Compressed Air Systems
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 3
to Rev 4
in Compressed Air Systems.
---
title: Compressed Air Systems
…27 unchanged lines
default:
- "Shop and pneumatic tool air"
+constraint: all_of
```
…101 unchanged lines
- "Distribution piping and outlet product data"
- "Electrical coordination data"
+constraint: all_of
```
…22 unchanged lines
- "Manufacturer's installation instructions"
- "Pressure test plan"
+constraint: all_of
```
…32 unchanged lines
- "As-built drawings"
- "Training record"
+constraint: all_of
```
…244 unchanged lines
step: 1
default: deferred
+constraint: exact
```
…9 unchanged lines
step: 1
default: deferred
+constraint: exact
```
…22 unchanged lines
setpoints: [30, 40, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200]
default: deferred
+constraint: exact
```
…9 unchanged lines
step: 1
default: derived
+constraint: exact
```
…79 unchanged lines
```datasheet
−label: Maximum Compressor Sound Pressure Level at 1 m
+label: Compressor Sound Pressure Level at 1 m
type: range
unit: dBA
min: 60
max: 95
setpoints: [60, 65, 70, 75, 80, 85, 90, 95]
+constraint: max
```
…119 unchanged lines
default:
- "Coalescing filter upstream of the dryer"
+constraint: all_of
```
…36 unchanged lines
step: 10
default: deferred
+constraint: exact
```
…169 unchanged lines
```datasheet
−label: Maximum Distribution Pressure Drop
+label: Distribution Pressure Drop
type: range
unit: psi
min: 1
max: 10
setpoints: [1, 2, 3, 4, 5, 7.5, 10]
+constraint: max
```
…3 unchanged lines
```datasheet
−label: Maximum Air Velocity in Mains
+label: Air Velocity in Mains
type: range
unit: ft/s
min: 10
max: 40
setpoints: [10, 15, 20, 25, 30, 40]
+constraint: max
```
…9 unchanged lines
max: 100
setpoints: [0, 10, 25, 50, 100]
+constraint: min
```
…159 unchanged lines
- "Compressor common alarm"
- "Low header pressure"
+constraint: all_of
```
…12 unchanged lines
- "Dew point transmitter at the dryer outlet"
- "Header pressure transmitter to the building automation system"
+constraint: all_of
```
…50 unchanged lines
setpoints: [1.1, 1.2, 1.25, 1.5]
default: derived
+constraint: exact
```
…7 unchanged lines
max: 24
setpoints: [0.5, 1, 2, 4, 8, 24]
+constraint: min
```
…9 unchanged lines
```datasheet
−label: Maximum System Leakage
+label: System Leakage
type: range
unit: '% of installed capacity'
min: 0
max: 25
setpoints: [0, 2, 5, 10, 15, 20, 25]
+constraint: max
```
…21 unchanged lines
default:
- "Pressure dew point at the dryer outlet by ISO 8573-3"
+constraint: all_of
```
…14 unchanged lines
setpoints: [0, 2, 4, 8, 16]
default: 4
+constraint: min
```
…18 unchanged lines
setpoints: [1, 2, 3, 5, 10]
default: 1
+constraint: min
```
…7 unchanged lines
max: 10
setpoints: [0, 2, 5, 10]
+constraint: min
```
…22 unchanged lines
- "Lubricant and oil filter for the first change of each oil-injected compressor"
- "One set of filter elements for each treatment train filter"
+constraint: all_of
```
## Spare parts shall be the same make and model as the installed items, delivered in their original packaging, and labeled with the equipment they serve.