Door Hardware

Read revision 3

Revision 3 · Oct 2, 2026 +1106 −419

Remade for neutrality: every choice explained, project facts as parameters, scope boundaries linked both ways
Showing changes from Rev 2 to Rev 3 in Door Hardware.
---
title: Door Hardware
category: Architectural / Openings
−toc_depth: 3
description: >
− When to use: Specifying, furnishing, and installing finish hardware for swinging door openings in commercial, institutional, and light-industrial construction. Covers hardware sets as the organizing framework; hinges and pivots; cylindrical, mortise, and bored locksets; rim, mortise, and vertical-rod exit devices including fire exit hardware; door closers and hold-opens; stops, holders, and protection plates; thresholds, weatherstripping, and gasketing; coordinators and flushbolts for pairs; finish selection; keying hierarchy and master-key schedules; electrified hardware items (electric strikes, electrified locks, electromagnetic hold-opens, power transfers) at the hardware-set level; ADA / ICC A117.1 height, force, and handle compliance; DHI location templates; and field verification. Use it where the door leaf and frame are specified elsewhere.
− Not intended for: Door leaves and hollow metal frames (see [[sync/doors-frames-and-hardware]], [[sync/exterior-doors-and-frames]], [[sync/wood-doors]]); access control head-end, card readers, controllers, and power supplies (see [[sync/access-control-systems]]); automatic pedestrian door operators; aluminum storefront entrance hardware (see [[sync/aluminum-entrances-and-storefronts]]); interior frameless glass pivots and patch fittings (see [[sync/interior-glazing]]); overhead coiling and sectional door hardware (see [[sync/overhead-coiling-doors]], [[sync/sectional-overhead-doors]]); and detention or ballistic-rated security hardware.
+ When to use: Finish hardware for swinging door openings specified and furnished as its own package, separate from the door leaves and the frames, in commercial, institutional, educational, healthcare, hospitality, and multi-family residential work. Covers the hardware schedule and numbered hardware sets as the coordination instrument; ANSI/BHMA operational grades; butt hinges, continuous hinges, pivots, and self-closing hinges; bored, mortise, interconnected, and tubular locksets and latches, auxiliary locks, and trim; cylinders, interchangeable cores, keyway control, keying hierarchy, construction keying, and key control; panic hardware and fire exit hardware; door closers, overhead stops and holders, and fire-alarm-released hold-open devices; door stops, silencers, protection plates, and push and pull trim; coordinators, flush bolts, and removable mullions at pairs; thresholds, weatherstripping, smoke and acoustic gasketing, intumescent edge seals furnished under the hardware sets, and automatic door bottoms; patch fittings, rails, pivots, locks, and closers for all-glass swing doors in interior partitions; electrified locks, strikes, exit devices, electromagnetic locks, delayed egress devices, and the power transfer into the leaf; low-energy power-operated and power-assist swing door operators under ANSI/BHMA A156.19 with their knowing-act actuators; hardware finishes; accessible-opening obligations; installation, adjustment, field verification, fire door acceptance inspection, warranty, and spare parts.
+ Not intended for: Hollow metal doors and frames and their factory reinforcement for hardware (see [[sync/exterior-doors-and-frames]]); wood door leaves and their machining, blocking, and raceway (see [[sync/wood-doors]]); swinging openings bought as one combined supply of door, frame, and hardware together (see [[sync/doors-frames-and-hardware]]); access control controllers, credential readers, request-to-exit devices, door position switches, power supplies, cabling, and programming (see [[sync/access-control-systems]]); the fire alarm control unit and the release circuit that drops hold-open devices and electrified locks on alarm (see [[sync/fire-alarm-systems]]); aluminum entrance doors and the hardware furnished with them (see [[sync/aluminum-entrances-and-storefronts]]); interior partition framing, borrowed lites, and the tempered or laminated panel of a frameless swing door, which is sized to the thickness the hardware selected here is rated for (see [[sync/interior-glazing]]); frameless all-glass entrance assemblies furnished as a system, the glass panels together with their patch fittings, rails, pivots, and closers (see [[sync/all-glass-entrances]]); full-energy power-operated sliding, swing, and folding entrance systems under ANSI/BHMA A156.10 with their operators, sensors, and guide rails (see [[sync/automatic-entrance-doors]]); overhead coiling doors (see [[sync/overhead-coiling-doors]]) and sectional overhead doors (see [[sync/sectional-overhead-doors]]); in-wall backing for wall stops and holders (see [[sync/gypsum-board-assemblies]]); code-required egress signage (see [[sync/signage-and-egress-markings]]); and detention, ballistic, blast, and forced-entry-rated hardware, which no standard in this library covers and which requires project-specific engineered design.
---
# Scope {toc}
−## This standard governs the selection, furnishing, and installation of finish hardware for swinging door openings, organized as numbered hardware sets, across commercial, institutional, and light-industrial occupancies. {note}
+## This standard governs the selection, furnishing, and installation of finish hardware for swinging door openings where the hardware is specified and bought as its own package, apart from the door leaves and the frames. It is organized around the hardware schedule and its numbered hardware sets, and it covers the hanging, latching, locking, closing, holding, protecting, sealing, and electrifying of the opening. {note}
−## The opening is a coordinated assembly whose parts are specified by three complementary standards, and this is the hardware-only complement. The door leaf, the frame, gauges, cores, and fire-label assembly requirements are governed by [[sync/doors-frames-and-hardware]] for combined opening packages, by [[sync/exterior-doors-and-frames]] for exterior leaves, and by [[sync/wood-doors]] for wood leaves. This standard is used when the hardware is specified separately from the door and frame manufacturing, which is common on larger projects where a hardware consultant authors the sets. {note}
+## The furnished work shall comprise every hardware item the hardware schedule assigns to an opening, the cylinders and keys, the fasteners and templates for that hardware, the power transfer devices and the electrified hardware at the opening, and the installation and adjustment of all of it.
−## Hardware sets shall be the organizing framework, with one numbered set assigned to each distinct opening type and every opening on the door schedule referencing exactly one set.
+## The leaves and the frames are separate subjects. Hollow metal doors and frames, with their factory reinforcement for this hardware, are governed by [[sync/exterior-doors-and-frames]]. Wood leaves, with their machining, blocking, and raceway, are governed by [[sync/wood-doors]]. Where the door, the frame, and the hardware are bought together as one coordinated supply, [[sync/doors-frames-and-hardware]] applies in place of this standard. {note}
−## Where a single opening is described by both this standard and a door or frame standard, the more specific requirement for that component shall govern, and conflicts shall be resolved by the Architect in writing.
+## Electrified hardware furnished under this standard stops at the opening. The controllers, credential readers, request-to-exit devices, door position switches, power supplies, cabling, and programming that decide who may pass are governed by [[sync/access-control-systems]], and the fire alarm control unit and the release circuit that drops hold-open devices and electrified locks on alarm are governed by [[sync/fire-alarm-systems]]. {note}
−## Electrified hardware items shall be specified in this standard at the product and hardware-set level only; their power supplies, conduit, raceway, and system programming are governed by [[sync/access-control-systems]] and shall be coordinated with that work and with [[sync/fire-alarm-systems]].
+## All-glass swing doors hung in interior glass partitions take their patch fittings, rails, pivots, locks, and closers from this standard. The tempered or laminated panel of that door, its thickness, and its edge work are governed by [[sync/interior-glazing]]. Frameless all-glass entrance assemblies furnished as a system, the glass panels together with their fittings and closers, are governed by [[sync/all-glass-entrances]]. {note}
−## Related standards {note}
+## Low-energy power-operated and power-assist swing door operators are hardware on the opening and are specified here with the closers they replace. Full-energy automatic entrances that open on approach, with their operators, sensors, and guide rails, are governed by [[sync/automatic-entrance-doors]]. Detention, ballistic, blast, and forced-entry-rated hardware has no standard in this library and is specified by project-specific engineered design outside this standard. {note}
−### The following standards carry adjacent scope and are commonly coordinated with this work: {note}
−- [[sync/doors-frames-and-hardware]] — combined opening packages where leaf, frame, and hardware are specified together.
−- [[sync/exterior-doors-and-frames]] and [[sync/wood-doors]] — door leaf manufacturing this standard relies on for prep and reinforcement.
−- [[sync/access-control-systems]] — head-end equipment and low-voltage power for electrified hardware specified here.
−- [[sync/aluminum-entrances-and-storefronts]] and [[sync/interior-glazing]] — glazing-integral hardware excluded here.
−- [[sync/fire-alarm-systems]] — release signal for electromagnetic hold-opens.
−- [[sync/gypsum-board-assemblies]] — wall backing and blocking for wall-mounted stops and magnetic holders.
−- [[sync/overhead-coiling-doors]] and [[sync/sectional-overhead-doors]] — non-swinging doors with their own hardware.
+## The Contractor shall reconcile the hardware schedule against the door schedule, the frame submittal, and the door submittal before any hardware is procured and before any frame is released for fabrication.
+## Frame preparation for hinges, strikes, closers, and exit devices is punched and reinforced at the factory from the hardware templates. A hardware change discovered after the frames are built means field welding on a labeled frame, a replacement frame, or a non-conforming opening, which is why the reconciliation sits ahead of procurement rather than ahead of installation. {note}
+
+## Where a requirement of this standard and a requirement of the door or frame standard both address the same component at one opening, the Architect shall resolve the conflict in writing before the component is fabricated.
+
# Referenced Standards {toc}
−## Hardware, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited or a more recent edition is mandated by the authority having jurisdiction.
+## Hardware, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
## Where referenced standards conflict, the more stringent requirement shall govern unless the Architect directs otherwise in writing.
+## Hardware at fire-rated openings shall comply with the edition of the fire test standard under which the door assembly is listed, and [[parameter: adopted-building-code]] governs which opening protective rating and which egress provisions apply at each opening.
+
| Standard | Title |
|----------|-------|
−| ANSI/BHMA A156.1-2021 | Standard for Butts and Hinges |
−| ANSI/BHMA A156.2-2022 | Locks, Latches, and Bolts |
−| ANSI/BHMA A156.3-2025 | Exit Devices |
−| ANSI/BHMA A156.4-2024 | Door Closers and Pivots |
−| ANSI/BHMA A156.13-2023 | Standard for Mortise Locks and Latches |
−| ANSI/BHMA A156.18-2023 | Materials and Finishes |
−| ANSI/BHMA A156.21-2021 | Standard for Thresholds |
−| ANSI/BHMA A156.22-2022 | Standard for Door Gasketing and Edge Seal Systems |
−| ANSI/BHMA A156.28-2023 | Standard for Cylinder and Input Devices for Locks |
−| NFPA 80 | Standard for Fire Doors and Other Opening Protectives (2025 Edition) |
−| NFPA 101 | Life Safety Code (2024 Edition) |
−| IBC Chapter 10 | International Building Code — Means of Egress (2024 Edition) |
−| ICC A117.1-2017 | Accessible and Usable Buildings and Facilities |
−| UL 305 | Standard for Panic Hardware |
+| ANSI/BHMA A156.1 | Butts and Hinges |
+| ANSI/BHMA A156.2 | Bored and Preassembled Locks and Latches |
+| ANSI/BHMA A156.3 | Exit Devices |
+| ANSI/BHMA A156.4 | Door Controls, Closers |
+| ANSI/BHMA A156.5 | Cylinders and Input Devices for Locks |
+| ANSI/BHMA A156.6 | Architectural Door Trim |
+| ANSI/BHMA A156.7 | Template Hinge Dimensions |
+| ANSI/BHMA A156.8 | Door Controls, Overhead Stops and Holders |
+| ANSI/BHMA A156.10 | Power Operated Pedestrian Doors |
+| ANSI/BHMA A156.12 | Interconnected Locks and Latches |
+| ANSI/BHMA A156.13 | Mortise Locks and Latches |
+| ANSI/BHMA A156.15 | Release Devices, Closer Holder, Electromagnetic and Electromechanical |
+| ANSI/BHMA A156.16 | Auxiliary Hardware |
+| ANSI/BHMA A156.17 | Self Closing Hinges and Pivots |
+| ANSI/BHMA A156.18 | Materials and Finishes |
+| ANSI/BHMA A156.19 | Power Assist and Low Energy Power Operated Doors |
+| ANSI/BHMA A156.21 | Thresholds |
+| ANSI/BHMA A156.22 | Door Gasketing and Edge Seal Systems |
+| ANSI/BHMA A156.23 | Electromagnetic Locks |
+| ANSI/BHMA A156.24 | Delayed Egress Locking Systems |
+| ANSI/BHMA A156.25 | Electrified Locking Devices |
+| ANSI/BHMA A156.26 | Continuous Hinges |
+| ANSI/BHMA A156.28 | Recommended Practices for Keying Systems |
+| ANSI/BHMA A156.29 | Exit Locks, Exit Alarms, Alarms for Exit Devices |
+| ANSI/BHMA A156.30 | High Security Cylinders |
+| ANSI/BHMA A156.31 | Electric Strikes and Frame Mounted Actuators |
+| ANSI/BHMA A156.36 | Auxiliary Locks |
+| ANSI/BHMA A156.115 | Hardware Preparation in Steel Doors and Steel Frames |
+| ANSI/BHMA A156.115-W | Hardware Preparation in Wood Doors with Wood or Steel Frames |
+| ANSI/NAAMM HMMA 831 | Recommended Hardware Locations for Custom Hollow Metal Doors and Frames |
+| DHI WDHS.3 | Recommended Locations for Architectural Hardware for Flush Wood Doors |
+| NFPA 70 | National Electrical Code |
+| NFPA 72 | National Fire Alarm and Signaling Code |
+| NFPA 80 | Standard for Fire Doors and Other Opening Protectives |
+| NFPA 101 | Life Safety Code |
+| NFPA 105 | Standard for Smoke Door Assemblies and Other Opening Protectives |
| UL 10C | Positive Pressure Fire Tests of Door Assemblies |
−| DHI WDHS.3 | Recommended Locations for Builders Hardware |
+| UL 228 | Door Closers-Holders, With or Without Integral Smoke Detectors |
+| UL 294 | Access Control System Units |
+| UL 305 | Panic Hardware |
+| UL 1034 | Burglary-Resistant Electric Locking Mechanisms |
+| UL 1784 | Air Leakage Tests of Door Assemblies and Other Opening Protectives |
+| IBC | International Building Code, Chapters 7, 10, and 11 |
+| ICC A117.1 | Accessible and Usable Buildings and Facilities |
+| 2010 ADA Standards | ADA Standards for Accessible Design |
# Submittals {toc}
## Action Submittals {toc}
−### The Contractor shall submit the following action submittals for review before fabrication or ordering of hardware:
−- Hardware schedule listing every opening, its assigned hardware set, and each item by manufacturer, product designation, function, finish, and quantity.
−- Hardware sets, each numbered and cross-referenced to the openings it serves on the door schedule.
−- Keying schedule showing the master-key hierarchy, keyed-alike groups, and the cylinder or core system.
