1 Scope
NOTE This standard covers factory-assembled, unitary water-source heat pump equipment rated below 135,000 Btuh and the shared building water loop that interconnects the units. (1.1)
NOTE A water-source heat pump moves heat between the conditioned space and a common circulating water loop rather than to outdoor air at each unit. In cooling, the unit rejects heat into the loop; in heating, it extracts heat from the loop. Because every unit shares one loop, a building can reject heat from sunny-side zones into the loop while shadow-side zones simultaneously draw heat from it, recovering energy internally before the loop conditioning equipment must add or reject any. (1.2)
NOTE The water-loop heat pump (WLHP) system is the dominant commercial application of this equipment and is the primary subject of this standard. (1.3)
NOTE In a water-loop system the circulating water is maintained within a moderate band, typically 60 °F to 90 °F, by a boiler that adds heat when the loop falls below its low limit and a cooling tower or closed-circuit fluid cooler that rejects heat when the loop rises above its high limit. The loop itself is a building recirculating loop, not a connection to the earth or groundwater. (1.4)
1.5Equipment furnished under this standard shall be certified under the AHRI Water-Source Heat Pump certification program.
1.6Equipment furnished under this standard shall be rated in accordance with ANSI/AHRI 600-2023.
1.7Each water-source heat pump unit shall be a self-contained, factory-charged, hermetically sealed refrigerant package requiring only loop-water, electrical, condensate, and air connections in the field.
1.8This standard addresses water-to-air and water-to-water packaged units in vertical, horizontal, console, and through-the-wall configurations.
NOTE Ground-source (geothermal) closed-loop, bore-field, and open-well systems are excluded; those systems share the same unit hardware but add earth-coupling design not covered here. (1.9)
NOTE Ground-source systems introduce bore-field thermal sizing, well flow, and low-temperature brine operation that change unit selection and loop design substantially. The unit hardware overlaps, but the loop engineering does not, so they are out of scope. Detailed hydronic distribution piping beyond the unit connections is likewise a coordination note only here; see the project plumbing and hydronic documents. (1.10)
NOTE Standalone loop-rejection and loop-heating equipment design is cross-referenced, not specified in full. (1.11)
NOTE Cooling towers and fluid coolers are addressed as loop heat-rejection equipment under
Cooling Towers. Where this standard sets loop-side requirements it does so to coordinate the WSHP units with that equipment, not to replace it.
(1.12) 2 Referenced Standards
2.1Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
| Standard |
Title |
| ANSI/AHRI 600-2023 (I-P) |
Performance Rating of Water/Brine to Air Heat Pump Equipment |
| ASHRAE 37-2009 |
Methods of Testing for Rating Electrically Driven Unitary Air-Conditioning and Heat Pump Equipment |
| ASHRAE 90.1-2022 |
Energy Standard for Buildings Except Low-Rise Residential Buildings |
| ASHRAE 62.1 |
Ventilation for Acceptable Indoor Air Quality |
| ASHRAE 15-2022 |
Safety Standard for Refrigeration Systems |
| ISO 13256-1:1998 |
Water-Source Heat Pumps — Testing and Rating for Performance, Part 1: Water-to-Air and Brine-to-Air |
| 10 CFR 431, Subpart F |
Energy Conservation Program: Water-Source Heat Pumps (DOE) |
| NFPA 70-2023 (NEC) |
National Electrical Code (Article 440) |
3 Submittals
3.1Action submittals are required before fabrication or ordering of equipment.
3.1.1The Contractor shall submit the following action submittals for review:
- Product data for each unit type, marked to show the proposed configuration, capacity, electrical characteristics, and certified ratings
- AHRI 600-2023 certification listing or certified-rating reference number for each unit model
- Manufacturer's capacity tables confirming cooling and heating capacity at the actual project design entering-water temperatures, not only the AHRI rating point
- Sound power and sound pressure (NC) data at the scheduled airflow and external static pressure
- Dimensioned drawings showing cabinet size, connection locations, service clearances, and weights
- Wiring diagrams showing factory and field wiring, control terminals, and two-position valve interface
- Loop schematic showing boiler, cooling tower or fluid cooler, pumps, and design loop temperatures and flow
☑ Product data per unit type
☑ AHRI 600-2023 certification listing
☑ Capacity tables at design EWT
☑ Sound power / NC data at scheduled airflow
☑ Dimensioned drawings with clearances and weights
☐ Wiring diagrams (factory and field)
☐ Loop schematic with design temperatures and flow
3.2Informational submittals document refrigerant, code compliance, and design assumptions.
