HVAC Pumps

Read revision 9

Revision 9 · Oct 12, 2026 +49 −15

Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 8 to Rev 9 in HVAC Pumps.
---
title: HVAC Pumps
…117 unchanged lines
- "Materials of construction"
- "Coordination drawings with removal clearances"
+constraint: all_of
```
…37 unchanged lines
- "Warranty documentation by serial number"
- "Spare parts inventory by pump tag and part number"
+constraint: all_of
```
…9 unchanged lines
```datasheet
−label: Minimum Manufacturer Experience
+label: Manufacturer Experience
type: range
unit: years
…3 unchanged lines
setpoints: [0, 3, 5, 10, 15, 20, 25]
default: 10
+constraint: min
```
…3 unchanged lines
```datasheet
−label: Minimum Replacement Parts Availability Period
+label: Replacement Parts Availability Period
type: range
unit: years
…3 unchanged lines
setpoints: [5, 10, 15, 20, 25, 30]
default: 15
+constraint: min
```
…27 unchanged lines
setpoints: [0, 5, 10, 25, 50, 75, 100, 200]
default: 50
+constraint: exact
```
…36 unchanged lines
setpoints: [0, 10, 20, 25, 30, 35, 40, 50, 60]
default: deferred
+constraint: exact
```
…29 unchanged lines
```datasheet
−label: Maximum Continuous Fluid Temperature
+label: Highest Continuous Fluid Temperature
type: range
unit: °F
…4 unchanged lines
setpoints: [32, 40, 60, 100, 140, 180, 200, 220, 250, 300]
default: deferred
+constraint: min
```
```datasheet
−label: Minimum Continuous Fluid Temperature
+label: Lowest Continuous Fluid Temperature
type: range
unit: °F
…4 unchanged lines
setpoints: [10, 20, 32, 36, 40, 45, 55, 65, 100, 180]
default: deferred
+constraint: max
```
…10 unchanged lines
setpoints: [75, 125, 175, 250, 300, 400]
default: deferred
+constraint: min
```
…18 unchanged lines
setpoints: [0, 1000, 2000, 3300, 5000, 6600, 8000, 10000, 12000]
default: deferred
+constraint: exact
```
…20 unchanged lines
setpoints: [10, 25, 50, 75, 100, 150, 200, 300, 400, 500, 750, 1000, 1500, 2000, 3000, 4000, 6000, 8000, 12000]
default: deferred
+constraint: exact
```
…8 unchanged lines
setpoints: [10, 20, 30, 40, 50, 60, 75, 90, 100, 125, 150, 200, 250, 300, 400, 500, 600]
default: deferred
+constraint: exact
```
…26 unchanged lines
```datasheet
−label: Maximum Selected Impeller Diameter, Percent of Maximum Catalog Diameter
+label: Selected Impeller Diameter, Percent of Maximum Catalog Diameter
type: range
unit: '%'
…3 unchanged lines
setpoints: [70, 75, 80, 85, 90, 95, 100]
default: 95
+constraint: max
```
…13 unchanged lines
```datasheet
−label: Minimum NPSH Margin Ratio, NPSHa Divided by NPSHr
+label: NPSH Margin Ratio, NPSHa Divided by NPSHr
type: range
options:
min: 1.0
max: 2.5
setpoints: [1.0, 1.1, 1.2, 1.3, 1.5, 1.75, 2.0, 2.5]
+constraint: min
```
### The NPSH available shall exceed the NPSH required by at least the absolute margin indicated in the datasheet, applied in addition to the margin ratio.
```datasheet
−label: Minimum Absolute NPSH Margin
+label: Absolute NPSH Margin
type: range
unit: ft
…2 unchanged lines
max: 20
setpoints: [0, 2, 3, 5, 7, 10, 15, 20]
+constraint: min
```
…11 unchanged lines
```datasheet
−label: Maximum Rotative Speed at the Design Point
+label: Rotative Speed at the Design Point
type: range
unit: RPM
…2 unchanged lines
max: 3550
setpoints: [880, 1150, 1750, 3550]
+constraint: max
```
…31 unchanged lines
```datasheet
−label: Maximum Pump Energy Index
+label: Pump Energy Index
type: range