−- Manufacturer product data for each hardware item, including ANSI/BHMA grade, listing, and applicable certifications.
−- Shop drawings or templates coordinating frame and door prep locations per DHI WDHS.3, including reinforcement for electrified items.
−- Wiring diagrams and point-to-point riser for all electrified hardware, coordinated with access control and fire alarm.
−- Samples of each finish on the actual hardware product where a finish match across manufacturers is required.
+### The submittals listed below shall be reviewed and returned before any hardware is ordered and before any frame or leaf is released for machining.
+- Hardware schedule listing every opening by mark with the hardware set assigned to it, and every item in each set by manufacturer designation, ANSI/BHMA standard and grade, function, size, finish code, fastening, and quantity
+- Product data for each hardware item, showing the listing and the ANSI/BHMA certification under which it is furnished
+- Keying schedule showing the hierarchy, the key symbols, the cylinder format, the keyway, and the openings each change key operates, prepared with the Owner
+- Hardware templates for every item that requires a frame or leaf preparation, issued to the frame and door manufacturers
+- Point-to-point wiring diagram and elevation for every electrified opening, showing each device, its voltage and current draw, its conductor count, and the terminating equipment
+- Finish samples on an actual hardware item for each finish code, and a sample of each item whose finish is to match across manufacturers
+- Manufacturer's published sizing for closers, power operators, and all-glass door fittings at the leaf sizes on the project
+
```datasheet
−label: Action submittals required
+label: Action Submittals Required
type: checkbox
options:
− - Hardware schedule (opening-by-opening)
− - Numbered hardware sets
− - Keying schedule
− - Manufacturer product data
− - Frame/door prep templates (DHI WDHS.3)
− - Electrified hardware wiring diagrams
− - Finish samples on actual product
+ - "Hardware schedule by opening and set"
+ - "Product data by item"
+ - "Keying schedule"
+ - "Hardware templates"
+ - "Electrified opening wiring diagrams"
+ - "Finish samples"
+ - "Closer and fitting sizing data"
default:
− - Hardware schedule (opening-by-opening)
− - Numbered hardware sets
− - Keying schedule
− - Manufacturer product data
− - Frame/door prep templates (DHI WDHS.3)
+ - "Hardware schedule by opening and set"
+ - "Product data by item"
+ - "Keying schedule"
+ - "Hardware templates"
+ - "Electrified opening wiring diagrams"
```
+### The hardware schedule shall be submitted as one complete document, and a partial or opening-by-opening submittal shall not be reviewed except where the Architect accepts a phased submission in writing for a stated group of openings.
+
+### A hardware schedule reviewed in pieces is a schedule whose sets cannot be checked against one another, and the keying, the finish, and the templates are each consistent only across the whole document. {note}
+
## Informational Submittals {toc}
−### The Contractor shall submit the following informational submittals:
−- Certification or qualification of the hardware consultant authoring the sets, where one is engaged.
−- Manufacturer listing documentation for fire exit hardware (UL 305 and UL 10C) and panic hardware (UL 305).
−- Installer qualifications for electrified hardware.
+### The Contractor shall submit the following for record before the corresponding work begins, without waiting for return.
+- Qualification record of the party preparing the hardware schedule, including the DHI certification where one is selected
+- Listing documentation for every fire exit hardware item, every closer-holder and hold-open device, every electrified locking device, and every gasketing product at a rated opening
+- Training record of the electrified hardware installer
+- Manufacturer's published installation, adjustment, and maintenance instructions for each item
+- Pre-installation conference record
+
```datasheet
−label: Informational submittals required
+label: Informational Submittals Required
type: checkbox
options:
− - Hardware consultant qualification (AHC/DAHC)
− - Fire exit hardware listing (UL 305 + UL 10C)
− - Panic hardware listing (UL 305)
− - Electrified hardware installer qualifications
+ - "Schedule preparer qualification"
+ - "Listing documentation for rated and electrified items"
+ - "Electrified hardware installer training record"
+ - "Installation and maintenance instructions"
+ - "Pre-installation conference record"
default:
− - Fire exit hardware listing (UL 305 + UL 10C)
− - Panic hardware listing (UL 305)
+ - "Schedule preparer qualification"
+ - "Listing documentation for rated and electrified items"
+ - "Electrified hardware installer training record"
+ - "Installation and maintenance instructions"
```
## Closeout Submittals {toc}
−### The Contractor shall submit the following closeout submittals before final acceptance:
−- Final keying schedule as keyed, with key bitting record delivered directly to the Owner under separate cover.
−- Operation and maintenance manuals for each hardware type, including adjustment and lubrication instructions.
−- Written record of door closer field adjustments, including measured opening force and sweep timing for ADA-path openings.
−- Warranty documents for each hardware category.
+### The Contractor shall submit the following before final acceptance.
+- Final keying schedule as keyed, and the key bitting list, each delivered to the Owner's designated representative under separate cover and not bound into the general closeout documents
+- Key record listing every key and core cut, the openings each operates, the quantity issued, the recipient, and the date
+- Record of closer adjustment at every accessible opening, showing the measured opening force and the measured closing time
+- Fire door assembly acceptance inspection record for every rated opening
+- Functional test record for every electrified opening
+- Executed warranties for each hardware category, in the Owner's name
+- Operation and maintenance data for each hardware item, including the adjustment procedure and the parts list
+
```datasheet
−label: Closeout submittals required
+label: Closeout Submittals Required
type: checkbox
options:
− - Final keying schedule and key bitting record
− - Operation and maintenance manuals
− - Door closer field-adjustment record (force and sweep)
− - Warranty documents
+ - "Final keying schedule and bitting list"
+ - "Key record"
+ - "Closer adjustment record"
+ - "Fire door acceptance inspection record"
+ - "Electrified opening test record"
+ - "Executed warranties"
+ - "Operation and maintenance data"
default:
− - Final keying schedule and key bitting record
− - Operation and maintenance manuals
− - Door closer field-adjustment record (force and sweep)
− - Warranty documents
+ - "Final keying schedule and bitting list"
+ - "Key record"
+ - "Closer adjustment record"
+ - "Fire door acceptance inspection record"
+ - "Electrified opening test record"
+ - "Executed warranties"
+ - "Operation and maintenance data"
```
# Quality Assurance {toc}
−## On projects with 50 or more openings, significant electrified hardware, or complex keying hierarchies, a Certified Architectural Hardware Consultant (AHC or DAHC) adds value that far exceeds their fee: omitting the consultant shifts the entire coordination burden onto the General Contractor during submittals, reliably multiplies RFIs, and the cost of late frame rework and re-keying is many times the consultant's cost. {note}
+## Authorship of the Hardware Schedule {toc}
−## On projects of 50 or more openings, the hardware sets and schedule shall be prepared or reviewed by a Certified Architectural Hardware Consultant.
+### The hardware schedule and the hardware sets shall be prepared by the party indicated in the datasheet.
−## The Contractor shall reconcile the hardware schedule against the door and frame schedule before any hardware is procured.
+```datasheet
+label: Hardware Schedule Preparer
+type: select
+options:
+ - "Architectural Hardware Consultant holding a current DHI certification"
+ - "Hardware supplier's consultant with a record of comparable projects"
+ - "The Architect's hardware specifier"
+```
−### Frame prep for hinges, strikes, closers, and exit devices is punched in the shop when the frame is fabricated. A hardware change discovered after the frame is built requires field welding, a new frame, or a non-conforming workaround, so reconciliation must precede procurement. {note}
+### Where the preparer is a consultant to the hardware supplier, the preparer shall have prepared hardware schedules for not fewer than five completed projects of comparable opening count and shall submit that record.
−## The hardware installer for electrified items shall be trained and certified by the hardware manufacturer for the products installed.
+### The preparer shall hold the hardware schedule and the hardware sets consistent with the door schedule, the keying schedule, and the electrified opening wiring diagrams through every revision until final acceptance.
−## A pre-installation conference shall be held with the hardware supplier, installer, electrical contractor, and access control and fire alarm trades before frames are set.
+### A DHI-certified consultant is examined on the code, the listings, and the templates, which is the expertise a project with rated pairs, electrified openings, and a master key system is buying, at a fee. A supplier's consultant prepares the schedule from the products the supplier stocks, at no separate fee, which fits a project whose openings are few and alike. The Architect's own specifier keeps the authorship inside the design contract and carries the coordination burden with it. The decision follows the opening count, the share of electrified and rated openings, and whether the Owner's key system already exists. {note}
−### Electric strikes, electrified locks, electrified exit devices, and electromagnetic hold-opens all require conduit, power supplies, and a fire-alarm interface that must be in the wall before the frame is set. Coordinating this after the rough-in is closed is a common and expensive miss. {note}
+## Supplier and Installer Qualifications {toc}
−# Hardware Sets and Grading {toc}
+### The hardware supplier shall be a firm that furnishes architectural hardware for projects of comparable opening count as a regular part of its business and that stocks the products furnished for replacement.
−## Hardware sets are the contract organizing unit, and the grade selected for each category sets the service life of the opening. {note}
+### Electrified hardware shall be installed and terminated by an installer trained by the manufacturer of the device installed, and the installer's training record shall be submitted before the work begins.
−### Each numbered hardware set lists every item a given opening type requires, from hinges through the threshold, so that the schedule resolves an opening to a complete, procurable list. Grade 1 is the heavy commercial and institutional class under the ANSI/BHMA A156 series; Grade 2 is light commercial and residential; Grade 3 is residential. {note}
+### Hardware at fire-rated openings shall be installed by personnel familiar with NFPA 80, and the installer shall be able to produce the listing for every item at a rated opening on request.
−## Each opening shall be assigned exactly one numbered hardware set, and the set shall list every hardware item the opening requires.
+## Pre-Installation Conference {toc}
−## All hardware shall be Grade 1 per the applicable ANSI/BHMA A156 standard for commercial and institutional work, including IBC occupancy groups A, B, E, I, M, and R-1.
+### Before any frame is set, the Contractor shall convene a conference attended by the hardware supplier, the hardware installer, the door and frame installers, the electrical contractor, the access control installer, and the fire alarm installer, and shall record its decisions.
+### The conference shall confirm, for every electrified opening, the device, the fail mode, the power transfer, the raceway path, the power supply location, and the fire alarm release point.
+
+### An electrified opening involves five trades and a listing, and every one of them has to agree on the same drawing before the frame goes in. The conference is where a strike drawn on the wrong jamb or a hold-open with no alarm relay is found while fixing it costs a pen stroke. {note}
+
+# Hardware Sets and the Hardware Schedule {toc}
+
+## Hardware shall be organized into numbered hardware sets, each set listing every item an opening type requires, and every opening on the door schedule shall be assigned exactly one set.
+
+## The hardware set assigned to each opening shall be [[drawing: as stated on the door schedule]].
+
+## Each hardware set shall be verified by the preparer against the leaf material, leaf thickness, leaf weight, hand, swing, fire-protection rating, smoke-control listing, sound rating, and egress function of every opening assigned to it before the set is released for procurement.
+
+## The hardware schedule format shall be as indicated in the datasheet.
+
```datasheet
−label: Default hardware grade
+label: Hardware Schedule Format
type: radio
options:
− - Grade 1 (heavy commercial / institutional)
− - Grade 2 (light commercial / residential common areas)
−default: Grade 1 (heavy commercial / institutional)
+ - "Vertical format, listing each set once with the openings it serves"
+ - "Horizontal format, listing each opening with its items across one line"
+default: "Vertical format, listing each set once with the openings it serves"
```
−## Grade 2 hardware may be used only in light commercial single-tenant office space or residential common areas, and any such downgrade shall be documented in the hardware schedule.
+## A vertical schedule lists every item in a set once and names the openings the set serves, so a change to the set is made in one place, and it is the format the hardware industry reviews against. A horizontal schedule lists each opening on its own line with its items across it, which reads directly against a door schedule and grows one line per opening, so a change to a set is repeated on every line that carries it. {note}
−### Specifying Grade 2 locksets or closers to save cost in assembly, educational, or healthcare occupancies produces premature failure under high cycle counts. The savings are recovered as warranty calls and early replacement within the first few years. {note}
+## The hardware sets shall list each item by its ANSI/BHMA standard and grade, its function designation, its size, its finish code, its fastening, and its quantity per opening, and shall name the manufacturer designation of the product furnished.
−### The party responsible for preparing the hardware sets, a Certified Architectural Hardware Consultant or the architect, shall be specified and documented in the hardware schedule.
+## Hardware shall be furnished from as few manufacturers as the set requirements allow, so that keying, finish, and template dimensions remain consistent across the work.
+## Where an item within a set is not manufactured in the finish, function, or size the set requires, the supplier shall submit the proposed substitution for review before the item is ordered rather than furnishing the nearest available product.
+
+## Fasteners shall be furnished with each item by its manufacturer, of the material class and finish of the item they fasten, with machine screws into every steel reinforcement and through-bolts where the leaf construction or the listing requires them.
+
+## Wood screws into a reinforcement plate strip, and a self-drilling screw into a lock block splits it. The fastener is part of the listing at a rated opening, which is why it is furnished by the hardware manufacturer and not substituted from site stock. {note}
+
+# Operational Grades {toc}
+
+## The ANSI/BHMA grade is a test result. Each A156 product standard assigns a grade from the cycle, strength, security, and finish tests the product survives, so a grade names a tested performance and not a price tier. A Grade 1 bored lock completes one million cycles under ANSI/BHMA A156.2, a Grade 2 lock eight hundred thousand, and a Grade 3 lock two hundred thousand; a Grade 1 closer completes two million cycles under ANSI/BHMA A156.4 against one million at Grade 2 and five hundred thousand at Grade 3. At an opening cycled a few hundred times a day the grades differ by years of service before the first rebuild; at an opening cycled a dozen times a day they differ by the price, and the lower grade at that opening buys the same service life. The grade selected here is the floor for the project, and the hardware schedule raises it at any opening whose traffic warrants it. {note}
+
+## The minimum grade for hinges shall be as indicated in the datasheet.
+
```datasheet
−label: Hardware consultant engaged
−type: radio
+label: Minimum Grade, Hinges
+type: select
options:
− - Yes, Certified Architectural Hardware Consultant (AHC/DAHC)
− - No, architect-self-specified
−default: Yes, Certified Architectural Hardware Consultant (AHC/DAHC)
+ - "Grade 1"
+ - "Grade 2"
+ - "Grade 3"
+default: "Grade 1"
```
−# Hinges and Pivots {toc}
+## The minimum grade for locksets and latches shall be as indicated in the datasheet.
−## Hinges carry the entire weight and cycle load of the leaf, and their type, weight, and count are selected from door size, frequency, and rating. {note}
+```datasheet
+label: Minimum Grade, Locksets and Latches
+type: select
+options:
+ - "Grade 1"
+ - "Grade 2"
+ - "Grade 3"
+default: "Grade 1"
+```
−### A standard-weight ball-bearing butt hinge serves doors up to 3 ft wide and under roughly 175 lb at normal traffic. A heavy-weight hinge with a thicker leaf is used for heavier leaves or high-frequency openings. A continuous (full-height) hinge distributes load along the entire edge for high-cycle or high-abuse openings and eliminates the sag point of a butt hinge. {note}
+## The minimum grade for exit devices shall be as indicated in the datasheet.
