Pressure Instrumentation
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 4
to Rev 5
in Pressure Instrumentation.
---
title: Pressure Instrumentation
…94 unchanged lines
- "Transmitter configuration sheets"
- "Mounting details"
+constraint: all_of
```
…22 unchanged lines
- "Factory calibration certificates"
- "Manufacturer's installation instructions"
+constraint: all_of
```
…17 unchanged lines
- "Operation and maintenance data with recalibration intervals"
- "Warranty documentation"
+constraint: all_of
```
…290 unchanged lines
```datasheet
−label: Maximum Reference Accuracy for Points Not Otherwise Designated
+label: Reference Accuracy for Points Not Otherwise Designated
type: range
unit: '% of calibrated span'
min: 0.025
max: 0.5
setpoints: [0.025, 0.04, 0.05, 0.065, 0.075, 0.1, 0.15, 0.2, 0.25, 0.5]
+constraint: max
```
…3 unchanged lines
```datasheet
−label: Minimum Rangeability, Upper Range Limit to Minimum Span
+label: Rangeability, Upper Range Limit to Minimum Span
type: range
unit: to 1
min: 5
max: 200
setpoints: [5, 10, 15, 20, 30, 50, 100, 150, 200]
+constraint: min
```
…166 unchanged lines
setpoints: [1.5, 2, 2.5, 3.5, 4, 4.5, 6, 8.5, 12]
default: 4.5
+constraint: exact
```
…228 unchanged lines
```datasheet
−label: Maximum Recalibration Interval
+label: Recalibration Interval
type: range
unit: months
…2 unchanged lines
setpoints: [6, 12, 24, 36, 60]
default: 12
+constraint: max
```
…93 unchanged lines
setpoints: [1, 2, 3, 5]
default: 1
+constraint: min
```
…19 unchanged lines
- "Transmitters of each model and sensor range installed"
- "Gauges of each range, grade, and connection installed"
+constraint: all_of
```
…8 unchanged lines
setpoints: [1, 2, 3, 5]
default: 1
+constraint: exact
```
## Spare parts shall match the installed devices in model, range, wetted material, output signal, and firmware, and shall be turned over against a written inventory signed by the Owner's representative.