Panelboards
Remake batch 25 and its neighbor re-points, batch 24 where missing, and the adopted-electrical-code parameter: brought in line with the authoring repository
Showing changes from Rev 5
to Rev 6
in Panelboards.
---
title: Panelboards
…25 unchanged lines
- the surge protective device as a product, its ratings, its protection modes, and its lead length, under [[sync/surge-protective-devices]]
- the meters, their accuracy class, their current transformers, and the monitoring system they report to, under [[sync/electrical-power-monitoring]]
−- the transformer feeding a panelboard and the grounding of its secondary, under [[sync/low-voltage-dry-type-transformers]]
+- the transformer feeding a panelboard, under [[sync/low-voltage-dry-type-transformers]], and the grounding of its secondary, under [[sync/grounding-and-bonding]]
- the receptacles, switches, and outlet devices on the branch circuits, under [[sync/wiring-devices]]
- the remotely operated breakers, relays, and controllers of a lighting-control panelboard, under [[sync/lighting-controls]]
…935 unchanged lines
# Identification {toc}
−## Nameplates, circuit directories, arc-flash labels, and field markings shall comply with [[sync/electrical-identification]] for material, lettering, attachment, and directory format.
+## Nameplates, circuit directories, arc-flash labels, and field markings shall comply with [[sync/equipment-labeling]] for material, lettering, attachment, and directory format.
## Each panelboard shall carry a nameplate stating the panelboard designation, the system voltage with the number of phases and wires, the main bus rating, the main device rating where one is furnished, the assembly short-circuit current rating, and the source that feeds it, in the text listed on the nameplate schedule.
…246 unchanged lines
## Spare devices shall be stored in a labeled container in the electrical room, and shall not be stored inside an operating panelboard.