−## Butt hinges shall be ball-bearing type, Grade 1 per ANSI/BHMA A156.1.
+```datasheet
+label: Minimum Grade, Exit Devices
+type: select
+options:
+ - "Grade 1"
+ - "Grade 2"
+default: "Grade 1"
+```
−## Standard-weight hinges (0.134 in leaf) shall be used for doors up to 3 ft wide weighing less than 175 lb at normal traffic frequency.
+## The minimum grade for door closers shall be as indicated in the datasheet.
−## Heavy-weight hinges (0.180 in leaf) shall be used for doors over 175 lb or openings exceeding 400 cycles per day.
+```datasheet
+label: Minimum Grade, Door Closers
+type: select
+options:
+ - "Grade 1"
+ - "Grade 2"
+ - "Grade 3"
+default: "Grade 1"
+```
−## Continuous geared or pin-and-barrel hinges shall be used where the schedule designates high-cycle or high-abuse openings.
+## Where the hardware schedule assigns a higher grade at an opening than the project minimum, the hardware schedule governs that opening.
−## A minimum of three hinges shall be provided for doors up to 90 in tall, and a fourth hinge shall be added for each additional 30 in of door height.
+# Hinges and Pivots {toc}
−## A minimum of three hinges shall be provided on all fire-rated openings regardless of height, per NFPA 80.
+## Butt hinges shall conform to ANSI/BHMA A156.1 and to the template dimensions of ANSI/BHMA A156.7, continuous hinges to ANSI/BHMA A156.26, and self-closing hinges and pivots to ANSI/BHMA A156.17.
−## Hinges on out-swinging exterior or secured doors shall have non-removable pins (NRP) or a security stud.
+## The hanging device used as the project standard at swinging openings shall be as indicated in the datasheet, and the hardware schedule governs any opening it assigns a different device.
```datasheet
−label: Primary hinge type
−type: radio
+label: Project Standard Hanging Device
+type: select
options:
− - 4.5 x 4.5 standard-weight ball-bearing butt (0.134 in leaf)
− - 4.5 x 4.5 heavy-weight ball-bearing butt (0.180 in leaf)
− - Continuous (full-height geared) hinge
− - Spring hinge (self-closing)
−default: 4.5 x 4.5 standard-weight ball-bearing butt (0.134 in leaf)
+ - "Full mortise butt hinge"
+ - "Half mortise butt hinge"
+ - "Full surface butt hinge"
+ - "Half surface butt hinge"
+ - "Continuous geared hinge"
+ - "Continuous pin-and-barrel hinge"
+ - "Center-hung pivot set"
+ - "Offset pivot set"
+ - "Spring hinge, self-closing"
+default: "Full mortise butt hinge"
```
+## A butt hinge carries the leaf at two, three, or four points on the stile and is the device every frame and leaf is prepared for by default. A continuous hinge spreads the load along the full height, which is why it appears at high-cycle openings, at leaves that have torn out a butt hinge once, and at exterior leaves where its stiffness also resists prying; it costs more and it covers the hinge stile so the leaf cannot be removed without removing the hinge. A pivot carries the load into the floor and the head instead of the jamb, which is what makes it the device for a very heavy or a very wide leaf and for a leaf that swings both ways. A spring hinge closes a light leaf without a closer and without closer control, so the leaf slams at one spring setting and fails to latch at the next. Surface and half-surface hinges serve leaves and frames that cannot be mortised, including existing openings and channel frames. {note}
+
+## The hinge bearing type shall be as indicated in the datasheet.
+
```datasheet
−label: Hinges per leaf
−type: radio
+label: Hinge Bearing Type
+type: select
options:
− - 3 (door up to 90 in tall)
− - 4 (door 90-120 in tall)
− - 5 (door over 120 in tall)
−default: 3 (door up to 90 in tall)
+ - "Ball bearing"
+ - "Concealed anti-friction bearing"
+ - "Plain bearing"
+default: "Ball bearing"
```
+## A plain bearing rides steel on steel and wears a leaf out of alignment at any opening that carries a closer. A ball bearing hinge carries the thrust on raceways and is the bearing a closer-equipped opening is specified with, and a concealed anti-friction bearing gives the same service with no visible bearing rings. {note}
+
+## The base material of hinges at interior openings shall be as indicated in the datasheet.
+
```datasheet
−label: Hinge pin security
−type: radio
+label: Hinge Base Material at Interior Openings
+type: select
options:
− - Standard pin
− - Non-removable pin (NRP)
− - Security stud
−default: Standard pin
+ - "Steel, plated"
+ - "Stainless steel"
+ - "Brass or bronze"
+default: "Steel, plated"
```
−# Locksets and Latchsets {toc}
+## The base material of hinges at exterior openings and at openings exposed to washdown or sustained high humidity shall be as indicated in the datasheet.
−## The lockset format and function together define how an opening is secured and operated, and the function must match the room's use. {note}
+```datasheet
+label: Hinge Base Material at Exterior and Wet Openings
+type: select
+options:
+ - "Stainless steel"
+ - "Brass or bronze"
+ - "Steel, plated"
+default: "Stainless steel"
+```
−### A cylindrical (bored) lockset fits a bored door prep and is the workhorse of commercial interiors; a mortise lockset uses a rectangular case let into the door edge and offers heavier duty, more functions, and integral deadbolt options at higher cost. Function names — passage, privacy, classroom, storeroom, office, dormitory, communicating, entrance — describe exactly which side latches, locks, or unlocks, and are selected per room, not per door type. {note}
+## A plated steel hinge is the lowest-cost base and holds its finish indoors; outdoors or under washdown its plating breaks at the knuckle and the steel beneath rusts, which stains the leaf below the hinge. Stainless steel and brass or bronze carry the finish through their thickness. Brass and bronze are softer and are selected for their color, and stainless matches the 630 finish family. {note}
−## All locksets shall be Grade 1 per ANSI/BHMA A156.2 for bored locksets and per ANSI/BHMA A156.13 for mortise locksets.
+## Hinges at fire-rated openings shall be of steel or stainless steel base material unless the hinge is listed for use on a fire door assembly, and shall be of a size and quantity within the assembly listing.
−## Lever or loop trim shall be provided on all locksets and latchsets; knobs shall not be used.
+## Hinge quantity shall be not fewer than two on a leaf up to 60 in. tall and not fewer than three on a leaf over 60 in. tall, plus one additional hinge for each 30 in. or fraction of leaf height over 90 in.
−### ICC A117.1 requires operable hardware that does not require tight grasping, pinching, or wrist twisting. A lever or loop handle satisfies this; a round knob does not and is non-compliant on accessible openings. {note}
+## Hinge height shall be 4-1/2 in. on a 1-3/4 in. thick leaf up to 3 ft 0 in. wide, 5 in. on a 1-3/4 in. thick leaf over 3 ft 0 in. wide, and 3-1/2 in. on a 1-3/8 in. thick leaf, and the hinge width shall clear the trim, the frame face, and any wall return the leaf must swing past.
−## The lock function for each opening shall match the room use designated on the schedule, and a function not on the standard list shall not be substituted without the Architect's approval.
+## Heavy-weight hinges, in the heavy-weight gauge ANSI/BHMA A156.1 assigns to the hinge size, shall be furnished where the leaf exceeds 200 lb or the opening is scheduled as high-frequency, and standard-weight hinges, in the standard-weight gauge for the size, at other openings.
−## Mortise locksets shall be used where the schedule designates heavy-duty service, integral deadbolt, or a function not available in a cylindrical case.
+## A standard-weight 4-1/2 in. hinge carries a 1-3/4 in. leaf of ordinary weight at ordinary traffic. At an entrance, a corridor cross door, or a classroom, the hinge sees several hundred cycles a day with a closer pulling on it at every one, and the thicker heavy-weight hinge leaf is what keeps the knuckle from wearing oval and the leaf from sagging onto the strike. The leaf weight comes from the door submittal, which is one of the reasons the schedule is reconciled against it. {note}
−## Lever return shall be within 1/2 in of the door face to prevent catching clothing or wheelchair components.
+## Hinges at outswinging exterior openings and at openings serving secured spaces shall be furnished with the pin security indicated in the datasheet.
```datasheet
−label: Lockset format
−type: radio
+label: Pin Security at Outswinging Exterior and Secured Openings
+type: select
options:
− - Cylindrical / bored (ANSI/BHMA A156.2 Grade 1)
− - Mortise (ANSI/BHMA A156.13 Grade 1)
−default: Cylindrical / bored (ANSI/BHMA A156.2 Grade 1)
+ - "Non-removable pin with a set screw"
+ - "Security stud interlocking the hinge leaves"
+ - "Continuous hinge presenting no removable pin"
+default: "Non-removable pin with a set screw"
```
+## A set screw in the barrel keeps the pin from being driven out while the leaf is closed; a security stud leaves the pin removable but locks the two hinge leaves together so the door stays hung without it; a continuous hinge has no exposed pin to attack. The set screw is the lowest-cost measure and is defeated only by cutting the knuckle; the stud is selected where the pin has to come out for leaf removal; the continuous hinge is selected where the opening is also high-cycle. {note}
+
+## Center-hung and offset pivot sets shall be furnished with an intermediate pivot where the pivot manufacturer's published limits for leaf height and weight require one, and the pivot set shall be rated by its manufacturer for the leaf weight stated on the door submittal.
+
+## Spring hinges shall not be furnished at a fire door assembly unless they are listed for that use, and a spring-hinged leaf shall meet the closing time required under the Accessible Opening Requirements section of this standard.
+
+## Continuous hinges at fire-rated openings shall be listed for the rating period and installed with the fasteners and at the spacing the listing names.
+
+# Locksets, Latches, and Trim {toc}
+
+## Bored locksets and latches shall conform to ANSI/BHMA A156.2, mortise locksets and latches to ANSI/BHMA A156.13, interconnected locks to ANSI/BHMA A156.12, and auxiliary locks to ANSI/BHMA A156.36.
+
+## The lockset chassis type used as the project standard shall be as indicated in the datasheet, and the hardware schedule governs any opening it assigns a different chassis.
+
```datasheet
−label: Lockset function
+label: Project Standard Lockset Chassis
type: select
options:
− - Passage (no lock)
− - Privacy (bath/bedroom)
− - Office (lockable from inside)
− - Classroom (key-locked outside trim)
− - Storeroom (always-locked outside, free egress)
− - Entrance
− - Communicating
−default: Office (lockable from inside)
+ - "Bored cylindrical lockset"
+ - "Mortise lockset"
+ - "Interconnected lockset"
+ - "Tubular lockset"
+default: "Bored cylindrical lockset"
```
+## A mortise case sits in a pocket cut into the stile and carries the latch, a deadbolt, an auxiliary latch, and the lever mechanism in one housing, which is what lets it offer functions a bored lock cannot and what makes it the heavier chassis at a high-abuse opening; it needs a leaf whose stile is solid through the pocket. A bored lock passes through two holes, installs in minutes, replaces without a locksmith, and asks less of the leaf's edge. An interconnected lock pairs a bored latch with a bored deadbolt so one lever retracts both, which is how a deadbolt is put on an egress door without a second motion. A tubular lock is the light-duty chassis and serves closets and residential interiors. {note}
+
+## The lock trim style shall be as indicated in the datasheet.
+
```datasheet
−label: Lever trim style
−type: radio
+label: Lock Trim Style
+type: select
options:
− - Lever (ADA-compliant)
− - Loop / return-to-door (ADA-compliant)
−default: Lever (ADA-compliant)
+ - "Lever handle"
+ - "Lever handle with a return to the leaf face"
+ - "Knob"
+ - "Thumbpiece with escutcheon"
+ - "Push-pull paddle trim"
+default: "Lever handle"
```
−# Exit Devices {toc}
+## A lever is operable with a closed fist and is the trim the accessibility standard describes. A return-to-door lever brings the lever end back toward the leaf face, so a sleeve or a wheelchair armrest slides off it rather than catching, which is the reason it is scheduled in healthcare and in schools. A knob cannot meet the accessible operating requirement and is selected only at openings off the accessible route. A thumbpiece escutcheon reads as a grip handle and is selected for its appearance at an entrance. Paddle trim is operated by pushing or pulling with a forearm, a hip, or a cart, and serves healthcare and food service openings where hands are full or gloved. {note}
−## Exit devices provide single-operation egress under load, and the distinction between panic hardware and fire exit hardware is a life-safety boundary that drives both listing and dogging. {note}
+## A knob shall not be furnished at an opening on an accessible route regardless of the datasheet selection.
−### Panic hardware is listed to UL 305 for egress-only openings and may be mechanically dogged to hold the latch retracted. Fire exit hardware is listed to both UL 305 and UL 10C and is required on fire-rated openings, where it must positively latch on every cycle. Specifying panic hardware on a fire-rated opening, or leaving mechanical dogging enabled on a fire door, is a code defect that fails inspection. {note}
+## The lock backset shall be as indicated in the datasheet.
−## Exit devices shall be Grade 1 per ANSI/BHMA A156.3.
+```datasheet
+label: Lock Backset
+type: range
+unit: in
+min: 2.375
+max: 5
+setpoints: [2.375, 2.75, 3.75, 5]
+default: 2.75
+```
−## Panic hardware shall be provided on egress doors in assembly (A) and educational (E) occupancies with an occupant load of 50 or more.
+## The backset shall be increased at any opening where the standard backset would place the trim against the frame stop, an adjacent wall, or a pull on the opposite face, and the increased backset shall be confirmed against the leaf's edge construction before the leaf is machined.
−## Panic hardware shall be provided on all egress doors in high-hazard (H) occupancies regardless of occupant load.
+## The lock function at each opening shall be [[drawing: as stated on the hardware schedule]] by its ANSI/BHMA function designation, selected to the security, privacy, and egress obligations of the space the opening serves.
−## Fire exit hardware listed to both UL 305 and UL 10C shall be provided on all fire-rated egress openings.
+## A function describes which side latches, which side locks, and what unlocks it. A passage function latches and never locks; a privacy function locks from inside with a turn and releases from outside with a tool; an office function locks from inside and opens with a key; a classroom function locks and unlocks by key from the corridor; a storeroom function is locked from outside at all times and free from inside at all times; a classroom security function adds an inside key cylinder so the room is locked from within. The function is a room decision and not a door-type decision, which is why it is stated opening by opening on the schedule. {note}
−## Mechanical dogging shall not be provided on fire-rated openings; cylinder dogging or electric latch retraction shall be used where the schedule requires the latch held retracted on a fire door.
+## A door in a means of egress shall be openable from the egress side without a key, a tool, special knowledge, or special effort, and the latch and any lock shall release with the number of releasing motions [[parameter: adopted-building-code]] permits for the occupancy served, except where a controlled, delayed, or sensor-released egress arrangement is installed in full compliance with the provision of that code that permits it.