3.2.1The Contractor shall submit the following informational submittals:
- Refrigerant type, charge quantity per unit, and GWP, with a statement of compliance with applicable HFC phase-down regulations
- Refrigerant leak-detection and machinery-room analysis where multiple units share an enclosed space, per ASHRAE 15
- Loop diversity and simultaneous-load calculations used to size the boiler and heat-rejection equipment
- Manufacturer's installation, operation, and maintenance instructions
☑ Refrigerant type, charge, and GWP with compliance statement
☐ ASHRAE 15 leak-detection / machinery-room analysis
☑ Loop diversity and simultaneous-load calculations
☑ Installation, operation, and maintenance instructions
3.3Closeout submittals are required before Substantial Completion.
3.3.1The Contractor shall submit the following closeout submittals:
- Commissioning records documenting measured entering and leaving water temperature, water flow, and airflow at each unit
- Air- and water-side balancing reports
- Operation and maintenance manuals, including recommended spare-parts list
- Executed warranty documents
☑ Commissioning records (water temps, flow, airflow per unit)
☑ Air- and water-side balancing reports
☑ Operation and maintenance manuals
☑ Executed warranty documents
4 Quality Assurance
4.1Units shall be the product of a single manufacturer regularly engaged in the production of water-source heat pump equipment.
NOTE Each unit model furnished shall carry a current AHRI 600-2023 certified rating; ratings published only by the manufacturer and not independently certified shall not be accepted. (4.2)
NOTE AHRI third-party certification confirms that the published cooling capacity, heating capacity, EER, and COP have been verified independently rather than self-declared. Requiring an active certification listing protects the owner from optimistic catalog ratings and is the single most effective quality gate for this equipment class. (4.3)
4.4Each unit shall be factory run-tested before shipment in accordance with the manufacturer's standard production test procedure.
4.5Each unit shall be factory pressure-tested before shipment in accordance with the manufacturer's standard production test procedure.
4.6The installing contractor shall be experienced in water-loop heat pump installation and shall perform work in accordance with the manufacturer's published instructions.
NOTE ANSI/AHRI 600-2023 is the current controlling rating standard and supersedes the legacy ARI 320, AHRI 325, and AHRI 330 family. (5.1)
NOTE AHRI 600-2023 (I-P) was approved September 2023 and consolidates the older water-loop, ground-water, and ground-loop rating standards into one document. It establishes capacity and efficiency at defined entering-water and entering-air conditions using ASHRAE 37 as its laboratory test method. Specifying superseded ARI 320 or AHRI 325/330 certification confuses manufacturers and delays submittals. (5.2)
NOTE DOE federal minimum efficiency standards at 10 CFR 431, Subpart F set the regulatory floor and reference ISO 13256-1:1998 as their test basis. (5.3)
NOTE The federal test procedure incorporates ISO 13256-1, while AHRI 600-2023 uses ASHRAE 37. The two are functionally equivalent at the 86 °F water-loop cooling rating point but diverge at ground-loop conditions. Cite ANSI/AHRI 600-2023 as the primary performance reference and treat the DOE values as the minimum efficiency floor below which equipment may not be furnished. (5.4)
NOTE Rated capacity and efficiency shall be established at the ANSI/AHRI 600-2023 standard rating conditions unless the project schedule states otherwise. (5.5)
NOTE The AHRI 600-2023 standard rating point for cooling is 86 °F entering water temperature, 2.25 gpm/ton source flow, and 80 °F dry-bulb / 67 °F wet-bulb entering air. For heating it is 68 °F entering water temperature, 2.25 gpm/ton source flow, and 70 °F dry-bulb entering air. These are laboratory reference conditions; they are not the project design conditions and capacity must always be reconfirmed at the actual design EWT. (5.6)
NOTE Selected units shall meet the scheduled cooling and heating capacity at the project design entering-water temperatures, not merely at the AHRI rating point. (5.7)
NOTE A unit selected at the 86 °F cooling rating point can fall short of its scheduled capacity at a 90 °F loop peak, because cooling capacity drops as entering water gets warmer. Confirming capacity at the actual high-limit loop temperature is the most common selection error this standard guards against. Heating capacity is typically 80 % to 110 % of cooling capacity at rated conditions and likewise shifts with loop temperature. (5.8)
NOTE Cooling efficiency (EER) and heating efficiency (COP) shall equal or exceed the values scheduled, and in no case shall fall below the federal minimum and the applicable ASHRAE 90.1 minimum. (5.9)
NOTE The DOE federal floor at 10 CFR 431 is 12.2 EER for units below 17,000 Btuh and 13.0 EER for units from 17,000 to 135,000 Btuh, both with a 4.3 COP minimum for heating. ASHRAE 90.1-2022 sets the same floor for code compliance. ENERGY STAR and owner high-efficiency tiers run well above this; select the tier from the schedule, not from the floor. (5.10)
● Code minimum (ASHRAE 90.1 / 10 CFR 431)
○ ENERGY STAR water-loop tier (EER ≥ 14.1)
○ Owner high-efficiency tier (per schedule)
5.11Source-side and load-side flow rates shall be selected within the manufacturer's published operating range.
