Conductors and Cables

Read revision 7

Revision 7 · Oct 12, 2026 +11 −3

Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 6 to Rev 7 in Conductors and Cables.
---
title: Conductors and Cables
…77 unchanged lines
- "Voltage drop calculations for feeders and long branch circuits"
- "Connector and splice product data"
+constraint: all_of
```
…17 unchanged lines
- "As-built conductor schedule"
- "Warranty documentation"
+constraint: all_of
```
…244 unchanged lines
setpoints: [600, 1000]
default: 600
+constraint: min
```
…48 unchanged lines
setpoints: [60, 75, 90]
default: 75
+constraint: exact
```
…88 unchanged lines
```datasheet
−label: Maximum Branch Circuit Voltage Drop
+label: Branch Circuit Voltage Drop
type: range
unit: '%'
…3 unchanged lines
setpoints: [1, 2, 3, 4, 5]
default: 3
+constraint: max
```
### The maximum permitted combined feeder and branch circuit voltage drop, measured at the farthest outlet under design full load, shall be as indicated in the datasheet.
```datasheet
−label: Maximum Combined Feeder + Branch Circuit Voltage Drop
+label: Combined Feeder + Branch Circuit Voltage Drop
type: range
unit: '%'
…3 unchanged lines
setpoints: [2, 3, 4, 5]
default: 5
+constraint: max
```
…329 unchanged lines
```datasheet
−label: Minimum Acceptable Insulation Resistance
+label: Acceptable Insulation Resistance
type: range
unit: MΩ
…3 unchanged lines
setpoints: [50, 100, 250, 500, 1000]
default: 100
+constraint: min
```
…23 unchanged lines
- "Short-circuit check on all feeders"
- "Short-circuit check on life-safety circuits"
+constraint: all_of
```
…51 unchanged lines
## Where the parties disagree whether a warranty-period failure results from workmanship, product defect, or building conditions such as moisture infiltration or chemical attack, the Engineer of Record shall make the initial determination.