title: Wire Mesh Partitions
…132 unchanged lines
# Environmental and Service Conditions {toc}
−## The specified finish shall suit the service environment, because corrosion of an unsuitable coating is the most common premature failure of mesh partitions in wet or chemically aggressive spaces. {note}
+## The specified finish shall suit the service environment, because corrosion of an unsuitable coating is the most common premature failure of mesh partitions in wet or chemically aggressive spaces.
### Partitions in dry, conditioned interior spaces shall be furnished with a powder-coat finish unless otherwise indicated.
…45 unchanged lines
### Carbon steel wire shall comply with ASTM A510.
−### Welded wire mesh is the default for new construction because a cut welded panel stays intact, while a cut woven panel unravels; welded mesh shall be furnished where field cuts around columns, pipes, or other obstructions are required. {note}
+### Welded wire mesh is the default for new construction because a cut welded panel stays intact, while a cut woven panel unravels; welded mesh shall be furnished where field cuts around columns, pipes, or other obstructions are required.
−### Woven wire mesh may be furnished where indicated for traditional appearance or where no field cutting is required. {note}
−
```datasheet
label: Wire mesh type
…5 unchanged lines
```
+### Woven wire mesh may be furnished where indicated for traditional appearance or where no field cutting is required. {note}
+
## Mesh Opening and Gauge {toc}
−### The mesh opening shall be as scheduled below; a smaller opening increases security and reduces reach-through but also reduces visibility and airflow. {note}
+### The mesh opening shall be as scheduled below; a smaller opening increases security and reduces reach-through but also reduces visibility and airflow.
### High-security enclosures shall be furnished with a 1 in. × 1 in. or smaller opening to resist reach-through and tool insertion.
…21 unchanged lines
## Panel Frame {toc}
−### Mesh shall be framed on all four edges in steel angle or tube to keep the panel rigid and to provide the bolted connection to adjacent panels and posts. {note}
+### Mesh shall be framed on all four edges in steel angle or tube to keep the panel rigid and to provide the bolted connection to adjacent panels and posts.
### Normal-duty panels shall be framed in not lighter than 1-1/4 in. × 1-1/4 in. × 1/8 in. steel angle.
…15 unchanged lines
## Panel Dimensions {toc}
−### Standard panel width shall be 2 ft to 4 ft, with 3 ft typical; panel height shall not exceed 12 ft in a single panel, and panels shall be stacked to a maximum assembly height of 20 ft. {note}
+### Standard panel width shall be 2 ft to 4 ft, with 3 ft typical; panel height shall not exceed 12 ft in a single panel, and panels shall be stacked to a maximum assembly height of 20 ft.
```datasheet
…19 unchanged lines
# Posts {toc}
−## Posts carry the panel loads to the floor and resist the lateral loads on the partition; post size shall increase with assembly height. {note}
+## Posts carry the panel loads to the floor and resist the lateral loads on the partition; post size shall increase with assembly height.
### Posts for assemblies up to 12 ft tall shall be not lighter than 2 in. × 2 in. × 14 ga steel tube.
…31 unchanged lines
# Connection Hardware {toc}
−## Panels shall be bolted to posts and to adjacent panels with plated steel hardware so the assembly can be erected and reconfigured without welding in the field. {note}
+## Panels shall be bolted to posts and to adjacent panels with plated steel hardware so the assembly can be erected and reconfigured without welding in the field.
### Panel-to-post and panel-to-panel connections shall use not smaller than 3/8 in. × 3 in. plated hex bolts and nuts at each framing intersection.
…16 unchanged lines
# Enclosure Configuration {toc}
−## The number of sides and the top condition shall be selected to match the security requirement; an open-top enclosure can be defeated by climbing over and is unacceptable for security-critical uses. {note}
+## The number of sides and the top condition shall be selected to match the security requirement; an open-top enclosure can be defeated by climbing over and is unacceptable for security-critical uses.
### Security-critical enclosures shall be fully enclosed with ceiling closure panels of the same mesh and frame as the wall panels.
…27 unchanged lines
# Doors {toc}
−## Door type and width shall suit the traffic through the opening; a swing door in a busy forklift aisle is a safety hazard and a sliding door shall be furnished for forklift- or pallet-jack-accessed enclosures. {note}
+## Door type and width shall suit the traffic through the opening; a swing door in a busy forklift aisle is a safety hazard and a sliding door shall be furnished for forklift- or pallet-jack-accessed enclosures.
### Personnel doors shall be not less than 3 ft wide × 7 ft tall single swing unless otherwise indicated.
…40 unchanged lines
# Locking Hardware {toc}
−## The locking method shall be stated in the documents and shall not be left to the Contractor's selection, because the lock determines the security level and must be coordinated with the building's door hardware and access-control work. {note}
+## The locking method shall be stated in the documents and shall not be left to the Contractor's selection, because the lock determines the security level and must be coordinated with the building's door hardware and access-control work.
### Locking hardware shall be coordinated with the Door Hardware Section so that keying, access control, and electrified power are consistent across the project.
…18 unchanged lines
# Pass-Through Windows {toc}
−## A pass-through window allows controlled transfer of small items without opening the main door; it shall be furnished only where indicated. {note}
+## A pass-through window allows controlled transfer of small items without opening the main door; it shall be furnished only where indicated.
### Pass-through windows shall be furnished with a hinged or sliding mesh closure and a shelf where indicated, and the closure shall be lockable where the enclosure is security-critical.
…11 unchanged lines
# Finish {toc}
−## Finish color shall be specified and coordinated with the Owner's color standards; an unspecified finish leads the Contractor to select the cheapest available color. {note}
+## Finish color shall be specified and coordinated with the Owner's color standards; an unspecified finish leads the Contractor to select the cheapest available color.
### Powder-coat finish shall be not less than 2 mil dry film thickness, measured per ASTM D7091.
…33 unchanged lines
# Coordination {toc}
−## Wire mesh partitions intersect several other trades, and the most common field problems come from missed coordination rather than from the partition itself; the layout shall be coordinated before fabrication. {note}
+## Wire mesh partitions intersect several other trades, and the most common field problems come from missed coordination rather than from the partition itself; the layout shall be coordinated before fabrication.
### The partition layout shall preserve the working space in front of electrical equipment required by NEC Article 110.26 and OSHA 29 CFR 1910.303; cage panels and door swings shall not encroach on the required clear depth.
…23 unchanged lines
# Installation {toc}
−## Partitions shall be installed plumb, level, and true to line, with panels tight to posts and uniform mesh alignment across the assembly. {note}
+## Partitions shall be installed plumb, level, and true to line, with panels tight to posts and uniform mesh alignment across the assembly.
### Posts shall be set plumb and anchored to the substrate with the specified anchors at the embedment and torque given in the manufacturer's printed installation instructions.
…49 unchanged lines
- Touch-up finish (matching color)
```