350450
Default: 400 cfm/ton
6 Unit Configuration and Capacity
NOTE The unit mounting orientation shall be selected to suit the architectural layout and the available service access. (6.1)
NOTE Vertical (closet or chase) units stack supply and return in a single cabinet and suit perimeter closets in hotels and apartments. Horizontal units mount above the ceiling and suit office and corridor plenums. Console units are low-profile floor-standing perimeter units for under-window placement. Through-the-wall units serve a single room from an exterior wall. The choice is driven by the architecture, not by the mechanical system, so it must be coordinated against the architectural drawings. (6.2)
● Vertical (closet / chase), upflow
○ Vertical (closet / chase), downflow
○ Horizontal (ceiling plenum)
○ Console (perimeter / under-window)
○ Through-the-wall
NOTE The unit type shall match the load-side distribution medium for the zone served. (6.3)
NOTE Water-to-air units deliver conditioned air and serve the great majority of zone applications. Water-to-water units deliver hydronic heating or cooling water and serve radiant panels, chilled beams, or secondary hydronic loops. Selecting the wrong type strands the distribution system, so confirm it against the zone's terminal devices. (6.4)
● Water-to-air
○ Water-to-water
NOTE Each unit's cooling and heating capacity shall be established by a block or zone load calculation, not by floor area rule of thumb. (6.5)
NOTE Capacity is set by an ACCA Manual J or equivalent block load for the zone. Typical hotel and apartment units fall in the 0.75 to 2 ton range; the equipment class spans 0.5 ton (6,000 Btuh) to 11.25 ton (135,000 Btuh) per unit. (6.6)
0.511.25
Default: 1.5 tons
○ Ductless console (blow-through)
● Short duct to grilles
○ Extended plenum (high static)
NOTE A dedicated outdoor air system (DOAS) should be provided to handle ventilation and latent load where the WSHP units handle sensible zone load. (6.7)
NOTE WSHP units are most effective sizing for sensible zone load while a separate DOAS unit delivers tempered, dehumidified outdoor air to satisfy ASHRAE 62.1 ventilation and the building's latent load. This pairing is increasingly the default in commercial and multifamily design and should be coordinated with the ventilation documents. Standalone cooling-tower and fluid-cooler selection for the loop is addressed in
Cooling Towers.
(6.8) 7 Refrigerant Circuit
NOTE The refrigerant circuit shall be factory-sealed, factory-charged, and leak-tested by the manufacturer; no field refrigerant work shall be required for a standard installation. (7.1)
NOTE WSHP units ship as sealed hermetic packages. Keeping field refrigerant work out of the standard installation preserves the certified charge and avoids the leak risk and skilled-labor cost of field brazing the refrigerant side. (7.2)
NOTE The refrigerant type shall be confirmed against the HFC phase-down schedule applicable at the project location before equipment is ordered. (7.3)
NOTE R-410A remains common across the installed base, but lower-GWP refrigerants such as R-32 and R-454B are replacing it in newer product lines. Several jurisdictions, including California under the AIM Act phase-down, restrict sales of higher-GWP equipment on a published timeline. Ordering R-410A equipment without checking the local schedule risks a unit that cannot legally be sold or installed when it arrives. (7.4)
NOTE Where multiple units share an enclosed space, the total refrigerant charge shall be evaluated against ASHRAE 15 and the building code for machinery-room classification and leak-detection requirements. (7.5)
NOTE ASHRAE 15 and IBC refrigeration provisions set charge limits per occupied volume and trigger machinery-room ventilation and refrigerant-detection alarms above defined thresholds. Multiple units in one mechanical room or chase can aggregate enough charge to cross those thresholds, so the analysis must be done rather than assumed away. (7.6)
8 Loop System and Conditioning
NOTE The system shall be a two-pipe water-loop arrangement with the boiler and heat-rejection equipment connected to a common loop. (8.1)
NOTE A reverse-return two-pipe loop is the most common arrangement because it self-balances and is forgiving of field variation. A direct-return two-pipe loop costs less to install but requires careful balancing valve selection at each unit. The choice trades first cost against balancing effort. (8.2)
8.3The loop piping arrangement (reverse-return or direct-return) shall be selected and documented in the contract documents.