−## The exit device type shall match the door and frame prep, and the device type shall not be changed against an already-fabricated frame without re-prepping or replacing the frame.
+## Auxiliary deadbolts shall not be furnished on a door in a means of egress unless the deadbolt is retracted by the same motion that retracts the latch or the building code expressly permits a separate deadbolt at that opening.
−### Rim devices need a frame-mounted rim strike; mortise devices need a mortise prep; surface and concealed vertical-rod devices need top and bottom preps. Substituting one type for another after the frame is built is a major RFI and often a frame replacement. {note}
+## Locking a means of egress door against the direction of travel is one of the few things a specification can do that kills people. Every controlled, delayed, and sensor-released egress arrangement the code allows carries a list of conditions, and all of them have to be satisfied together, not selectively, at every opening that uses it. {note}
−## Exit device operating force shall not exceed 15 lbf to release the latch, per NFPA 101 and IBC Section 1010.
+## Strikes shall be furnished with a strike box at every frame preparation, with a curved lip of a length that clears the frame face and does not project into the path of travel, and the strike at a fire-rated opening shall be the strike the listing names.
−## Exit device touchpad or crossbar shall be mounted between 34 in and 48 in above the finished floor, per ICC A117.1.
+## Latchbolt throw at a fire-rated opening shall be not less than 1/2 in. at a single leaf and not less than 3/4 in. at a pair, or the longer throw the assembly listing names.
+## Lever trim shall be through-bolted or secured to the chassis so that the trim cannot be pulled from the leaf, and a return-to-door lever shall return to within 1/2 in. of the leaf face.
+
+# Cylinders and Keying {toc}
+
+## Cylinder Format {toc}
+
+### Cylinders and input devices shall conform to ANSI/BHMA A156.5, high-security cylinders shall additionally conform to ANSI/BHMA A156.30, and the keying system shall follow the practices of ANSI/BHMA A156.28.
+
+### The cylinder format used throughout the project shall be as indicated in the datasheet.
+
```datasheet
−label: Exit device type
−type: radio
+label: Cylinder Format
+type: select
options:
− - Rim (single-point, surface)
− - Mortise (multi-point with mortise case)
− - Surface vertical rod (SVR)
− - Concealed vertical rod (CVR)
−default: Rim (single-point, surface)
+ - "Conventional fixed cylinder"
+ - "Small format interchangeable core"
+ - "Large format interchangeable core"
+ - "Removable core in a proprietary format"
```
+### Every keyed device on the project, including the exit device trim, the removable mullions, and the key switches furnished under this standard, shall accept the cylinder format selected, so that one core inventory serves the building.
+
+### An interchangeable core comes out with a control key and goes back in without disassembling the lock, so rekeying a building is a walk-through with a bag of cores instead of a locksmith at every door. The small format fits one housing across every manufacturer that makes it, which lets the Owner change lock brands and keep the cores; the large format carries more pins and more key changes but is proprietary to each maker. A conventional cylinder is the lowest cost at purchase and is rekeyed by pulling the lock. The control key becomes the most security-sensitive key in the building under any interchangeable format. {note}
+
+## Keyway Control {toc}
+
+### The keyway control level shall be as indicated in the datasheet.
+
```datasheet
−label: Exit device listing
−type: radio
+label: Keyway Control Level
+type: select
options:
− - Panic hardware (UL 305) - non-rated opening
− - Fire exit hardware (UL 305 + UL 10C) - rated opening
−default: Panic hardware (UL 305) - non-rated opening
+ - "Standard open commercial keyway"
+ - "Restricted keyway with patented key control"
+ - "High-security keyway conforming to ANSI/BHMA A156.30"
+ - "The Owner's existing keyway extended to this project"
```
+### Where the Owner operates an existing key system at this or another facility, the Owner shall confirm in writing whether this project joins that system before cylinders are ordered, and the cylinder format and keyway shall then match the existing system.
+
+### An open keyway means blanks are sold to any locksmith, so any key can be copied by anyone holding it. A patented keyway restricts the blanks to authorized channels for the life of the patent, which is what makes a "do not duplicate" stamp enforceable rather than advisory. A high-security cylinder adds measured resistance to picking, drilling, and bumping on top of the restricted blank. Joining an existing system inherits whatever control that system has, and a core format that differs from the Owner's existing cylinders forces a facility-wide rekey, which is rarely intended and always costly. {note}
+
+## Keying System Hierarchy {toc}
+
+### The keying system hierarchy shall be as indicated in the datasheet.
+
```datasheet
−label: Dogging
−type: radio
+label: Keying System Hierarchy
+type: select
options:
− - Mechanical dogging (non-rated only)
− - Cylinder dogging
− - Electric latch retraction
− - None (positive latching, rated opening)
−default: None (positive latching, rated opening)
+ - "Keyed alike throughout"
+ - "Keyed different, with no master keying"
+ - "Master key system"
+ - "Grand master key system"
+ - "Great grand master key system"
+ - "The Owner's existing key system extended to this project"
```
+### The keying system shall be designed by the hardware schedule preparer in a keying conference with the Owner, and the keying schedule shall be accepted by the Owner in writing before cylinders are ordered.
+
+### The keying system shall have theoretical key change capacity for the openings on this project plus the expansion the Owner identifies at the keying conference, and the preparer shall state that capacity on the keying schedule.
+
+### Each level of master keying adds a shear line to every cylinder in the system, which enlarges the set of key cuts that will turn a given lock and spends key change capacity. A hierarchy deeper than the building's departmental structure buys no operational benefit and costs both security margin and expansion room. A specification that leaves the keying to be worked out during submittals hands the design of the Owner's key system to the contractor, who does not know the Owner's departments. {note}
+
+## Construction Keying {toc}
+
+### The construction keying method shall be as indicated in the datasheet.
+
```datasheet
−label: Exit device actuator centerline height
+label: Construction Keying Method
+type: select
+options:
+ - "Temporary construction cores replaced at Owner acceptance"
+ - "Construction master keying within the permanent cylinders"
+ - "Permanent cylinders installed at the outset"
+ - "Owner-furnished temporary cylinders"
+```
+
+### Where temporary cylinders or cores are furnished, the Contractor shall replace them with the permanent cylinders keyed to the accepted keying schedule at Owner acceptance, in the Owner's presence or against the Owner's written release.
+
+### The Contractor shall collect every construction key and every temporary core from the trades and shall account for them in writing before the permanent cylinders are installed, and shall rekey at the Contractor's cost any cylinder whose construction key cannot be accounted for.
+
+### A temporary core is pulled and discarded, so nothing cut during construction operates the finished building. Construction master keying leaves the permanent cylinder in place and voids the construction key by a one-time operation of the change key, which is the lower-cost method with conventional cylinders and the one that leaves a residual cut in the cylinder. Permanent cylinders from the outset are selected where the Owner takes control of the building floor by floor. {note}
+
+## Key Quantities and Key Control {toc}
+
+### The number of change keys furnished for each keyed cylinder or core shall be as indicated in the datasheet.
+
+```datasheet
+label: Change Keys per Cylinder
type: range
−unit: in AFF
−min: 34
−max: 48
+unit: keys
+min: 1
+max: 10
step: 1
−default: 40
+default: 2
```
−# Door Closers and Hold-Opens {toc}
+### The number of keys furnished for each master, grand master, and control key symbol shall be as indicated in the datasheet.
−## Closers control the swing for both safety and accessibility, and the mounting, force, and timing must be set in the field to meet ADA limits. {note}
+```datasheet
+label: Keys per Master and Control Key Symbol
+type: range
+unit: keys
+min: 1
+max: 10
+step: 1
+```
−### A surface-mounted closer mounts to the door or frame face in a regular-arm, top-jamb, or parallel-arm configuration; a concealed overhead closer hides in the frame head; a floor closer carries heavy or high-traffic leaves from below. The parallel-arm and top-jamb mountings produce different opening-force results from the same closer, so the configuration matters to ADA compliance and must be verified after installation. {note}
+### Two keys per change is the quantity every manufacturer ships, and more are cut at the Owner's request against the key record. The master and control quantities follow how many people carry a master and how the Owner stores the control key, and no one count is the norm. {note}
−## Door closers shall be Grade 1 per ANSI/BHMA A156.4.
+### Keys shall be stamped with the key symbol from the keying schedule and shall not be stamped with the opening number or any text identifying the space they operate.
−## The closer mounting configuration shall be selected to suit the door swing, frame condition, and the required opening force, and shall be shown on the hardware set.
+### Stamping a room number on a key turns a lost key into a map. The key symbol identifies the key to the person holding the keying schedule and to nobody else. {note}
−## Closer sweep speed shall be adjusted so the door takes a minimum of 5 seconds to move from 90° to 12° from the latch, per ICC A117.1.
+### The Contractor shall furnish a key control cabinet sized for the keys the accepted keying schedule generates, with tags, hooks, and an index.
−## Closer latch speed shall be adjusted to seat the door without slamming, typically within 0 to 3 seconds.
+### Keys, cores, and the key bitting list shall be delivered directly to the Owner's designated representative against a signed receipt, and shall not be routed through the site office or left at an installation area.
−## Closer backcheck should be set to engage at approximately 70° of opening to protect adjacent walls and the door from over-swing.
+# Exit Devices {toc}
−## Interior hinged doors on accessible routes shall be adjusted so the opening force does not exceed 5 lbf, per ICC A117.1.
+## Exit devices shall conform to ANSI/BHMA A156.3 and shall be listed as panic hardware under UL 305, and devices at fire-rated openings shall be listed as fire exit hardware for the rating period of the assembly.
−### The 5 lbf interior limit does not apply to exterior doors or fire-rated doors, which require a higher closing force to latch reliably and are exempt. {note}
+## Panic hardware or fire exit hardware shall be furnished at every opening [[parameter: adopted-building-code]] requires to have it, including doors serving a Group H occupancy, doors serving a room or space with an occupant load of 50 or more in a Group A or Group E occupancy, and the electrical equipment room doors the referenced electrical code requires to have it.
−## Electromagnetic hold-opens shall be fail-safe and shall release the door to the closed position on a signal from the fire alarm system, coordinated with [[sync/fire-alarm-systems]].
+## Whether the device at each opening is furnished as panic hardware or as fire exit hardware shall follow the fire-protection rating of that opening, with fire exit hardware at every fire-rated opening and panic hardware at every other opening.
−## Door closer opening force and sweep timing shall be measured and recorded at final inspection for every accessible-path opening.
+```datasheet
+label: Exit Device Listing at Each Opening
+type: select
+derived: "the fire-protection rating of the opening on the door schedule"
+options:
+ - "Panic hardware"
+ - "Fire exit hardware"
+default: derived
+```
+## The exit device chassis type used as the project standard shall be as indicated in the datasheet, and the hardware schedule governs any opening it assigns a different chassis.
+
```datasheet
−label: Door closer type
+label: Project Standard Exit Device Chassis
+type: select
+options:
+ - "Rim device"
+ - "Mortise device"
+ - "Surface vertical rod device"
+ - "Concealed vertical rod device"
+ - "Concealed vertical cable device"
+default: "Rim device"
+```
+
+## A rim device mounts on the face and latches into a strike on the frame or a mullion, so it fits any leaf, replaces without machining, and is the device most frames are prepared for. A mortise device puts the latch in the leaf edge and offers the functions of a mortise lock, at the cost of a solid stile and a mortise preparation. A vertical rod device latches at the head and, where the bottom rod is furnished, at the floor, which is what secures the inactive leaf of a pair with no mullion; the surface version is visible and serviceable from the face, the concealed version runs inside the leaf and needs a leaf built for it. A concealed cable device replaces the rods with a cable and a single top latch, so there is no bottom rod to be kicked out of adjustment. {note}
+
+## The actuating member of the device shall be as indicated in the datasheet.
+
+```datasheet
+label: Exit Device Actuating Member
type: radio
options:
− - Surface-mounted, parallel arm
− - Surface-mounted, top jamb
− - Surface-mounted, regular arm
− - Concealed overhead
− - Floor closer / pivot closer
−default: Surface-mounted, parallel arm
+ - "Touchpad"
+ - "Crossbar"
+default: "Touchpad"
```
+## A crossbar spans the leaf on pivots and is the historic form; a touchpad is a push rail flush to the device body, takes no grasp to operate, and leaves nothing projecting for a sleeve or a cart to catch. {note}
+
+## The dogging provision on panic hardware at non-rated openings shall be as indicated in the datasheet.
+
```datasheet
−label: Sweep time (90° to 12° from latch)
−type: range
−unit: s
−min: 5
−max: 10
−step: 1
−default: 5
+label: Dogging on Panic Hardware
+type: select
+options:
+ - "No dogging"
+ - "Hex-key mechanical dogging"
+ - "Cylinder dogging"
+ - "Electric dogging by latch retraction"
```
+## Dogging holds the latch retracted so the leaf works as a push-pull door during business hours. A hex key dogs any device and anyone holding the key can dog it; cylinder dogging puts a keyed cylinder on the operation so only a keyholder can leave the opening unlatched; electric latch retraction dogs the device from the access control schedule and releases it on command, which is what lets an automatic operator or a remote unlock work with an exit device. {note}
+
+## Fire exit hardware shall not be furnished with mechanical dogging, and electric latch retraction on fire exit hardware shall be arranged so that the latch projects on activation of the fire alarm system and on loss of power.
+
+## The exit device features furnished at the openings the hardware schedule assigns them to shall be as indicated in the datasheet.
+
```datasheet
−label: Accessible-route interior opening force
−type: range
−unit: lbf
−min: 3
−max: 5
−step: 0.5
−default: 5
+label: Exit Device Features Furnished
+type: checkbox
+options:
+ - "Exit alarm conforming to ANSI/BHMA A156.29"
+ - "Latchbolt monitor switch"
+ - "Request-to-exit switch in the touchpad"
+ - "Cylinder-operated outside trim"
+ - "Less-bottom-rod configuration with an auxiliary fire pin at rated pairs"
+default: []
```
+## The outside trim function at each device shall be [[drawing: as stated on the hardware schedule]], and the trim shall be listed for use with the device it operates.
+
+## The force to release the latch shall not exceed 15 lbf applied in the direction of egress travel, and the actuating portion of the device shall be mounted not less than 34 in. and not more than 48 in. above the finished floor.
+
+## The actuating portion shall extend not less than one-half the clear width of the leaf.
+
+## No lock, latch, chain, or other device shall be installed on a door carrying panic hardware or fire exit hardware that prevents the leaf from opening on operation of the device, other than the electrified arrangements the building code permits and the Electrified Hardware section of this standard describes.
+
+## Where a bottom rod is furnished, the floor strike shall be set flush with the finished floor and located out of the accessible route, and where the bottom rod is omitted at a fire-rated pair, the device shall carry the auxiliary fire pin the listing names.
