Distributed Antenna Systems
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 3
to Rev 4
in Distributed Antenna Systems.
---
title: Distributed Antenna Systems
…100 unchanged lines
- "Head-end equipment room layout"
- "Carrier approval or acknowledgment of the RF design"
+constraint: all_of
```
…30 unchanged lines
- "Acceptance test procedure"
- "Monitoring configuration plan"
+constraint: all_of
```
…32 unchanged lines
- "Operation and maintenance data, credentials, and warranty certificate"
- "Spare parts receipt"
+constraint: all_of
```
…89 unchanged lines
- "Dedicated branch circuits at each carrier's rack position"
- "Conduit or innerduct from the entrance facility to each carrier's rack position for backhaul"
+constraint: all_of
```
…49 unchanged lines
max: 55
setpoints: [40, 45, 50, 55]
+constraint: min
```
…124 unchanged lines
- "1900 MHz PCS (Bands 2 and 25)"
- "1700/2100 MHz AWS (Bands 4 and 66, n66)"
+constraint: all_of
```
…18 unchanged lines
setpoints: [-95, -90, -85, -80, -75]
default: -85
+constraint: min
```
…16 unchanged lines
setpoints: [90, 95, 98, 99]
default: 95
+constraint: min
```
…9 unchanged lines
```datasheet
−label: Minimum Downlink Signal-to-Interference-plus-Noise Ratio
+label: Downlink Signal-to-Interference-plus-Noise Ratio
type: range
unit: dB
min: 0
max: 15
setpoints: [0, 3, 5, 10, 15]
+constraint: min
```
…58 unchanged lines
default:
- "SNMP traps to the Owner's network monitoring system"
+constraint: all_of
```
…19 unchanged lines
setpoints: [20, 24, 27, 30, 33, 37, 40, 43]
default: derived
+constraint: exact
```
…9 unchanged lines
```datasheet
−label: Maximum System Uplink Noise Figure
+label: System Uplink Noise Figure
type: range
unit: dB
min: 3
max: 8
setpoints: [3, 4, 5, 6, 8]
+constraint: max
```
…33 unchanged lines
max: 480
setpoints: [0, 15, 30, 60, 120, 240, 480]
+constraint: min
```
…122 unchanged lines
```datasheet
−label: Maximum Passive Intermodulation of Passive Components
+label: Passive Intermodulation of Passive Components
type: range
unit: dBc
…2 unchanged lines
setpoints: [-160, -155, -153, -150, -140]
default: -150
+constraint: max
```
…51 unchanged lines
```datasheet
−label: Maximum Voltage Standing Wave Ratio of Installed Coaxial Runs
+label: Voltage Standing Wave Ratio of Installed Coaxial Runs
type: range
unit: ratio
min: 1.2
max: 1.5
setpoints: [1.2, 1.3, 1.4, 1.5]
+constraint: max
```
…116 unchanged lines
max: 5
setpoints: [1, 2, 3, 5]
+constraint: min
```
…21 unchanged lines
max: 10
setpoints: [0, 2, 5, 10]
+constraint: min
```
…3 unchanged lines
## Spare parts shall be turned over against a written inventory signed by the Owner's representative, and the inventory shall be included in the closeout submittals.