● Two-pipe reverse-return
○ Two-pipe direct-return
NOTE The loop shall be maintained within its design temperature band by automatic control of the boiler and the heat-rejection equipment. (8.4)
NOTE The standard water-loop band is 60 °F to 90 °F. Common design setpoints are a 65 °F low limit that energizes the boiler and an 85 °F high limit that energizes the cooling tower or fluid cooler. A dead band between the two prevents simultaneous heating and rejection. (8.5)
NOTE A loop temperature reset or setpoint schedule shall be included in the contract documents so the controls contractor has a defined basis of control. (8.6)
NOTE Omitting the boiler and cooling-tower setpoint basis from the documents is a chronic source of RFIs, because the controls contractor finds no setpoint to program. Stating the low limit, high limit, and any reset strategy in the specification closes that gap before it becomes a field question. (8.7)
NOTE The loop fluid shall be plain water for loops maintained above the freezing range; a propylene glycol solution shall be provided only where loop or ambient conditions can approach freezing. (8.8)
NOTE A building recirculating loop held at 60 °F or above needs no freeze protection and runs on plain water, which preserves capacity and pumping efficiency. Propylene glycol is reserved for hybrid arrangements where some portion of the loop can approach or fall below 32 °F; glycol reduces capacity and increases pumping head, so it is not added without cause. (8.9)
● Plain water
○ Propylene glycol solution
NOTE The boiler and heat-rejection equipment shall be sized against the simultaneous loop load using a diversity factor, not the sum of every unit's peak. (8.10)
NOTE In a mixed-use building, heating and cooling zones rarely peak together, and the loop recovers heat internally. Sizing the boiler and tower for 100 % simultaneous load grossly oversizes both. A diversity factor of 60 % to 75 % is typical for mixed-use buildings. (8.11)
8.12A simultaneous-load diversity factor shall be applied and documented in the loop calculations.
● Gas-fired condensing boiler
○ Electric boiler
○ Heat-recovery boiler
○ Open cooling tower
● Closed-circuit fluid cooler
○ Hybrid evaporative fluid cooler
NOTE Each unit shall be provided with a balancing valve so that it receives its design loop flow. (8.13)
NOTE Without a balancing provision at each unit, the loop short-circuits to the path of least resistance and starves units at the hydraulic extremes. (8.14)
8.15The balancing valve scope responsibility shall be assigned in the contract documents so it is not lost between the mechanical and plumbing trades.
9 Two-Position Shutoff Valve
NOTE Each unit on a two-pipe loop shall be provided with a two-position automatic shutoff valve that closes when the compressor is off, per ASHRAE 90.1 Section 6.5.7. (9.1)
NOTE When a unit's compressor cycles off, leaving its loop circuit open lets water circulate through it for no benefit, wasting pump energy continuously across every idle unit. ASHRAE 90.1 Section 6.5.7 requires an automatic valve that isolates the off unit. Omitting it is both an energy-code violation and a permanent parasitic loss. (9.2)
9.3The valve actuator shall be a 24 VAC two-position actuator interlocked with the compressor so the valve is closed whenever the compressor is not running.
NOTE The submittal shall identify whether the two-position valve is factory-mounted by the unit manufacturer or field-mounted, and that responsibility shall be assigned in the contract documents. (9.4)
NOTE The valve can ship factory-mounted on the unit or be field-installed in the loop drop. Either is acceptable, but the documents must state which, or the valve falls between scopes and is omitted. Confirming factory-versus-field mounting on the submittal prevents that gap. (9.5)
● Factory-mounted by unit manufacturer
○ Field-mounted by installing contractor
10 Controls and Integration
NOTE Each unit shall be furnished with controls compatible with the project's control architecture. (10.1)
NOTE A standalone thermostat suits a simple installation. A unit-mounted BACnet or Modbus controller allows point-level monitoring and is the norm for managed commercial and hospitality buildings. Full BAS integration adds demand-controlled loop temperature reset and central scheduling. (10.2)
10.3The unit control level shall match the building's overall control strategy and the loop temperature reset basis stated in the contract documents.