+
+## A bottom rod places a strike in the path of every mop, every cart wheel, and every shoe that crosses the opening, and the rod falls out of adjustment as the leaf settles. A less-bottom-rod device removes the floor strike by relying on the top latch alone, and at a rated pair it carries a thermal pin that projects into the opposite leaf when the pin's fusible element lets go, which is what keeps the pair from bowing apart in a fire. {note}
+
+# Door Closers and Hold-Open Devices {toc}
+
+## Door closers shall conform to ANSI/BHMA A156.4, overhead holders to ANSI/BHMA A156.8, and electromagnetic release and hold-open devices to ANSI/BHMA A156.15, and closers and hold-open devices at fire-rated openings shall be components covered by the fire door assembly listing.
+
+## Every fire door assembly and every smoke and draft control assembly shall be furnished with a closer or a self-closing device that closes and latches the leaf from any open position.
+
+## The closer mounting class used as the project standard shall be as indicated in the datasheet, and the hardware schedule governs any opening it assigns a different class.
+
```datasheet
−label: Hold-open device
−type: radio
+label: Project Standard Closer Mounting Class
+type: select
options:
− - None
− - Mechanical hold-open (non-rated only)
− - Electromagnetic hold-open, fail-safe (FA release)
−default: None
+ - "Surface-mounted on the leaf face"
+ - "Surface-mounted in the frame soffit"
+ - "Concealed in the leaf"
+ - "Concealed in the frame head"
+ - "Floor-mounted closer with pivots"
+default: "Surface-mounted on the leaf face"
```
−# Stops, Holders, and Protection Plates {toc}
+## A surface closer is reached with a screwdriver from a ladder, which is why it survives twenty years of adjustment; the parallel-arm mounting on the push face keeps the arm inside the room and out of reach, and the regular-arm mounting on the pull face is the most efficient and the most visible. A soffit mount clears the leaf face for a lite or a sign. A concealed closer disappears into the leaf or the head and takes the leaf off its hinges to service, so an opening that will be readjusted often is the one where concealment costs the most. A floor closer carries a heavy or a double-acting leaf on pivots and holds the closer under the threshold. {note}
−## Stops, holders, and plates protect the door, the wall, and the finish from the wear of daily use. {note}
+## The arm configuration at each opening shall be [[drawing: as stated on the hardware schedule]] to suit the mounting face and the stop condition of that opening, rather than selected project-wide.
−### A wall stop or floor stop arrests the swing before the lever strikes the wall; a magnetic holder parks the door open where the schedule allows; kick, mop, and armor plates take the abuse at the base; push and pull plates protect the face of doors without a lockset. {note}
+## The adjustable features required on closers shall be as indicated in the datasheet.
−## A door stop shall be provided at every opening to arrest the swing before the trim contacts the wall.
+```datasheet
+label: Closer Adjustable Features Required
+type: checkbox
+options:
+ - "Adjustable backcheck"
+ - "Separately adjustable sweep and latch speeds"
+ - "Adjustable spring power across the size range"
+ - "Delayed action"
+ - "Cush arm with an integral dead stop"
+ - "Spring cush arm"
+default:
+ - "Adjustable backcheck"
+ - "Separately adjustable sweep and latch speeds"
+ - "Adjustable spring power across the size range"
+```
−## Wall stops shall be installed only where solid blocking or backing exists in the wall, coordinated with [[sync/gypsum-board-assemblies]]; a floor stop or overhead stop shall be used where backing is absent.
+## Backcheck slows the leaf in the last part of the opening arc so a leaf thrown open does not strike the wall or tear the closer off the leaf. Separate sweep and latch valves let the leaf close slowly through its travel and still accelerate to latch, which is how the accessible closing time and reliable latching are met together. Adjustable spring power lets one closer body be set from the lightest interior setting to the force an exterior leaf needs, so one model serves the project and the installer sets the force at the opening. Delayed action holds the leaf near fully open for a settable interval before the sweep begins, which gives a person with a cart or a walker time to pass. A cush arm stops the leaf in the arm and spares the wall where no stop can be mounted, at the cost of loading the leaf's top rail with every stop. {note}
−## Kick plates shall be provided on the push side of doors subject to cart, foot, or equipment traffic, sized to 2 in less than the door width and 10 in high unless otherwise scheduled.
+## Closer spring power at each opening shall be selected from the manufacturer's published sizing for the leaf width, the mounting, and the exposure, and shall be set to the lowest value that closes and latches the leaf against the gasketing and the pressure conditions at that opening.
−## Mop plates shall be provided at the base of doors in wet-cleaned areas.
+## Backcheck shall not be furnished as a substitute for a door stop where a stop is required to protect a wall, a window, or equipment within the swing.
−## Push and pull plates shall be provided on doors without a lockset where hand contact is expected on a finished face.
+## The hold-open method used as the project standard at openings that are to stand open in normal use shall be as indicated in the datasheet.
−## Overhead stops or holders shall be specified where a wall or floor stop is not feasible and the swing must be limited.
+```datasheet
+label: Project Standard Hold-Open Method
+type: select
+options:
+ - "No hold-open"
+ - "Hold-open arm on the closer"
+ - "Overhead surface holder"
+ - "Overhead concealed holder"
+ - "Wall-mounted or floor-mounted magnetic holder with the closer"
+ - "Electromagnetic closer-holder released by the fire alarm system"
+default: "No hold-open"
+```
+## A hold-open arm or an overhead holder parks the leaf mechanically and is released by hand, which is what makes it unusable at a rated opening. A magnetic wall holder works with any closer and releases on loss of power to the magnet, so it is released by the fire alarm; it needs a wall within the swing and backing behind it. An electromagnetic closer-holder puts the holder in the closer body and is released the same way, with no wall required and with an integral smoke detector where the listing provides one. {note}
+
+## A hold-open arm, an overhead holder, or any other hold-open device that is not released by the fire alarm system shall not be furnished on a fire door assembly or on a smoke and draft control assembly.
+
+## Hold-open devices at fire door assemblies and at smoke and draft control assemblies shall be electromagnetic devices listed under UL 228 or ANSI/BHMA A156.15, released as described under the Fire Alarm Release article of this standard.
+
+## Closers at accessible openings shall be adjusted to the closing time and the opening force stated under the Accessible Opening Requirements section of this standard.
+
+# Low-Energy Power Operators {toc}
+
+## Low-energy power-operated and power-assist operators on swing doors shall conform to ANSI/BHMA A156.19, and an operator at a fire door assembly shall be listed as a closing device for use on a fire door assembly.
+
+## A low-energy operator opens a swing door only on a knowing act, at a speed and a force ANSI/BHMA A156.19 limits so that the leaf can meet a person without injuring them, which is why it needs no approach sensor and why it is scheduled with the finish hardware of the opening it serves. A full-energy entrance opens on approach and carries the sensors and guide rails that make that safe; it is a different product under ANSI/BHMA A156.10 and is governed by [[sync/automatic-entrance-doors]]. {note}
+
+## The operator class at the openings the hardware schedule assigns a power operator to shall be as indicated in the datasheet.
+
```datasheet
−label: Door stop type
+label: Power Operator Class
type: radio
options:
− - Wall stop (requires backing)
− - Floor stop (dome or rod)
− - Overhead stop / holder
−default: Wall stop (requires backing)
+ - "Low-energy power-operated, opening fully on a knowing act"
+ - "Power-assist, reducing the manual opening force"
+default: "Low-energy power-operated, opening fully on a knowing act"
```
+## A low-energy power-operated door opens fully when the actuator is pressed and closes on its own, so a person using a wheelchair passes without touching the leaf, and it is the operator an accessible entrance or a corridor cross door is scheduled with. A power-assist door only lightens the push on the leaf; the person still opens it, and it serves an opening where a full power swing into a corridor or a lobby is unwanted. {note}
+
+## The operator drive shall be as indicated in the datasheet.
+
```datasheet
−label: Protection plates
+label: Power Operator Drive
+type: radio
+options:
+ - "Electromechanical"
+ - "Electrohydraulic"
+default: "Electromechanical"
+```
+
+## An electromechanical operator drives the arm through a motor and a gear train and closes by spring, and is the drive most low-energy operators use. An electrohydraulic operator pairs the motor with a hydraulic closer body and closes with closer-type control, which holds its closing speed through a wider temperature range at an exterior leaf. {note}
+
+## The operator mounting shall be as indicated in the datasheet.
+
+```datasheet
+label: Power Operator Mounting
+type: select
+options:
+ - "Surface-mounted on the push face with a parallel arm"
+ - "Surface-mounted on the pull face with a regular arm"
+ - "Concealed overhead in the frame head"
+```
+
+## A push-face mounting keeps the arm on the side the leaf swings toward and is the mounting a corridor or an out-swinging entrance takes; a pull-face mounting puts the arm on the side the leaf swings away from and is the more efficient geometry where the frame soffit is clear; a concealed operator disappears into a frame head built deep enough to take it and is serviced by removing the head cover. The mounting follows the swing, the stop condition, and the frame depth at each opening, which is why no one mounting is the norm. {note}
+
+## The knowing-act actuators furnished at each power-operated opening shall be as indicated in the datasheet.
+
+```datasheet
+label: Knowing-Act Actuators Furnished
type: checkbox
options:
− - Kick plate (push side)
− - Mop plate (wet areas)
− - Armor plate (high abuse)
− - Push plate
− - Pull plate
+ - "Wall-mounted push plate"
+ - "Bollard-mounted push plate"
+ - "Wireless push plate"
+ - "Touchless wave sensor"
+ - "Push-and-go operation from the leaf"
+ - "Key switch"
+ - "Release from the access control system"
default:
− - Kick plate (push side)
+ - "Wall-mounted push plate"
```
−# Thresholds, Weatherstripping, and Gasketing {toc}
+## A push plate is the plainest knowing act and the one every person recognizes; a wireless plate avoids a conduit to a bollard or a glass wall. A wave sensor reads a hand held near it and is selected where hands are gloved, full, or kept off surfaces, at the cost of occasional false actuation from passing traffic. Push-and-go starts the operator when the leaf is pushed a few degrees by hand, so there is no actuator to find, and it suits a leaf that is also used manually all day. A key switch or an access control release confines the operated opening to the people it is intended for. {note}
−## The threshold and seal package controls air, water, smoke, and sound at the opening perimeter, and ADA limits the threshold profile a wheelchair must cross. {note}
+## The operator shall open and close the leaf within the speed, time, kinetic energy, and force limits of ANSI/BHMA A156.19, and the force required to stop the leaf at any point of its travel shall not exceed 15 lbf.
−### A threshold seals and transitions the floor at the opening; weatherstripping at the head and jambs and a sweep or automatic door bottom at the base complete the seal. Smoke seals are required on smoke-rated assemblies, acoustic seals on sound-rated assemblies, and weather seals on exterior openings. A sound-rated door needs both perimeter gasketing and an automatic door bottom to reach its rated STC. {note}
+## On loss of power, the operator shall allow the leaf to be opened manually and to close under its spring, within the manual operating forces ANSI/BHMA A156.19 permits with power off.
−## Thresholds shall comply with ANSI/BHMA A156.21 and gasketing shall comply with ANSI/BHMA A156.22.
+## Actuators shall be located outside the arc of the swing where a person operating them stands clear of the moving leaf and within view of the opening, and shall be mounted at the height the Accessible Opening Requirements section of this standard states for operable parts.
−## Thresholds on accessible routes shall not exceed 1/2 in in total height, per ICC A117.1.
+## Each power-operated leaf shall carry, on both faces, the signage ANSI/BHMA A156.19 requires for the operator class furnished.
−## Any vertical face of a threshold on an accessible route shall not exceed 1/4 in in height.
+## At a latched opening, the operator shall be furnished with an electric strike, an electrified lock, or electric latch retraction from the Electrified Hardware section of this standard, interlocked so that the latch is released before the operator begins to open the leaf.
−## The remainder of a threshold rise above 1/4 in shall be beveled at a slope no steeper than 1:2.
+## An operator at a fire door assembly or a smoke and draft control assembly shall close and latch the leaf, and its actuators shall be disabled, on activation of the fire alarm system and on loss of power, through the release described under the Fire Alarm Release article of this standard.
−## Smoke-rated openings shall be provided with listed smoke-seal gasketing at the head, jambs, and meeting stiles.
+## The Contractor shall coordinate a dedicated 120 V branch circuit to each operator location with the electrical work, and the operator, its actuators, and the low-voltage wiring between them shall be furnished under this standard.
−## Exterior openings shall be provided with full perimeter weatherstripping and a door bottom seal appropriate to the sill condition.
+# Door Stops and Silencers {toc}
−## Sound-rated openings shall be provided with both perimeter acoustic gasketing and an automatic door bottom.
+## Door stops and auxiliary hardware shall conform to ANSI/BHMA A156.16, and overhead stops to ANSI/BHMA A156.8.
−### Omitting the automatic door bottom on a sound-rated assembly is a frequent miss that is only discovered during testing and balancing or acoustic commissioning, after the opening is installed. {note}
+## A stop shall be furnished at every opening where the leaf, its trim, or its hardware would otherwise strike a wall, a window, a casework unit, or adjacent equipment within the full arc of the swing.
−## The door bottom type shall be selected to suit the sill, with an automatic (drop-seal) door bottom where a continuous sill seal is required and a surface sweep where a threshold-only seal is adequate.
+## The stop type used as the project standard shall be as indicated in the datasheet.
```datasheet
−label: Threshold height (accessible route)
+label: Project Standard Door Stop
+type: select
+options:
+ - "Wall-mounted bumper stop"
+ - "Floor-mounted dome stop"
+ - "Overhead concealed stop"
+ - "Overhead surface stop"
+ - "Dead stop integral to the closer arm"
+default: "Wall-mounted bumper stop"
+```
+
+## A wall stop takes the lever at the height of the lever, which is where the force is, and needs a wall within the swing with backing behind it. A floor stop is the lowest-cost stop and the one a cane or a wheel catches, and it is set where the leaf's bottom rail meets it. An overhead stop moves the whole problem to the head of the opening where no wall is reachable, concealed in the leaf and frame or mounted on their surface. A dead stop in the closer arm uses the closer as the stop and loads the leaf's top rail with every slam. {note}
+
+## Wall stops and wall-mounted magnetic holders shall be fastened into the in-wall backing furnished under [[sync/gypsum-board-assemblies]], and where no backing exists behind the stop location, an overhead stop or a floor stop shall be furnished in its place.
+
+## Floor stops shall not be located within the maneuvering clearance of an accessible opening or in the path of travel across the opening.
+
+## Silencers shall be furnished at every hollow metal frame that receives no perimeter gasketing, three at the strike jamb of a single opening and two at the head of a pair.
+
+# Protection Plates and Push and Pull Trim {toc}
+
+## Protection plates and push and pull trim shall conform to ANSI/BHMA A156.6.
+
+## The protection plates furnished at the openings the hardware schedule assigns them to shall be as indicated in the datasheet.
