. (5.1.2)
5.1.3The minimum required performance class for the membrane shall be Class A unless the Contract Documents specify otherwise.
5.1.4Class selection shall account for installation risk, traffic during the pour, subgrade condition, and any flooring-manufacturer requirement that exceeds the code minimum.
ASTM E1745 performance classradio
● Class A
○ Class B
○ Class C
NOTEA coarse or angular granular fill, heavy reinforcement, or an aggressive pour sequence all argue for the higher puncture resistance of Class A even where code would permit a lower class. (5.1.5)
5.1.6The membrane shall meet or exceed the following ASTM E1745 minimum properties for the selected class.
NOTEThe tabulated values are the ASTM E1745 class minimums. The membrane is selected to the class, not to a mil thickness; the values below are the acceptance criteria, and the manufacturer's certified test report is the proof of compliance. (5.1.7)
Property
Class A
Class B
Class C
Tensile strength (lb/in., min.)
45
30
13.6
Puncture resistance (g, min.)
2,200
1,700
475
Permeance after conditioning (perms, max.)
0.1
0.1
0.1
5.2Permeance and the Vapor Barrier Threshold
5.2.1The membrane permeance shall be determined per ASTM E96/E96M and reported in U.S. perms.
NOTEPermeance is the controlling moisture-performance property. ASTM E1745 caps all classes at 0.1 perms, but that ceiling is not low enough for every floor. (5.2.2)
5.2.3For slabs receiving moisture-sensitive flooring, coatings, or adhesives, the membrane shall have a permeance less than or equal to 0.01 perms (a true vapor barrier per ACI 302.2R) unless the flooring or adhesive manufacturer permits a higher value in writing.
NOTEThis is the most consequential pitfall in under-slab vapor control. A membrane that satisfies ASTM E1745 Class A at 0.1 perms can still pass enough vapor to debond resilient flooring adhesives and blister coatings. ACI 302.2R recommends the 0.01-perm threshold for moisture-sensitive finishes. Specifying a class without also specifying the permeance ceiling is therefore insufficient whenever an adhered or coated finish will be installed; always cross-check the flooring or adhesive manufacturer's stated maximum permeance. (5.2.4)
5.2.5The flooring or adhesive manufacturer's maximum permeance shall be obtained and the membrane selected to satisfy the more stringent of that value and this Standard.
5.2.6The code-minimum 6-mil polyethylene permitted by IBC Section 1805.2.2 for below-grade floor dampproofing shall not be used where flooring adhesives, coatings, or moisture-sensitive finishes will be installed.
NOTEThe IBC below-grade floor dampproofing provision allows a minimum 6-mil polyethylene sheet or approved equivalent. That sheet is inadequate for flooring applications on two counts: its tested performance falls short of the durability needed to survive the pour, and its permeance is far above the threshold for moisture-sensitive finishes. The 6-mil sheet is a dampproofing minimum, not a vapor-control specification. (5.2.7)
6Membrane Type
6.1The membrane shall be one of the following types, selected to meet the required class and permeance.
NOTEThree material families serve this scope, and they trade off cost, puncture resistance, and achievable permeance: (6.2)
Single-ply polyethylene sheet (HDPE or LLDPE): a single extruded film. Economical; commonly available at 10-mil through 20-mil nominal thickness. Higher mil grades from major manufacturers are Class A capable.
Multi-layer reinforced laminate: a woven polyethylene scrim core laminated between two polyethylene films. The scrim core gives high tensile and puncture resistance, so these products are typically Class A and are the workhorse for commercial slabs.
Bituminous sheet per ASTM E1993: an asphalt-based composite sheet that achieves true vapor barrier performance (less than or equal to 0.01 perms). Used where the project demands a true vapor barrier for high-sensitivity occupancies.
6.3The membrane material shall be free of recycled content that would compromise the certified ASTM E1745 properties or the manufacturer's permeance rating.
7Nominal Thickness
7.1The membrane nominal thickness shall be as required to meet the specified class and permeance, and not less than the value scheduled.