options:
…2 unchanged lines
setpoints: [0.5, 0.6, 0.7, 0.8, 0.9, 0.95, 1.0]
default: 1.0
+constraint: max
```
…13 unchanged lines
```datasheet
−label: Minimum Pump Hydraulic Efficiency at the Design Point
+label: Pump Hydraulic Efficiency at the Design Point
type: range
unit: '%'
…2 unchanged lines
max: 90
setpoints: [40, 50, 55, 60, 65, 70, 75, 80, 85, 90]
+constraint: min
```
…118 unchanged lines
- "Suction gauge connection"
- "Discharge gauge connection"
+constraint: all_of
```
…148 unchanged lines
```datasheet
−label: Minimum Bearing Rating Life at the Design Point
+label: Bearing Rating Life at the Design Point
type: range
unit: hours
…2 unchanged lines
max: 100000
setpoints: [8760, 17500, 25000, 40000, 50000, 100000]
+constraint: min
```
…121 unchanged lines
setpoints: [0.25, 0.33, 0.5, 0.75, 1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 350, 400, 500, 600, 700]
default: deferred
+constraint: exact
```
…8 unchanged lines
setpoints: [115, 208, 230, 460, 480, 575, 2300, 4160]
default: deferred
+constraint: exact
```
…109 unchanged lines
setpoints: [1.0, 1.15, 1.25]
default: 1.15
+constraint: min
```
…93 unchanged lines
```datasheet
−label: Minimum Isolator Static Deflection
+label: Isolator Static Deflection
type: range
unit: in.
…2 unchanged lines
max: 3.5
setpoints: [0.15, 0.25, 0.5, 0.75, 1.0, 1.5, 2.5, 3.5]
+constraint: min
```
…100 unchanged lines
- "Fault or trip alarm"
- "Lead and lag designation and rotation"
+constraint: all_of
```
…28 unchanged lines
- "Mechanical run test report"
- "Certified performance curve from production testing"
+constraint: all_of
```
…103 unchanged lines
```datasheet
−label: Maximum Coupling Misalignment After Thermal Stabilization
+label: Coupling Misalignment After Thermal Stabilization
type: range
unit: mils
…2 unchanged lines
max: 10
setpoints: [1, 2, 3, 4, 5, 7, 10]
+constraint: max
```
…51 unchanged lines
```datasheet
−label: Minimum Straight Suction Pipe Run
+label: Straight Suction Pipe Run
type: range
unit: pipe diameters
…3 unchanged lines
setpoints: [3, 5, 8, 10, 15, 20]
default: 5
+constraint: min
```
…41 unchanged lines
```datasheet
−label: Minimum Submergence Above the Suction Bell
+label: Submergence Above the Suction Bell
type: range
unit: in.
…2 unchanged lines
max: 72
setpoints: [6, 12, 18, 24, 36, 48, 60, 72]
+constraint: min
```
…77 unchanged lines
setpoints: [1, 2, 3, 5]
default: 1
+constraint: min
```
…21 unchanged lines
max: 5
setpoints: [1, 2, 3, 5]
+constraint: min
```
…13 unchanged lines
- "Replacement parts"
- "On-site labor for repair or replacement"
+constraint: all_of
```
…44 unchanged lines
- "One coupling element for each coupling installed"
- "One set of casing and seal gaskets for each pump model installed"
+constraint: all_of
```
…24 unchanged lines
- "Bearing lubrication chart naming grease type, quantity, and interval"
- "Spare parts ordering guide with manufacturer part numbers"
+constraint: all_of
```
### The certified curve for each pump tag, marked with the as-installed impeller diameter and the measured startup operating point, shall be placed in the operation and maintenance manual.
### The curve with the startup point marked on it is the single most useful page in the manual, because every future troubleshooting question about the pump is answered by comparing a new measurement against that mark. {note}

View current revision