+
+```datasheet
+label: Protection Plates Furnished
+type: checkbox
+options:
+ - "Kick plate on the push face"
+ - "Mop plate on the pull face"
+ - "Armor plate on the push face"
+ - "Stretcher plate on both faces"
+ - "Edge guard on the lock stile"
+default:
+ - "Kick plate on the push face"
+```
+
+## A kick plate takes the shoe and the cart at the bottom of the push face; a mop plate takes the mop on the pull face where the kick plate is not; an armor plate extends the kick plate to the height a cart, a bed, or a gurney strikes; a stretcher plate sits at the height of a stretcher rail; an edge guard wraps the lock stile where a cart catches the edge. The plates are scheduled where the traffic is, which is why they are a per-opening assignment and not a project-wide one. {note}
+
+## Kick plate height shall be as indicated in the datasheet.
+
+```datasheet
+label: Kick Plate Height
type: range
unit: in
−min: 0
−max: 0.5
−step: 0.125
−default: 0.25
+min: 6
+max: 16
+setpoints: [6, 8, 10, 12, 16]
+default: 10
```
+## Armor plate height shall be as indicated in the datasheet.
+
```datasheet
−label: Perimeter seal package
−type: radio
+label: Armor Plate Height
+type: range
+unit: in
+min: 24
+max: 48
+step: 2
+```
+
+## Plate material shall be as indicated in the datasheet.
+
+```datasheet
+label: Protection Plate Material
+type: select
options:
− - None (interior, non-rated)
− - Smoke seal (smoke-rated)
− - Acoustic seal (sound-rated)
− - Weather seal (exterior)
−default: Smoke seal (smoke-rated)
+ - "Stainless steel"
+ - "Brass"
+ - "Bronze"
+ - "Aluminum"
+ - "Laminated plastic or acrylic"
+default: "Stainless steel"
```
+## A stainless plate is the material through its thickness and matches the 630 finish family; brass and bronze match the warm finishes and show every scuff; aluminum is the lightest and least costly metal and dents; a plastic plate matches a laminate-faced leaf and is selected where a metal plate on a wood or laminate face is not wanted. A 10 in. kick plate covers the zone a shoe reaches, and an armor plate is sized to the height of whatever strikes the leaf, which is why its height has no norm. {note}
+
+## Plates shall be sized 2 in. less than the leaf width on the push face and 1 in. less than the leaf width on the pull face, and shall be attached with countersunk fasteners, or with an adhesive backing where the leaf's listing or construction does not admit screws.
+
+## Plates on a fire-rated leaf shall not extend higher above the bottom of the leaf than the leaf's listing permits, and a plate extending higher than 16 in. above the bottom of a rated leaf shall be a listed plate installed as the listing names.
+
+## Push and pull trim at openings that carry no latch shall be as indicated in the datasheet.
+
```datasheet
−label: Door bottom type
−type: radio
+label: Push and Pull Trim Furnished
+type: checkbox
options:
− - None
− - Surface sweep
− - Automatic (drop-seal) door bottom
−default: None
+ - "Push plate"
+ - "Pull plate with a pull"
+ - "Offset pull"
+ - "Push bar and pull bar"
+default:
+ - "Push plate"
+ - "Pull plate with a pull"
```
−# Pair Hardware: Coordinators and Flushbolts {toc}
+## Push and pull trim shall be through-bolted to each other across the leaf where no latch chassis carries the pull, and the pull shall be mounted within the height range the Accessible Opening Requirements section of this standard states.
−## Pairs of doors need extra hardware so the leaves close and latch in the correct order. {note}
+# Pair Hardware: Coordinators, Flush Bolts, and Mullions {toc}
−### A coordinator forces the inactive leaf to close before the active leaf so an astragal or overlapping edge seats correctly. Flushbolts secure the inactive leaf top and bottom; automatic flushbolts release when the active leaf opens and are required on fire-rated pairs without a mullion. {note}
+## Coordinators and removable mullions shall conform to ANSI/BHMA A156.3, flush bolts and surface bolts to ANSI/BHMA A156.16, and every item at a fire-rated pair shall be covered by the assembly listing.
−## A coordinator shall be provided on pairs with an astragal or overlapping edge where the leaves must close in sequence.
+## The latching arrangement at pairs carrying exit devices shall be as indicated in the datasheet, and the hardware schedule governs any pair it assigns a different arrangement.
−## Automatic or constant-latching flushbolts shall be provided on the inactive leaf of fire-rated pairs that do not use a removable mullion.
+```datasheet
+label: Latching Arrangement at Pairs With Exit Devices
+type: select
+options:
+ - "Removable mullion with a rim device on each leaf"
+ - "Vertical rod device on each leaf"
+ - "Mortise device on the active leaf with a vertical rod device on the inactive leaf"
+ - "Exit device on the active leaf with automatic flush bolts on the inactive leaf"
+```
−## A removable mullion may be used in place of vertical-rod or flushbolt hardware on rated pairs where the schedule permits.
+## A removable mullion gives each leaf a rim device latching into a fixed strike, which is the most reliable latch at a pair and keeps every rod and floor strike off the opening; the mullion divides the clear width when it is in and is keyed out for a wide load. Vertical rod devices on both leaves leave the full width clear at every opening, at the cost of two devices with rods to adjust. A mortise device on the active leaf with a rod device on the inactive leaf gives the active leaf a lockset-type latch and the inactive leaf an independent latch. An exit device on the active leaf with flush bolts on the inactive one is the lowest cost and leaves the inactive leaf without panic release, which is admissible only where the inactive leaf is not required for egress. {note}
+## The inactive leaf latching at pairs that carry no exit device shall be as indicated in the datasheet.
+
```datasheet
−label: Pair latching method
−type: radio
+label: Inactive Leaf Latching at Pairs Without Exit Devices
+type: select
options:
− - Removable mullion with rim devices
− - Vertical-rod devices on both leaves
− - Active leaf device with flushbolts on inactive leaf
−default: Removable mullion with rim devices
+ - "Automatic flush bolts"
+ - "Constant-latching flush bolts"
+ - "Manual flush bolts"
+ - "Surface bolts"
```
−# Finishes {toc}
+## Automatic flush bolts retract when the active leaf is opened and project when it closes, so the inactive leaf latches without anyone remembering to throw a bolt. Constant-latching bolts project whenever the inactive leaf is closed and release by a trigger when the active leaf opens. Manual flush bolts are thrown by hand and are what a fire door inspector finds unthrown. Surface bolts are mounted on the face and are selected where the leaf edge cannot be mortised. {note}
−## Finish is specified by the BHMA designation and matched across every item in a set so the opening reads as one. {note}
+## At a fire-rated pair without a mullion, the inactive leaf shall be latched by automatic or constant-latching flush bolts, and manual flush bolts shall be furnished only where the inactive leaf is not required for egress, NFPA 80 permits them at that pair, and the authority having jurisdiction accepts them.
−### The 600-series numbers (626, 630, 613) are the current ANSI/BHMA A156.18 designations that replaced the older US designations (US26D, US32D, US10B); both still appear in practice and should be listed together. Mixing finish sources without a sample submittal produces visible variation between, for example, hinges from one maker and locksets from another. {note}
+## A coordinator shall be furnished at every pair that carries an overlapping astragal or a meeting-edge seal that requires the inactive leaf to close first and at every pair with automatic flush bolts, together with the filler bar and the mounting brackets its length requires.
−## All hardware finishes shall comply with ANSI/BHMA A156.18 and shall be specified by both the BHMA 600-series number and the corresponding US designation.
+## The astragal at a pair is furnished with the leaves under the door standard that supplies them, and this standard furnishes the coordinator, the bolts, the mullion, and the meeting-stile seal that work with it. {note}
−## Finishes shall be matched across all items within a hardware set, and a finish match between items from different manufacturers shall be verified by a sample submittal.
+## Removable mullions at fire-rated pairs shall be listed for the rating period and shall be keyed removable only where the listing provides for it, and a mullion at a pair carrying fire exit hardware shall be reinstalled and secured after every removal.
−## Where a project finish is not designated, satin chromium (US26D / 626) shall be the default for interior hardware and satin stainless steel (US32D / 630) for exterior or high-moisture openings.
+## Where an electrified mullion carries power to a device on the leaf, the mullion shall be furnished with its power transfer as part of the hardware set.
+# Thresholds, Gasketing, and Door Bottoms {toc}
+
+## Thresholds shall conform to ANSI/BHMA A156.21, and gasketing, door bottoms, and edge seal systems shall conform to ANSI/BHMA A156.22.
+
+## The threshold type at exterior openings shall be as indicated in the datasheet.
+
```datasheet
−label: Hardware finish
+label: Threshold Type at Exterior Openings
type: select
options:
− - Satin chromium US26D / 626 (interior default)
− - Satin stainless steel US32D / 630 (exterior / high-moisture)
− - Oil-rubbed bronze US10B / 613 (institutional / hospitality)
− - Satin brass US4 / 606
− - Bright stainless steel US32 / 629
−default: Satin chromium US26D / 626 (interior default)
+ - "No threshold"
+ - "Saddle threshold"
+ - "Bumper-seal threshold"
+ - "Interlocking threshold with a hook door bottom"
+ - "Thermal-break threshold"
+ - "Offset threshold with a door bottom seal"
```
−# Keying and Cylinders {toc}
+## A saddle is a flat bar that closes the gap and takes a sweep on the leaf; a bumper-seal threshold carries a vinyl insert the leaf closes against; an interlocking threshold hooks a shaped door bottom and is the tightest against driven rain and the one a wheel feels most; a thermal-break threshold divides the inside and outside halves with a plastic bridge where the sill would otherwise condense; an offset threshold steps up to an interior floor that is higher than the exterior slab. The condition at the sill, the exposure, and the accessible route together select the threshold at each exterior opening. {note}
−## The keying plan defines who can open what, and it must be designed with the Owner before submittals or the contractor inherits a design problem. {note}
+## Threshold material shall be as indicated in the datasheet.
−### Cylinders may be keyed alike within a group, master-keyed so one key opens many openings, or grand-master-keyed across master groups. An interchangeable core (SFIC or LFIC) lets the Owner re-key without removing the lock, but cores are manufacturer-proprietary, so a core brand that differs from the Owner's existing system forces a facility-wide re-key. {note}
+```datasheet
+label: Threshold Material
+type: select
+options:
+ - "Extruded aluminum, mill finish"
+ - "Extruded aluminum, dark bronze anodized"
+ - "Extruded bronze"
+ - "Stainless steel"
+default: "Extruded aluminum, mill finish"
+```
−## Cylinders and input devices shall comply with ANSI/BHMA A156.28.
+## Aluminum is the lowest cost and the lightest and is the threshold at the great majority of openings, mill or anodized to match the storefront; bronze is selected for its color at an entrance; stainless is selected where salt, washdown, or a cart ramp would wear through an aluminum threshold. {note}
−## A complete keying schedule shall be developed with the Owner before hardware submittals, establishing master-key levels, keyed-alike groups, and the cylinder or core system.
+## Thresholds at interior openings shall be furnished where [[drawing: the hardware schedule]] assigns one, at a change of floor finish, at a sound-rated opening, and at a smoke or fire-rated opening whose listing requires one.
−### A hardware specification without a keying plan forces the contractor to author the keying design during submittals, which is outside their scope and a common source of schedule delay. The Owner must be engaged at the design stage. {note}
+## Thresholds in an accessible route shall meet the change-in-level limits stated under the Accessible Opening Requirements section of this standard.
−## Where interchangeable cores are specified, the core format and keyway shall match the Owner's existing master-key system.
+## The gasketing furnished at exterior openings shall be as indicated in the datasheet.
−### Selecting an SFIC core brand different from the Owner's existing cylinders requires re-keying the entire facility to a single system, which is rarely the intent and always costly. The existing system must be confirmed before the core brand is chosen. {note}
+```datasheet
+label: Gasketing at Exterior Openings
+type: checkbox
+options:
+ - "Head and jamb perimeter weatherstripping"
+ - "Surface-applied door bottom sweep"
+ - "Automatic door bottom"
+ - "Rain drip at the head"
+ - "Meeting-stile seal at pairs"
+ - "Corner seal pads"
+default:
+ - "Head and jamb perimeter weatherstripping"
+ - "Surface-applied door bottom sweep"
+ - "Rain drip at the head"
+```
−## Keys shall be stamped "Do Not Duplicate" only where the Owner directs, and a restricted or patented keyway shall be used where key control is required.
+## The gasketing furnished at the interior openings the hardware schedule assigns it to shall be as indicated in the datasheet.
−## The key bitting record shall be delivered directly to the Owner under separate cover and shall not be included in general closeout documents.
+```datasheet
+label: Gasketing at Interior Openings
+type: checkbox
+options:
+ - "Smoke and draft control gasketing listed to UL 1784"
+ - "Surface-applied intumescent edge seal at rated openings"
+ - "Acoustic perimeter seal"
+ - "Automatic door bottom"
+ - "Light seal"
+ - "Sound-rated meeting-stile seal at pairs"
+default: []
+```
+## The weatherstripping material at exterior openings shall be as indicated in the datasheet.
+
```datasheet
−label: Keying system
−type: radio
+label: Weatherstripping Material
+type: select
options:
− - Keyed alike (single group)
− - Master-keyed
− - Grand-master-keyed
− - Construction keying with Owner change-over
−default: Master-keyed
+ - "Silicone bulb or fin"
+ - "Neoprene or EPDM bulb"
+ - "Pile brush"
+ - "Vinyl fin"
+ - "Magnetic strip"
```
+## Silicone holds its seal from well below freezing to the heat of a sunlit leaf and outlasts every other material, at the highest price; neoprene and EPDM seal as well when new and harden over a decade; a pile brush seals against a leaf that is not flat and lets air through by design; vinyl is the lowest cost and stiffens in the cold; a magnetic strip seals a steel leaf the way a refrigerator seals and needs a steel face to pull against. {note}
+
+## The door bottom at sound-rated openings, and at smoke and draft control assemblies whose listing requires one, shall be as indicated in the datasheet.
+
```datasheet
−label: Cylinder / core type
−type: radio
+label: Door Bottom at Sound-Rated and Smoke-Rated Openings
+type: select
options:
− - Conventional cylinder
− - Small-format interchangeable core (SFIC)
− - Large-format interchangeable core (LFIC)
− - Restricted / patented keyway
−default: Small-format interchangeable core (SFIC)
+ - "Surface-mounted automatic door bottom"
+ - "Semi-mortised automatic door bottom"
+ - "Mortised automatic door bottom"
```
+## An automatic door bottom retracts into its housing while the leaf is moving and drops onto the threshold or the floor in the last part of the closing arc, which is what lets it clear a carpet inside and still seal. A surface-mounted unit is screwed to the face and is visible; a semi-mortised unit sits in a shallow groove with its face plate flush; a mortised unit is hidden in the bottom rail and needs a leaf built with the mortise and a bottom rail deep enough to take it. {note}
+
+## Gasketing at a fire-rated opening and at a smoke and draft control assembly shall be a product listed for that use, installed as the listing and NFPA 80 or NFPA 105 require, and shall not be substituted by an unlisted gasket in the same profile.
