HVAC Variable Frequency Drives

Read revision 6

Revision 6 · Oct 12, 2026 +24 −4

Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 5 to Rev 6 in HVAC Variable Frequency Drives.
---
title: HVAC Variable Frequency Drives
…93 unchanged lines
- "Motor compatibility verification"
- "Accessory product data for reactors, filters, and heaters"
+constraint: all_of
```
…37 unchanged lines
- "Warranty documentation by tag and serial number"
- "Spare parts inventory with part numbers"
+constraint: all_of
```
…43 unchanged lines
```datasheet
−label: Maximum Ambient Operating Temperature
+label: Highest Ambient Operating Temperature
type: range
unit: °C
…3 unchanged lines
setpoints: [40, 45, 50, 55]
default: 40
+constraint: min
```
…9 unchanged lines
```datasheet
−label: Maximum Installation Altitude
+label: Installation Altitude
type: range
unit: ft
…4 unchanged lines
setpoints: [0, 3300, 5000, 6600, 8000, 10000, 13000]
default: deferred
+constraint: min
```
…61 unchanged lines
setpoints: [208, 230, 240, 460, 480, 575, 600]
default: deferred
+constraint: exact
```
…13 unchanged lines
```datasheet
−label: Minimum Input Voltage Tolerance
+label: Input Voltage Tolerance
type: range
unit: '%'
…3 unchanged lines
setpoints: [10, 15]
default: 10
+constraint: min
```
…18 unchanged lines
setpoints: [1, 1.5, 2, 3, 5, 7.5, 10, 15, 20, 25, 30, 40, 50, 60, 75, 100, 125, 150, 200, 250, 300, 350, 400, 450, 500]
default: deferred
+constraint: exact
```
…56 unchanged lines
```datasheet
−label: Minimum Short Circuit Current Rating
+label: Short Circuit Current Rating
type: range
unit: kAIC
…4 unchanged lines
setpoints: [5, 10, 14, 18, 22, 30, 35, 42, 65, 100]
default: deferred
+constraint: min
```
…137 unchanged lines
setpoints: [5, 8, 12, 15, 20]
default: 8
+constraint: max
```
…185 unchanged lines
setpoints: [0, 10, 15, 20, 25, 30, 40, 50]
default: 20
+constraint: exact
```
…9 unchanged lines
setpoints: [100, 105, 110, 115, 120]
default: 100
+constraint: exact
```
…42 unchanged lines
max: 300
setpoints: [5, 10, 15, 20, 30, 45, 60, 90, 120, 180, 240, 300]
+constraint: exact
```
…8 unchanged lines
max: 300
setpoints: [5, 10, 15, 20, 30, 45, 60, 90, 120, 180, 240, 300]
+constraint: exact
```
…132 unchanged lines
- "Safe torque off input"
- "External fault input from a fire alarm or smoke detection interface"
+constraint: all_of
```
…81 unchanged lines
- "Cooling fan runtime and service alert"
- "Drive operating mode"
+constraint: all_of
```
…90 unchanged lines
setpoints: [25, 50, 75, 100, 150, 200, 300, 500, 750, 1000]
default: deferred
+constraint: exact
```
…58 unchanged lines
setpoints: [2, 2.5, 4, 5, 8, 10, 12, 16]
default: 4
+constraint: exact
```
…288 unchanged lines
setpoints: [1, 2, 3, 5]
default: 2
+constraint: min
```
…19 unchanged lines
default:
- "Parts and labor including on-site repair"
+constraint: all_of
```
…52 unchanged lines
- "One set of cooling fans for each frame size installed"
- "One set of control power fuses for each drive model installed"
+constraint: all_of
```
### The manufacturer shall furnish fan replacement instructions and the expected fan service life at the ambient temperature indicated in the datasheet.
### Cooling fans are the shortest-lived component in the drive and the most common cause of an overtemperature shutdown after a fouled intake. Both failures are correctable the same day when the replacement is already on site. {note}