Below-Grade Waterproofing
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 9
to Rev 10
in Below-Grade Waterproofing.
---
title: Below-Grade Waterproofing
…107 unchanged lines
- "Written material compatibility confirmation"
- "Installer qualification statement"
+constraint: all_of
```
…27 unchanged lines
- "Manufacturer field representative reports"
- "Field watertightness test reports"
+constraint: all_of
```
…21 unchanged lines
- "Installer's written workmanship warranty made out to the Owner"
- "Indexed photographic record of detail locations"
+constraint: all_of
```
…18 unchanged lines
```datasheet
−label: Minimum Installer Experience
+label: Installer Experience
type: range
unit: 'years'
…2 unchanged lines
setpoints: [0, 2, 3, 5, 10, 20]
default: 5
+constraint: min
```
…19 unchanged lines
```datasheet
−label: Manufacturer Field Representative — Minimum Site Visits
+label: Manufacturer Field Representative — Site Visits
type: range
unit: 'visits'
min: 0
max: 12
setpoints: [0, 1, 2, 4, 6, 12]
+constraint: min
```
…33 unchanged lines
drawing_ref: "geotechnical investigation report"
default: deferred
+constraint: min
```
…80 unchanged lines
```datasheet
−label: Self-Adhering Sheet Membrane — Minimum Thickness on Walls
+label: Self-Adhering Sheet Membrane — Thickness on Walls
type: range
unit: 'mil'
min: 40
max: 100
setpoints: [40, 50, 60, 80, 100]
+constraint: min
```
## The minimum thickness of self-adhering sheet membrane beneath slabs shall be as indicated in the datasheet.
```datasheet
−label: Self-Adhering Sheet Membrane — Minimum Thickness Beneath Slabs
+label: Self-Adhering Sheet Membrane — Thickness Beneath Slabs
type: range
unit: 'mil'
min: 40
max: 120
setpoints: [40, 60, 80, 100, 120]
+constraint: min
```
…21 unchanged lines
```datasheet
−label: Cold Fluid-Applied Membrane — Minimum Dry-Film Thickness
+label: Cold Fluid-Applied Membrane — Dry-Film Thickness
type: range
unit: 'mil'
…2 unchanged lines
setpoints: [40, 60, 80, 100, 125]
default: 60
+constraint: min
```
…8 unchanged lines
setpoints: [1, 2, 3]
default: 2
+constraint: exact
```
…26 unchanged lines
```datasheet
−label: Hot-Applied Rubberized Asphalt — Minimum Total Applied Thickness
+label: Hot-Applied Rubberized Asphalt — Total Applied Thickness
type: range
unit: 'mil'
…2 unchanged lines
setpoints: [90, 125, 180, 215, 250]
default: 215
+constraint: min
```
…19 unchanged lines
```datasheet
−label: Sodium Bentonite Composite — Minimum Bentonite Mass per Unit Area
+label: Sodium Bentonite Composite — Bentonite Mass per Unit Area
type: range
unit: 'lb/ft²'
…2 unchanged lines
setpoints: [0.75, 1.0, 1.25, 1.5]
default: 1.0
+constraint: min
```
…15 unchanged lines
```datasheet
−label: Pre-Applied Bonded Sheet Membrane — Minimum Total Thickness
+label: Pre-Applied Bonded Sheet Membrane — Total Thickness
type: range
unit: 'mil'
min: 30
max: 100
setpoints: [30, 40, 50, 60, 80, 100]
+constraint: min
```
## The minimum peel adhesion of the pre-applied bonded sheet membrane to concrete cast against it shall be as indicated in the datasheet, tested in accordance with ASTM D903 after water immersion.