+
+## Where the positive-pressure edge seal category selected under the door standard places the intumescent seal in the hardware sets, the Contractor shall record on the hardware schedule which openings receive the seal under this standard, so that each opening receives exactly one seal.
+
+## The acoustic seal set furnished under this standard at a sound-rated opening shall be the seals and the threshold described in the leaf manufacturer's test report for the scheduled rating.
+
+## A sound-rated opening reaches the rating of its tested assembly only with the seal set that was in the test, and the automatic door bottom is the item most often left off. The absence is found at acoustic commissioning, after the leaf is hung and the floor is down. {note}
+
+## Gasketing at exterior openings shall be installed continuously around the head and both jambs without interruption at the hinge and strike preparations, and the Contractor shall verify after the closer is adjusted that gasketing compression does not prevent the leaf from latching.
+
+# Hardware Finish {toc}
+
+## Hardware finishes shall be designated by the three-digit codes of ANSI/BHMA A156.18 on the hardware schedule and on every submittal.
+
+## The finish of hardware at interior openings shall be as indicated in the datasheet.
+
```datasheet
−label: Keyed by
−type: radio
+label: Hardware Finish at Interior Openings
+type: select
options:
− - Owner-keyed (factory to Owner system)
− - Contractor-keyed with Owner change-over
−default: Owner-keyed (factory to Owner system)
+ - "BHMA 605, bright brass, clear coated"
+ - "BHMA 606, satin brass, clear coated"
+ - "BHMA 612, satin bronze, clear coated"
+ - "BHMA 613, oil-rubbed bronze"
+ - "BHMA 619, satin nickel plated"
+ - "BHMA 622, flat black coated"
+ - "BHMA 625, bright chromium plated"
+ - "BHMA 626, satin chromium plated"
+ - "BHMA 628, satin aluminum, clear anodized"
+ - "BHMA 630, satin stainless steel"
+ - "BHMA 652, satin chromium plated on a steel base"
+ - "BHMA 689, aluminum painted"
+ - "BHMA 690, dark bronze painted"
+default: "BHMA 626, satin chromium plated"
```
−# Electrified Hardware {toc}
+## The finish of hardware at exterior openings and at openings exposed to washdown or sustained high humidity shall be as indicated in the datasheet.
−## Electrified items add access control and remote release at the opening, and the fail mode must match whether the door is on an egress path or secures an asset. {note}
+```datasheet
+label: Hardware Finish at Exterior and Wet Openings
+type: select
+options:
+ - "BHMA 612, satin bronze, clear coated"
+ - "BHMA 613, oil-rubbed bronze"
+ - "BHMA 622, flat black coated"
+ - "BHMA 626, satin chromium plated"
+ - "BHMA 629, bright stainless steel"
+ - "BHMA 630, satin stainless steel"
+ - "BHMA 690, dark bronze painted"
+default: "BHMA 630, satin stainless steel"
+```
−### A fail-safe device unlocks when power is removed and is required on egress doors and on fire-alarm-released hold-opens, so people are never trapped on a power loss. A fail-secure device locks when power is removed and is appropriate for protecting a secure room. Choosing the wrong mode is a life-safety defect on egress and a security defect on a secured opening. {note}
+## A plated finish is a coating over a different base metal, and once it wears through at a lever's contact point the base is exposed and the mark is permanent. A solid stainless finish is the base metal itself, so wear polishes it rather than breaching it, which is the mechanism behind its use where hands touch hardware all day and where salt air or washdown reaches it. The brass and bronze families are living finishes unless clear coated, and the clear coat is what keeps them even across a building. The painted finishes, 689 and 690, are how a closer or a holder with a cast aluminum body is brought to the color of the plated hardware beside it. {note}
−## Electrified hardware shall be specified at the product and hardware-set level in this standard; power supplies, conduit, and system programming are governed by [[sync/access-control-systems]].
+## All hardware within one set shall carry the same finish code, and closers, holders, and other items available only in a painted finish shall be furnished in the painted finish that matches the set.
−## Egress openings and electromagnetic hold-opens shall use fail-safe devices that release on loss of power or on a fire-alarm signal.
+## Where a required item is not manufactured in the selected finish code, the supplier shall submit the closest available finish for review before the item ships.
−## Secured openings that are not on an egress path may use fail-secure devices that remain locked on loss of power.
+## Finish shall be matched across manufacturers on the actual items, and the accepted sample shall be the standard for every item of that finish code on the project.
−## Electrified hardware shall operate at 24VDC unless a specific item requires 12VDC, and the power supply VA rating shall be verified against the connected hardware load.
+# All-Glass Door Hardware {toc}
−### 24VDC is preferred over 12VDC because it draws less current and tolerates the voltage drop of longer wire runs, which matters as door count and run length grow. {note}
+## Patch fittings, rails, pivots, locks, and closers for all-glass swing doors hung in interior glass partitions shall be furnished under this standard, rated by their manufacturer for the leaf size, the leaf weight, and the glass thickness indicated below.
−## Power transfer to the door leaf shall be provided by a concealed electric hinge, an electric power-transfer device, or a door loop, coordinated with the door and frame prep.
+## The glass thickness the all-glass door fittings are rated for shall be as indicated in the datasheet.
−## All electrified hardware locations, conduit, and power supplies shall be coordinated with [[sync/access-control-systems]] and [[sync/fire-alarm-systems]] before frames are set.
+```datasheet
+label: Glass Thickness Rated for All-Glass Door Fittings
+type: range
+unit: in
+min: 0.375
+max: 0.75
+setpoints: [0.375, 0.5, 0.75]
+default: 0.5
+```
+## Patch fittings and rails are machined for one glass thickness and clamp on it; a 3/8 in. leaf in a 1/2 in. fitting rocks in the clamp and a 1/2 in. leaf does not enter a 3/8 in. fitting. The 1/2 in. leaf is the common interior door, 3/8 in. serves a small and light leaf, and 3/4 in. serves a tall or wide one. The tempered or laminated panel itself, its thickness, and its edge work are governed by [[sync/interior-glazing]], which glazes the leaf to the thickness selected here. {note}
+
+## The fitting type at all-glass swing doors shall be as indicated in the datasheet.
+
```datasheet
−label: Electrified hardware item
+label: All-Glass Door Fitting Type
type: select
options:
− - None
− - Electric strike
− - Electrified mortise lock
− - Electrified cylindrical lock
− - Electrified exit device (electric latch retraction)
− - Electromagnetic hold-open
−default: None
+ - "Patch fittings at the top and bottom corners"
+ - "Full-width top and bottom rails"
+ - "Patch fitting at the top with a bottom rail"
```
+## A corner patch is the smallest piece of metal on the leaf and carries the pivot and the lock in the corners; a full-width rail carries the pivot, the lock, and a door bottom seal along the whole edge, takes a heavier leaf, and reads as a framed bottom; a top patch over a bottom rail puts the seal and the lock at the floor and keeps the head clean. {note}
+
+## The closing device at all-glass swing doors shall be as indicated in the datasheet.
+
```datasheet
−label: Fail mode
−type: radio
+label: All-Glass Door Closing Device
+type: select
options:
− - Fail-safe (de-energize to unlock) - egress / hold-open
− - Fail-secure (de-energize to lock) - secured non-egress
−default: Fail-safe (de-energize to unlock) - egress / hold-open
+ - "Floor closer with a bottom pivot in the floor"
+ - "Overhead concealed closer in the partition header"
+ - "Surface closer mounted to a top rail"
+ - "Free-swinging pivots without a closer"
```
+## A floor closer holds the closer under the floor finish and needs a recess in the slab and a cement case set before the floor goes down; an overhead concealed closer sits in the partition header and needs a header deep enough to take it; a surface closer on a top rail is the one closer that goes on after the fact; free-swinging pivots leave the leaf where it is pushed and are selected where the partition carries no acoustic or privacy function. {note}
+
+## Locks at all-glass swing doors shall be as indicated in the datasheet.
+
```datasheet
−label: Operating voltage
−type: radio
+label: All-Glass Door Lock
+type: select
options:
− - 24VDC
− - 12VDC
−default: 24VDC
+ - "No lock"
+ - "Patch lock at the lock stile with a strike on the adjacent panel or jamb"
+ - "Bottom rail deadbolt into a floor strike"
+ - "Electromagnetic lock in the header with a leaf armature"
```
−# Installation {toc}
+## A patch lock latches into the adjacent panel or a wall jamb at lever height and is the lock a person expects to find; a bottom rail bolt drops into a floor strike and leaves the stile clean but is thrown by bending down; a header magnet needs no cutout in the leaf and is an electrified lock under the Electrified Hardware section of this standard, with all of that section's egress obligations. {note}
−## Correct installation locations and adjustments are what make compliant hardware actually perform, and the DHI template governs the prep. {note}
+## All-glass swing doors in a means of egress shall carry the same egress release, operating force, and operable-part obligations as every other door under this standard.
−### DHI WDHS.3 fixes the standard locations: the top hinge 5 in from the head of the door, the bottom hinge 10 in from the floor, and additional hinges evenly spaced between. These locations must match the shop frame prep, so the template controls coordination, not field judgment. {note}
+## Floor closers at all-glass doors shall be set in a cement case anchored to the slab before the floor finish is placed, with the pivot location confirmed against the partition shop drawings.
−## Hardware shall be installed in the locations established by DHI WDHS.3 and the approved frame prep templates.
+## A frameless all-glass entrance bought as a system, with its glass panels, patch fittings, rails, pivots, and closers engineered together, is governed by [[sync/all-glass-entrances]]. The hardware furnished with aluminum entrance doors is governed by [[sync/aluminum-entrances-and-storefronts]]. {note}
−## The top hinge shall be located 5 in from the head of the door and the bottom hinge 10 in from the floor, with intermediate hinges evenly spaced.
+# Electrified Hardware {toc}
−## Lockset and lever centerlines shall be mounted between 34 in and 48 in above the finished floor, per ICC A117.1.
+## Electrified Items and Coordination {toc}
−## Lockset and lever centerlines should be mounted between 38 in and 44 in above the finished floor as the standard installed range.
+### Electrified locking devices shall conform to ANSI/BHMA A156.25, electromagnetic locks to ANSI/BHMA A156.23, electric strikes to ANSI/BHMA A156.31, and delayed egress locking systems to ANSI/BHMA A156.24, and electrified locking hardware shall additionally be listed under UL 1034 where the opening is required to resist burglary.
−## Door viewers shall be mounted at 60 in above the finished floor, with an additional accessible viewer at 48 in where an accessible viewer is required.
+### The electrified hardware items furnished on the project shall be as indicated in the datasheet, assigned opening by opening on the hardware schedule.
−## Fire door hardware shall be installed without field modifications prohibited by NFPA 80, and no holes shall be cut in a fire door or frame beyond those permitted by the listing.
+```datasheet
+label: Electrified Hardware Items Furnished
+type: checkbox
+options:
+ - "Electric strike"
+ - "Electromagnetic lock"
+ - "Electrified mortise lockset"
+ - "Electrified bored lockset"
+ - "Electrified exit device trim"
+ - "Electric latch retraction exit device"
+ - "Delayed egress locking device"
+ - "Electromagnetic hold-open device"
+ - "Electrified removable mullion"
+ - "Key switch"
+ - "Credential reader integral to the lock trim"
+default: []
+```
−## Door closers shall be adjusted in the field for sweep speed, latch speed, backcheck, and opening force after the door and frame are fully installed.
+### The electrified locking device at an opening is the mechanism that secures it, and the families differ in what they do when nothing is powered. An electrified lockset or an electrified exit device trim keeps a mechanical latch and a free-turning egress lever, so the egress side always works and only the access side is controlled. An electric strike leaves the lock mechanical and releases the keeper in the frame. An electromagnetic lock has no latch at all and holds the leaf by magnetic force, so every egress release is an electrical event, and it is the device that attracts the most code conditions. A delayed egress device holds an egress door for the interval the code allows after the device is pushed and is permitted only in the occupancies the code names. {note}
−## Electrified hardware shall be installed, terminated, and functionally tested by the manufacturer-certified installer.
+### The hardware supplier shall issue, for every electrified opening, the point-to-point wiring diagram listed under Action Submittals, and the hardware supplier and the access control installer shall jointly confirm every electrified opening against it before the frames are fabricated.
−## Hardware shall be installed only after painting and finishing of the door and frame are substantially complete to avoid finish damage.
+### The raceway in a wood leaf is furnished under [[sync/wood-doors]], the conduit, junction boxes, and through-bolt reinforcement in hollow metal are furnished under [[sync/exterior-doors-and-frames]], and the controllers, power supplies, and cabling beyond the opening are furnished under [[sync/access-control-systems]]; this standard furnishes the devices, the power transfer, and the connections at the opening. {note}
+## Fail Mode at Electrically Locked Openings {toc}
+
+### The fail mode at each electrically locked opening shall be as indicated in the datasheet.
+
```datasheet
−label: Lever centerline mounting height
−type: range
−unit: in AFF
−min: 34
−max: 48
−step: 1
−default: 40
+label: Fail Mode at Electrically Locked Openings
+type: select
+drawing_ref: "the hardware schedule"
+options:
+ - "Fail safe, unlocked on loss of power"
+ - "Fail secure, locked on loss of power"
+default: deferred
```
+### A door in a means of egress that is electrically locked shall unlock on loss of power to the locking device, unless the installation satisfies in full a provision of [[parameter: adopted-building-code]] that expressly permits the arrangement without that release.
+
+### Every electromagnetic lock on a door in a means of egress shall release on activation of the fire alarm system, on activation of the automatic sprinkler system where the permitting provision requires it, on loss of power, and on operation of the request-to-exit device and the manual release the permitting provision requires at that opening.
+
+### A sensor-released or electromagnetically locked egress door shall be furnished with the manual release, the signage, and the door-mounted release hardware the provision that permits it requires, and the arrangement shall be accepted by the authority having jurisdiction before the device is ordered.
+
+### A delayed egress device shall release not more than 15 seconds after it is actuated, or 30 seconds where the authority having jurisdiction has approved the longer delay, and shall release immediately on fire alarm activation, on sprinkler activation, and on loss of power.
+
+### The fail mode carries opposite consequences at the two ends of the opening. A fail-secure device that loses power holds people on the wrong side of it; a fail-safe device that loses power opens a secured space to anyone in the building. Which risk a project accepts is a decision for the Owner with the Architect, and it belongs on the hardware schedule so it is recorded per opening rather than assumed. {note}
+
+## Power Transfer to the Leaf {toc}
+
+### The method of transferring power into the leaf at openings with a leaf-mounted electrified item shall be as indicated in the datasheet.