Membrane nominal thicknessselect
10
15
20
NOTENominal thickness is not the same as ASTM E1745 class. A "15-mil" sheet is not automatically Class A; class is determined by tested tensile, puncture, and permeance performance, and the manufacturer's certified test report is the only proof. Thicker membranes generally resist puncture better and are preferred where the subgrade is coarse or the pour traffic is heavy, but thickness is selected alongside the class requirement, never as a substitute for it. (7.2)
7.3A nominal thickness of 10-mil shall be regarded as a Class C baseline and shall not be specified where Class A performance is required.
7.4A nominal thickness of 15-mil or greater shall be used where Class A performance is required, subject to certified test confirmation.
8True Vapor Barrier Configuration
8.1Where a true vapor barrier is required, the membrane shall be a bituminous sheet per ASTM E1993, or a multi-layer laminate independently certified to a permeance less than or equal to 0.01 perms.
NOTEASTM E1993 is the product standard for bituminous under-slab vapor barriers and is written around the 0.01-perm threshold. Some heavy multi-layer polyethylene laminates also achieve 0.01 perms; where one is proposed in place of a bituminous sheet, the certified permeance test report is the basis for acceptance. (8.2)
9Accessory Materials
9.1Seam tape shall be the pressure-sensitive tape produced or approved by the membrane manufacturer for use with the specified membrane.
NOTEField-improvised tapes are a leading cause of seam failure. Standard duct tape and generic packaging tape do not bond reliably to polyethylene and lose adhesion in the moist sub-slab environment. Only the manufacturer's project-specific seam tape carries a compatibility and performance warranty for the joint. (9.2)
9.3Pipe boots and penetration collars shall be the prefabricated or field-formed components produced or approved by the membrane manufacturer for the specified membrane.
9.4Mastic and sealant used to seal penetrations and terminations shall be compatible with the membrane and approved by the membrane manufacturer.
9.5Repair patch material shall be the same membrane as the field sheet.
10Sub-Base and Placement Position
10.1The membrane shall be placed directly beneath the concrete slab, in contact with the underside of the slab, on a prepared sub-base.
Membrane placement positionradio
● Directly under slab, no blotter (current ACI recommendation)
○ Under slab with granular cushion below membrane on coarse sub-base
NOTEACI 302.1R explicitly recommends placing the vapor retarder directly under the slab. This is a deliberate reversal of the older "blotter" method and is the current position for moisture-sensitive applications. (10.2)
10.3A granular blotter layer shall not be placed on top of the membrane beneath a slab that will receive moisture-sensitive flooring.
NOTEThe legacy blotter detail placed several inches of sand or fine granular fill on top of the membrane, with the slab poured on the blotter. The intent was to absorb bleed water and reduce curling, but the blotter traps bleed water against the slab and stays saturated, which dramatically slows slab drying and keeps the relative humidity at the flooring level high for months. For any slab receiving moisture-sensitive flooring, the blotter is omitted and the slab is poured directly on the membrane. (10.4)
10.5The sub-base supporting the membrane shall be a compacted, fine-graded surface free of sharp protrusions, ruts, and debris that could puncture the membrane.
NOTEDesign and compaction of the granular sub-base are outside this scope and are covered by Slab On GradeSlab-on-GradeResolves to the current edition.sync/slab-on-grade and Site Rough GradingSite Grading and Subgrade PreparationResolves to the current edition.sync/site-rough-grading; this Standard governs only the condition of that surface where it receives the membrane. Where a granular cushion is used to protect the membrane on a coarse sub-base, a minimum 4 in. of compacted granular material per ACI 302.1R is typical. (10.6)
11Installation
11.1The membrane shall be installed in accordance with ASTM E1643 and the manufacturer's printed instructions.
11.2The membrane shall be unrolled and positioned so the long dimension of the sheet runs in the direction that minimizes the number of end laps.
11.3The membrane shall be installed continuously over the entire slab area to be protected, with no gaps.
11.4The membrane shall be drawn taut and free of wrinkles and fishmouths before concrete placement, to the extent practical without stretching the sheet beyond its rated elongation.
11.5Laps and Seams
11.5.1Adjacent membrane sheets shall lap a minimum of 6 in.
Minimum seam lap widthrange
in
612
Default: 6 in
NOTEASTM E1643 sets the minimum lap at 6 in. The lap is the most likely path for vapor to bypass the membrane, so the width is a floor, not a target; widen it where the manufacturer's detail or field conditions warrant. (11.5.2)
11.5.3All laps shall be sealed with the manufacturer's seam tape for vapor barrier applications.