○ Standalone thermostat
● BACnet unit controller
○ Modbus unit controller
○ Full BAS integration with loop reset
NOTE A desuperheater for domestic hot water heat recovery shall be provided only where the connection to the plumbing system is coordinated and shown. (10.4)
NOTE Many units offer a desuperheater that recovers compressor heat to preheat domestic hot water. The option is wasted if the connection port is left capped because the plumbing tie-in was never coordinated. Resolve the connection in design, or do not specify the option. (10.5)
● Not provided
○ Provided, connected to DHW system
11 Sound
NOTE Each unit shall meet a scheduled maximum NC level in the occupied space, stated at the scheduled airflow and external static pressure. (11.1)
NOTE Sound is critical in hotels and residences, where guestroom and bedroom NC targets of 25 to 35 are typical, while commercial office space tolerates NC 35 to 45. A bare NC number without the airflow and static-pressure test conditions is ambiguous and generates RFIs. (11.2)
11.3The equipment schedule shall state the NC test basis consistent with the AHRI 600-2023 sound test conditions.
11.4Compressor sound blankets and flexible duct and pipe connectors shall be provided where required to meet the scheduled NC level in noise-sensitive occupancies.
12 Electrical
NOTE Electrical characteristics and branch-circuit protection shall comply with NFPA 70 (NEC) Article 440 for hermetic refrigerant motor-compressors. (12.1)
NOTE NEC Article 440 governs minimum circuit ampacity and maximum overcurrent protection for the hermetic compressor in each unit. Branch circuits and disconnects shall be sized from the unit nameplate minimum circuit ampacity and maximum overcurrent protection, not from running amps. (12.2)
● 208 V / 1Φ / 60 Hz
○ 208 V / 3Φ / 60 Hz
○ 230 V / 1Φ / 60 Hz
○ 460 V / 3Φ / 60 Hz
12.3A unit-mounted or adjacent disconnecting means shall be provided for each unit as required by the NEC and the local jurisdiction.
13 Installation
NOTE Units shall be installed in accordance with the manufacturer's published instructions and with the service clearances shown on the approved submittal. (13.1)
NOTE Closet and chase installations are the most clearance-constrained. Units squeezed in without the filter-pull and compressor-access clearance the manufacturer requires become expensive to service for the life of the building. (13.2)
13.3The Engineer of Record shall confirm that required manufacturer service clearances are achievable within the architectural layout during design, before the clearance conflict reaches the field.
13.4Service access for filter replacement, coil cleaning, and compressor service shall be maintained at each unit per the manufacturer's clearance requirements.
13.5Loop, condensate, electrical, and air connections shall be made at the locations shown unit connection points. 13.6Each unit shall be installed with a condensate drain trapped and routed to an approved point of disposal.
13.7Vibration isolation shall be provided at unit hangers or bases as required to prevent structure-borne noise transmission in noise-sensitive occupancies.
14 Testing and Commissioning
NOTE After installation, the entering and leaving water temperature and water flow at each unit shall be measured and shall fall within 5 % of the design conditions. (14.1)
NOTE Field verification confirms that the loop actually delivers the design flow and temperature to each unit, which is what makes the certified capacity real on the project. A 5 % tolerance band on water temperature and flow is the practical acceptance criterion; units outside it indicate a balancing or sizing problem to resolve before acceptance. (14.2)
14.3Airflow at each unit shall be measured and balanced to the scheduled cfm.
14.4The two-position shutoff valve at each unit shall be verified to close when the compressor is commanded off.
14.5Loop temperature control shall be verified to maintain the loop within its design band by energizing the boiler at the low limit and the heat-rejection equipment at the high limit.
15 Delivery, Storage, and Handling
15.1Units shall be delivered in the manufacturer's original packaging with factory charge intact and shall be stored indoors, protected from weather and construction dust until installation.
15.2Units shall be kept upright and handled only at the manufacturer's designated lifting points to protect the sealed refrigerant circuit.
16 Warranty
NOTE The manufacturer shall warrant each unit against defects in materials and workmanship for the period stated below from the date of Substantial Completion. (16.1)
NOTE A one-year whole-unit warranty is the industry baseline. Extended compressor coverage of five years is widely available and commonly specified for equipment that is difficult to access after occupancy, such as ceiling-mounted units above finished spaces. (16.2)
17 Spare Parts
17.1The Contractor shall furnish the spare parts indicated below for owner stock.
17.1.1The Contractor shall furnish the following spare parts:
- One complete set of air filters for each unit size installed
- Spare two-position valve actuators in the quantity scheduled
- Manufacturer's recommended spare-parts list with current part numbers
☑ One set of air filters per unit size
☐ Spare two-position valve actuators
☑ Manufacturer's recommended spare-parts list