```datasheet
−label: Pre-Applied Bonded Sheet Membrane — Minimum Peel Adhesion to Cast Concrete
+label: Pre-Applied Bonded Sheet Membrane — Peel Adhesion to Cast Concrete
type: range
unit: 'lbf/in'
min: 2
max: 15
step: 1
+constraint: min
```
…26 unchanged lines
setpoints: [1, 2, 3]
default: 2
+constraint: exact
```
…13 unchanged lines
```datasheet
−label: Concrete Substrate — Minimum Age Before Membrane Application
+label: Concrete Substrate — Age Before Membrane Application
type: range
unit: 'days'
…2 unchanged lines
setpoints: [0, 3, 7, 14, 21, 28]
default: 7
+constraint: min
```
…40 unchanged lines
```datasheet
−label: Maximum Substrate Surface Irregularity Under a 10 ft Straightedge
+label: Substrate Surface Irregularity Under a 10 ft Straightedge
type: range
unit: 'in'
…2 unchanged lines
setpoints: [0.125, 0.25, 0.375, 0.5]
default: 0.25
+constraint: max
```
…30 unchanged lines
```datasheet
−label: Minimum Air and Surface Temperature During Application
+label: Air and Surface Temperature During Application
type: range
unit: '°F'
min: 0
max: 60
setpoints: [0, 20, 25, 32, 40, 50, 60]
+constraint: min
```
…9 unchanged lines
```datasheet
−label: Maximum Membrane Exposure Before Cover
+label: Membrane Exposure Before Cover
type: range
unit: 'days'
min: 1
max: 180
setpoints: [1, 7, 14, 30, 60, 90, 180]
+constraint: max
```
…7 unchanged lines
```datasheet
−label: Sheet Membrane Minimum Side and End Lap
+label: Sheet Membrane Side and End Lap
type: range
unit: 'in'
min: 2
max: 12
setpoints: [2, 2.5, 3, 4, 6, 12]
+constraint: min
```
…30 unchanged lines
drawing_ref: "wall sections in the contract documents"
default: deferred
+constraint: exact
```
…90 unchanged lines
```datasheet
−label: Protection Course — Minimum Thickness
+label: Protection Course — Thickness
type: range
unit: 'in'
min: 0.125
max: 2
setpoints: [0.125, 0.25, 0.375, 0.5, 1, 1.5, 2]
+constraint: min
```
…29 unchanged lines
```datasheet
−label: Wall Drainage Composite — Minimum In-Plane Flow Rate
+label: Wall Drainage Composite — In-Plane Flow Rate
type: range
unit: 'gal/min per ft of width'
min: 1
max: 40
step: 1
+constraint: min
```
…24 unchanged lines
- "Flood test of horizontal waterproofing"
- "Visual inspection of the completed membrane before cover"
+constraint: all_of
```
…7 unchanged lines
```datasheet
−label: Flood Test — Minimum Duration
+label: Flood Test — Duration
type: range
unit: 'h'
…2 unchanged lines
setpoints: [8, 12, 24, 48, 72, 96]
default: 24
+constraint: min
```
…8 unchanged lines
setpoints: [1, 2, 3, 4]
default: 2
+constraint: min
```
…41 unchanged lines
```datasheet
−label: Maximum Backfill Lift Thickness Adjacent to Waterproofed Walls
+label: Backfill Lift Thickness Adjacent to Waterproofed Walls
type: range
unit: 'in'
min: 6
max: 24
setpoints: [6, 8, 12, 18, 24]
+constraint: max
```
## The minimum standoff distance within which compaction shall be performed by hand-operated equipment rather than by ride-on or towed equipment shall be as indicated in the datasheet.
```datasheet
−label: Minimum Standoff Distance for Ride-On Compaction Equipment
+label: Standoff Distance for Ride-On Compaction Equipment
type: range
unit: 'ft'
min: 0
max: 20
setpoints: [0, 3, 5, 10, 20]
+constraint: min
```
…31 unchanged lines
setpoints: [1, 2, 5, 10, 15, 20]
default: 5
+constraint: min
```
…8 unchanged lines
setpoints: [1, 2, 3, 5, 10]
default: 2
+constraint: min
```
…9 unchanged lines
## The Contractor shall bear the cost of repairing damage to interior finishes, stored contents, and building systems caused by water entering through a defect covered by the warranty, up to the limits stated in the Contract Documents.