NOTESealed (taped) laps are mandatory wherever the membrane functions as a vapor barrier or a Class A/B vapor retarder under moisture-sensitive flooring. Unsealed, unsupported laps are acceptable only for basic below-grade dampproofing, which is outside the moisture-sensitive scope this Standard is written for. (11.5.4)
11.5.5Seam tape shall be applied to clean, dry membrane surfaces and pressed to achieve continuous adhesion across the full lap.
11.5.6End laps and side laps shall be sealed by the same method.
Seam sealing methodradio
● Manufacturer seam tape, fully sealed
○ Manufacturer-supplied double-sided tape within lap
11.6Penetrations
NOTEEvery pipe, conduit, drain, and other penetration through the membrane shall be sealed with a manufacturer-approved boot, collar, or mastic detail compatible with the membrane. (11.6.1)
NOTEPenetrations are the most common moisture ingress point in an otherwise sound installation. A continuous membrane with unsealed pipe penetrations is not a vapor barrier. Each penetration is sealed individually with a detail rated for the membrane type, not patched with field tape. (11.6.2)
11.6.3Pipe penetrations shall be sealed with a prefabricated pipe boot where one is available for the penetration size, or with a field-formed collar sealed to both the pipe and the membrane.
11.6.4The membrane shall be sealed tightly to the penetrating element so that no open annular gap remains.
11.6.5Penetration locations and the routing of under-slab utilities shall be coordinated with the plumbing, electrical, and mechanical work as shown. under-slab utility penetration locations
Penetration sealing methodradio
● Prefabricated pipe boot
○ Field-formed collar with mastic
○ Manufacturer pre-cut collar
11.7Perimeter Termination
11.7.1The membrane shall be terminated at the slab perimeter so that no continuous moisture path bypasses the membrane at the slab edge.
NOTEAn unsealed perimeter lets soil moisture migrate under the slab edge and around the membrane, defeating the field installation. The termination detail depends on whether the slab abuts a foundation wall, a grade beam, or a thickened edge, and on the below-grade wall dampproofing it must tie into. (11.7.2)
11.7.3The membrane shall be lapped up and sealed to the foundation wall, grade beam, or footing face as shown.
11.7.4Where the slab edge abuts below-grade wall dampproofing or waterproofing, the membrane termination shall be lapped and sealed to that assembly so the two systems are continuous.
Perimeter termination detailradio
● Lap up and seal to foundation wall
○ Lap up and seal to grade beam
○ Lap over and seal to footing face
○ Seal to below-grade wall dampproofing
NOTEFailing to tie the under-slab membrane to the wall dampproofing is a common detailing gap; the two assemblies are coordinated so there is no break in moisture control at the wall-to-slab joint. (11.7.5)
11.8Repair
NOTEThe membrane shall be inspected for damage immediately before concrete placement, and all tears, punctures, and open seams shall be repaired before concrete is placed. (11.8.1)
NOTEForm stakes, rebar chairs, and foot traffic routinely tear the membrane between installation and the pour. Specifying repair before placement is frequently omitted, and the omission is exactly why so many installed barriers underperform; once concrete covers the membrane, no defect can be corrected. (11.8.2)
11.8.3Damaged areas shall be repaired with a patch of the same membrane, overlapping the damage a minimum of 6 in. in all directions, sealed per ASTM E1643.
11.9Exposure and Coordination with Concrete Placement
11.9.1Concrete shall be placed over the membrane within the maximum exposure interval established at the pre-installation conference, after which the membrane shall be re-inspected and repaired before placement.
