Distributed Antenna Systems

Read revision 5

Revision 5 · Oct 19, 2026 +2 −2

Remake batch 25 and its neighbor re-points, batch 24 where missing, and the adopted-electrical-code parameter: brought in line with the authoring repository
Showing changes from Rev 4 to Rev 5 in Distributed Antenna Systems.
---
title: Distributed Antenna Systems
…554 unchanged lines
### The head-end equipment shall be supplied from dedicated branch circuits as indicated on [[drawing: the head-end equipment room layout]], with no other load on any circuit serving the head-end.
−### Each circuit breaker serving the head-end or a remote unit power supply shall be identified at the panelboard as serving the DAS, with the legend "DAS: DO NOT DE-ENERGIZE WITHOUT NOTICE TO THE OWNER", in accordance with [[sync/electrical-identification]].
+### Each circuit breaker serving the head-end or a remote unit power supply shall be identified at the panelboard as serving the DAS, with the legend "DAS: DO NOT DE-ENERGIZE WITHOUT NOTICE TO THE OWNER", in accordance with [[sync/equipment-labeling]].
### Each circuit breaker serving the head-end or a remote unit power supply shall be furnished with a handle lock-on device.
…383 unchanged lines
### Each remote unit and head-end unit shall carry a label stating that it is part of the DAS and giving the Owner's contact for service.
−### Equipment nameplates and circuit identification at the panelboards shall comply with [[sync/electrical-identification]].
+### Equipment nameplates and circuit identification at the panelboards shall comply with [[sync/equipment-labeling]].
## Head-End and Remote Unit Mounting {toc}
…62 unchanged lines
## Spare parts shall be turned over against a written inventory signed by the Owner's representative, and the inventory shall be included in the closeout submittals.

View current revision