+
+```datasheet
+label: Power Transfer Method
+type: select
+options:
+ - "Electric through-wire hinge"
+ - "Continuous hinge with integral wiring"
+ - "Concealed electric power transfer in the hinge edge"
+ - "Concealed armored door loop"
+ - "Surface-mounted armored door cord"
+```
+
+### A through-wire hinge carries a few conductors in a hinge that looks like every other hinge and is the lowest-cost transfer; its wires are the finest on the opening and the first thing to fail if the hinge is ever pulled. A wired continuous hinge carries more conductors along a hinge that already serves the high-cycle opening. A concealed electric power transfer mortises into the hinge edge of the leaf and the frame and carries the conductor count a latch-retraction device needs, at a mortise in both. A concealed loop is a flexible conduit between leaf and frame hidden in the hinge edge, and a surface cord is the same loop on the face and the one transfer that goes on an existing leaf without machining. {note}
+
+### Conductors crossing from the frame into the leaf shall be carried in a device made for that purpose and shall not be looped unprotected across the hinge line.
+
+### The transfer device shall be included in the hardware set for every opening carrying a leaf-mounted electrified item, and its conductor count and gauge shall match the device it feeds.
+
+### An unprotected conductor at the hinge line flexes through its full bend radius every time the door swings, which at a busy opening is hundreds of cycles a day. Its failure is intermittent long before it is total, which is why it is usually diagnosed as a controller fault first. {note}
+
+## Operating Voltage {toc}
+
+### Electrified hardware shall operate at the voltage indicated in the datasheet, and every device on the project shall be furnished for that voltage unless the hardware schedule states a different voltage at a named opening.
+
+```datasheet
+label: Electrified Hardware Operating Voltage
+type: radio
+options:
+ - "24 VDC"
+ - "12 VDC"
+default: "24 VDC"
+```
+
+### At the same power, a 24 VDC device draws half the current of a 12 VDC device, so the voltage drop on a given conductor run is half as large and the run to a remote opening can be twice as long before the device falls below its rated voltage. Devices that exist only at 12 VDC are the exception the schedule names. {note}
+
+### Each device shall be furnished with its rated voltage and its inrush and holding current stated on the wiring diagram, so that the power supply and the conductors furnished under [[sync/access-control-systems]] can be sized to hold the voltage at the device within the manufacturer's stated range under its rated load.
+
+### An electromagnetic lock that receives less than its rated voltage still energizes and still appears locked. It simply does not develop its rated holding force, and the deficiency is invisible until someone pulls hard enough to find it. {note}
+
+### Electrified hardware shall be supplied from Class 2 circuits fed by power supplies listed under UL 294, and no electrified hardware item shall be connected to line voltage at the opening.
+
+## Fire Alarm Release {toc}
+
+### Every electromagnetic hold-open device on a fire door assembly or a smoke and draft control assembly, every electromagnetic lock on a door in a means of egress, and every fire exit hardware device with electric latch retraction shall be connected to the building fire alarm system so that alarm activation releases the hold-open, releases the lock, and projects the latch.
+
+### The release circuit shall be arranged so that loss of power to the circuit also releases every device on it, and activation of the fire alarm system shall release every hold-open device within the affected zone simultaneously.
+
+### The Contractor shall coordinate the relay contacts, the release circuit conductors, and the device quantities with the fire alarm installer working under [[sync/fire-alarm-systems]], and the release point shall be recorded at the pre-installation conference.
+
+### Holding a fire door open with a wedge, a chair, a stop, or any device not released by the fire alarm system is prohibited by NFPA 80, and the Contractor shall neither do so during construction nor leave such a condition at turnover.
+
+# Accessible Opening Requirements {toc}
+
+## Openings on an accessible route shall comply with the accessibility standard adopted by the authority having jurisdiction, and where that standard and ICC A117.1 differ, the adopted standard shall govern.
+
+## The Architect shall identify the accessible route on the drawings, and the hardware schedule preparer shall confirm that every opening on that route complies with the requirements of this section.
+
+## Operable parts of door hardware on an accessible route, including levers, pulls, exit device actuating members, key cylinders operated by the public, push-to-exit controls, and power operator actuators, shall be mounted not less than 34 in. and not more than 48 in. above the finished floor.
+
+## Operable hardware on an accessible route shall be operable with one hand and shall not require tight grasping, tight pinching, or twisting of the wrist to operate.
+
+## The force required to operate operable hardware on an accessible route shall not exceed 5 lbf.
+
+## The force required to push or pull open an interior swinging door on an accessible route, other than a fire door assembly, shall not exceed 5 lbf applied at the latch edge, and an exterior door or a fire door assembly shall release its latch at not more than 15 lbf, be set in motion at not more than 30 lbf, and swing to the full open position at not more than 15 lbf.
+
+## Closers on an accessible route shall be adjusted so that, from an open position of 90 degrees, the leaf takes not less than 5 seconds to move to a position 12 degrees from the latch, and spring hinges shall be adjusted so that the leaf takes not less than 1.5 seconds to move from 70 degrees open to the closed position.
+
+## A threshold in an accessible route shall present a change in level of not more than 1/2 in., and any portion of that change exceeding 1/4 in. shall be beveled at a slope not steeper than 1:2.
+
+## The push face of a swinging door on an accessible route shall be smooth within 10 in. of the finished floor across the full width of the leaf, with any plate or joint in that zone within 1/16 in. of the plane of the face, except where the adopted standard exempts an all-glass leaf with a tapered bottom rail or shoe.
+
+## Where a fire door assembly requires a closing force that cannot be reconciled with the opening force limit, the Contractor shall raise the conflict in writing with the Architect and the authority having jurisdiction rather than adjusting the closer below the force needed to latch the leaf.
+
+## Maneuvering clearances required by the adopted accessibility standard shall be kept clear of floor stops, wall stops, holders, and pulls, and the Architect shall confirm the clearances shown at each accessible opening before frames are set.
+
+## The opening force limit and the hardware operating force limit are separate obligations that apply at the same time. A lever that meets the operable-force limit on a door whose closer is set above the opening-force limit leaves the opening non-compliant, and the reverse is equally true. Accessibility obligations are not selections; they apply wherever the route applies, and no datasheet entry in this standard relaxes them. {note}
+
+# Installation {toc}
+
+## Hardware shall be installed at the locations established by the approved hardware templates, at the locations of ANSI/NAAMM HMMA 831 in hollow metal and DHI WDHS.3 in wood leaves unless the hardware schedule locates an item otherwise, and in accordance with the manufacturer's published instructions.
+
+## Hardware shall be installed only after the leaves and frames are finished, except for the hinges and the items needed to hang the leaf for fitting, and finished hardware shall be protected from paint, plaster, and sealant through the remainder of the work.
+
+## Hardware at fire door assemblies shall be installed in accordance with NFPA 80, with no field modification of a labeled leaf or frame beyond the job-site preparations NFPA 80 permits, and no fastener hole shall be made in a labeled leaf or frame for an item the listing does not cover.
+
+## Fire door assemblies shall be installed to the clearances the listing and NFPA 80 require, and the Contractor shall report in writing any frame that is out of tolerance before hanging a leaf in it.
+
+## Closers shall be adjusted after the leaf and frame are fully installed, the gasketing is in place, and the building is under its normal pressure conditions, for sweep speed, latch speed, backcheck, and spring power, and the adjustment shall be recorded at every accessible opening.
+
+## Electrified hardware shall be installed, terminated, and functionally tested by the manufacturer-trained installer, with every conductor labeled at both ends and the wiring diagram marked up to the as-installed condition.
+
+## Thresholds shall be set in a full bed of sealant, anchored at the spacing the manufacturer publishes with fasteners of stainless steel or of the threshold material, and notched around the frame stops so that no gap remains at the jamb.
+
+## The Contractor shall coordinate the latch-side wall space at each opening with the tactile signage installed under [[sync/signage-and-egress-markings]], so that no stop, holder, or leaf in its open position obstructs the sign.
+
+## The Contractor shall instruct the Owner's maintenance personnel in the adjustment of closers, the operation of the keying system and the interchangeable cores, and the function of every electrified opening before final acceptance, and shall record the instruction.
+
+## Every installed item shall operate freely without binding, with the latch engaging the strike without forcing and the leaf closing and latching under its closer alone.
+
# Field Quality Control {toc}
−## Every opening is verified for operation, force, and life-safety function before acceptance. {note}
+## Every opening shall be operated through a full cycle after installation and adjustment, and any item that binds, fails to latch, or fails to hold its adjustment shall be corrected before the opening is presented for inspection.
−## Each opening shall be operated through a full cycle to confirm the latch, lock, closer, and seals function as specified.
+## At every accessible opening, the opening force and the closing time shall be measured with a door pressure gauge and a timer, recorded by opening mark, and corrected to the limits of the Accessible Opening Requirements section where they are exceeded.
−## Opening force and closer sweep timing shall be measured and recorded for every accessible-path opening, and any opening exceeding the ADA limits shall be re-adjusted.
+## Every fire door assembly shall receive the acceptance test NFPA 80 requires after installation, performed by a person with the qualifications NFPA 80 names, and the Contractor shall correct any leaf that does not close and latch under its closer alone, any clearance outside the listing, and any missing or defaced label before the inspection is recorded.
−## Fire-rated openings shall be tested for positive latching and proper closing on every cycle, and any opening that fails to latch shall be corrected before acceptance.
+## Every electrified opening shall be tested with the access control system and the fire alarm system in service to demonstrate the specified fail mode, the release on fire alarm, the release on loss of power, and the egress release, and the test shall be witnessed by the Architect or the Owner's representative and recorded.
−## Electrified hardware shall be functionally tested with the access control and fire alarm systems to confirm correct fail-safe or fail-secure operation and fire-alarm release.
+## Every power-operated opening shall be tested after installation to the opening and closing times, the stall force, and the manual operation with power off that ANSI/BHMA A156.19 requires, with the measured values recorded by opening mark.
−## Fire door assemblies shall be functionally inspected annually after acceptance, per NFPA 80, with results documented and retained by the Owner.
+## The cost of retesting an opening that fails a field test, and of the trades attending the retest, shall be borne by the Contractor.
+## Fire door assemblies are inspected and tested annually after acceptance under NFPA 80, and the acceptance record delivered at closeout is the baseline the Owner's inspector compares against. {note}
+
# Delivery, Storage, and Handling {toc}
−## Hardware shall be delivered in the manufacturer's original packaging, individually marked with the opening number and hardware set it serves.
+## Hardware shall be delivered in the manufacturer's packaging, each package marked with the opening mark and the hardware set it serves, with the templates and the fasteners packed with the item they serve.
−## Hardware shall be stored in a clean, dry, secure area and protected from weather, dust, and theft until installation.
+## Hardware shall be stored off the floor in a dry, locked room, and cylinders, cores, keys, and electrified devices shall be stored in a locked cabinet within that room under the control of one named person.
−## Keys and cores shall be kept under the Owner's or hardware supplier's secure control and shall not be left at the installation area.
+## Keys and cores shall not be issued to any trade except against a signed record, and the record shall be reconciled before the permanent cylinders are installed.
+## Finish hardware is the most portable material on a site and the one whose replacement never quite matches the rest of the set, which is why it is stored locked and issued against a record. {note}
+
# Warranty {toc}
−## Door closers shall carry a manufacturer warranty against defects in material and workmanship for a minimum of 10 years.
+## Each hardware manufacturer shall warrant its products against defects in materials and workmanship for not less than the period indicated in the datasheet.
−## Exit devices and locksets shall carry a manufacturer warranty for a minimum of 3 years.
+```datasheet
+label: Minimum Hardware Warranty Period
+type: range
+unit: yr
+min: 1
+max: 10
+setpoints: [1, 2, 3, 5, 10]
+default: 1
+```
−## Electrified hardware shall carry a manufacturer warranty for a minimum of 1 year, or the longer period offered by the manufacturer.
+## Door closers shall be warranted against defects in materials and workmanship, including loss of closing power and fluid leakage, for not less than the period indicated in the datasheet.
−## All other finish hardware shall carry the manufacturer's standard warranty, and warranty documents shall be delivered at closeout.
−
```datasheet
−label: Door closer warranty period
−type: radio
−options:
− - 10 years
− - 25 years
− - 30 years
−default: 10 years
+label: Minimum Door Closer Warranty Period
+type: range
+unit: yr
+min: 1
+max: 30
+setpoints: [1, 2, 5, 10, 25, 30]
+default: 10
```
−# Spare Parts {toc}
+## Closers are the item that fails in service, by a seal letting the fluid out or a spring losing its power, and the major manufacturers publish closer warranties of ten years and longer, so a closer floor set well above the general floor costs the project nothing. Exit devices and locksets commonly carry published terms of three to five years, and the general floor is set so that the shortest published term on the project is still a term the Owner accepted; a floor set above the published terms narrows the bidders to the manufacturers who publish it. {note}
−## The Owner shall be furnished with spare keys and maintenance items so the facility can be operated and serviced after handover.
+## Where a manufacturer publishes a longer warranty for a product category than the period indicated, that longer warranty shall apply in addition to the period indicated and shall not be waived by it.
−## The Contractor shall furnish spare keys in the quantity established by the keying schedule, delivered directly to the Owner.
+## A warranted repair or replacement shall carry a fresh warranty of the original period running from the date of the repair, or the unexpired remainder of the original period, whichever ends later.
−## The Contractor shall furnish a maintenance kit of closer adjustment tools, spring cartridges, and seal stock as recommended by the manufacturer.
+## The Contractor shall bear the cost of removing and reinstalling adjacent work that must be disturbed to make a warranty repair, and the cost of repairing collateral damage caused by the repair.
+## The Contractor shall warrant the installation, including the operation of every hardware item and the compliance of every fire door assembly with the clearance and closing requirements of NFPA 80, for the period established in the general conditions of the Contract, and shall correct deficiencies attributable to installation workmanship at no cost to the Owner.
+
+## The hardware supplier shall furnish at closeout a consolidated summary listing, for every product on the project, the warranty period and the service contact.
+
+# Spare Parts and Maintenance Materials {toc}
+
+## The Contractor shall deliver the spare parts and maintenance materials indicated in the datasheet to the Owner before final acceptance.
+
```datasheet
−label: Spare hardware furnished
+label: Spare Parts and Maintenance Materials
type: checkbox
options:
− - Spare keys per keying schedule
− - Closer adjustment tools
− - Spare seal / gasket stock
− - Spare interchangeable cores
+ - "Spare key blanks for each keyway"
+ - "Spare cylinders and cores of each format"
+ - "Door closer adjustment tools"
+ - "Exit device rebuild kits"
+ - "Spare gasketing and door bottom stock"
+ - "Spare hinges of each type furnished"
+ - "Spare protection plates of each size furnished"
+ - "Touch-up finish materials for painted hardware"
default:
− - Spare keys per keying schedule
− - Closer adjustment tools
+ - "Spare key blanks for each keyway"
+ - "Door closer adjustment tools"
```
+
+## Spare parts shall be of the same manufacturer, model, and finish as the items installed, delivered in labeled packaging identifying the hardware sets they serve.
+
+## Spare cylinders and cores delivered to the Owner shall be keyed to the accepted keying schedule as the Owner directs, and their key symbols shall be entered in the key record.
+
+## The Contractor shall obtain a signed receipt from the Owner for the spare parts delivered, and shall include the receipt in the closeout submittals.