Maximum membrane exposure before concrete placementrange
days
330
Default: 14 days
NOTEPolyethylene degrades under sustained UV exposure, and wind and construction traffic accumulate damage over time. Fixing a maximum interval keeps the membrane in serviceable condition at the pour; if the schedule slips past it, the membrane is re-inspected rather than assumed sound. (11.9.2)
NOTEConcrete placement shall not damage or displace the membrane; equipment, chutes, and personnel routing shall protect the installed sheet. (11.9.3)
NOTEConcrete mix design, placement, curing, and finishing are governed by Cast In Place ConcreteCast-in-Place ConcreteResolves to the current edition.sync/cast-in-place-concrete; this clause governs only protection of the membrane during the pour. Rebar chairs, support accessories, and other items bearing on the membrane are covered by Concrete AccessoriesConcrete Accessories and EmbedsResolves to the current edition.sync/concrete-accessories. (11.9.4)
11.10Radon Coordination
NOTEWhere the project is in an EPA radon Zone 1 area or the Contract Documents require radon control, the membrane type and all penetration sealing shall be coordinated with the sub-slab depressurization system. (11.10.1)
NOTEIn high-radon areas a vapor barrier alone may be insufficient; the membrane works with a sub-slab depressurization system, and the two are coordinated so penetrations are sealed and the barrier supports the mechanical mitigation. This coordination is with the mechanical work and is confirmed in the informational submittals. (11.10.2)
11.10.3Penetrations serving the sub-slab depressurization system shall be sealed to the membrane to the same standard as all other penetrations.
Radon coordination requiredradio
○ Yes - coordinate with sub-slab depressurization system
● No - not in a designated radon control area
12Testing
12.1Post-Cure Slab Moisture Verification
NOTEBefore moisture-sensitive flooring is installed, the slab relative humidity shall be tested per ASTM F2170 using in situ probes. (12.1.1)
NOTEThe under-slab membrane controls vapor from the soil, but the concrete itself releases mixing water as it cures. ASTM F2170 measures the in-place relative humidity inside the slab, which is the test flooring and adhesive manufacturers rely on to confirm the slab is dry enough to receive the finish. A correctly installed vapor barrier shortens the drying time and lets the slab reach the threshold; it does not eliminate the test. (12.1.2)
12.1.3The slab relative humidity shall not exceed the threshold required by the flooring or adhesive manufacturer before flooring is installed.
Maximum slab relative humidity before flooring (ASTM F2170)range
%
7085
Default: 75 %
NOTEA relative humidity of 75% is a common ceiling for resilient flooring, but the controlling value is whatever the flooring or adhesive manufacturer states; some systems require 80% and some require lower. The more stringent of the manufacturer's value and 75% governs unless the manufacturer permits otherwise in writing. (12.1.4)
12.1.5Relative humidity testing shall not begin until the slab has cured and dried sufficiently for a representative result.
Minimum slab drying period before RH testingrange
days
3090
Default: 60 days
NOTEA minimum drying period of approximately 60 days is typical for standard water-cement-ratio concrete before relative humidity testing is meaningful, but the actual time varies with the water-cement ratio, slab thickness, and the drying environment. The probes are read after the slab has had a realistic opportunity to dry, not on a fixed calendar date alone. (12.1.6)
12.1.7The number and distribution of test locations shall conform to ASTM F2170.
13Delivery, Storage, and Handling
13.1Membrane rolls, seam tape, boots, and mastic shall be delivered in the manufacturer's original packaging with labels intact and the product designation legible.
13.2Membrane rolls shall be stored off the ground, protected from prolonged sunlight, and protected from puncture and crushing until installed.
NOTEPolyethylene and bituminous sheet both degrade under sustained UV exposure, and crushed or punctured rolls yield damaged sheet that is hard to detect once unrolled. (13.3)
13.4Seam tape and mastic shall be stored within the temperature range the manufacturer specifies so their adhesion is not compromised.
13.5Damaged rolls and material past the manufacturer's shelf life shall not be installed.
14Warranty
14.1The membrane manufacturer shall warrant the membrane against defects in material for the period the manufacturer publishes for the specified product.
NOTEThe under-slab membrane is buried and permanent; it cannot be inspected or replaced over the life of the slab, so the manufacturer's material warranty and the certified test data at submittal are the only assurances of long-term performance. There is no field warranty for the installed assembly beyond the Contractor's workmanship obligations, because the assembly is concealed at completion. (14.2)
14.3The Contractor shall warrant the membrane installation, including laps, penetration seals, and terminations, against defects in workmanship for the project's general construction warranty period.
This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.
Attribution & reuse notice — keep this with any copy:
"Under-Slab Vapor Barriers." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/vapor-barriers-under-slab — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.