Site Utilities

Read revision 9

Revision 9 · Oct 19, 2026 +2 −2

Remake batch 25 and its neighbor re-points, batch 24 where missing, and the adopted-electrical-code parameter: brought in line with the authoring repository
Showing changes from Rev 8 to Rev 9 in Site Utilities.
---
title: Site Utilities
…27 unchanged lines
### Interior plumbing within 5 feet of the building is governed by [[sync/domestic-water-piping]] and [[sync/sanitary-waste-and-vent-piping]].
−### For the dry utilities, this standard covers the raceway pathway — the duct bank, conduit, spacers, encasement, and pull/splice structures — but not the conductors, cable, terminations, or grounding pulled through it, which are covered by the electrical standards.
+### For the dry utilities, this standard covers the raceway pathway — the duct bank, conduit, spacers, and encasement — but not the pull/splice structures, which are covered by [[sync/utility-manholes-and-handholes]], and not the conductors, cable, terminations, or grounding pulled through it, which are covered by the electrical standards.
## Design Information on the Drawings {toc}
…66 unchanged lines
- Product data for all gravity sanitary sewer pipe and fittings, indicating the standard (ASTM D3034 SDR 35, ASTM F679, or ASTM C76), the SDR or class, the joint type, and the gasket standard (ASTM D3212 / F477 or ASTM C443)
- Product data for valves (gate, butterfly, tapping), valve boxes, fire hydrants (AWWA C502), service saddles and corporation/curb stops (AWWA C800), air-release/vacuum valves on force mains, and restrained-joint and mechanical-joint fittings, with pressure ratings
−- Product data for dry-utility conduit and duct (NEMA TC-2 PVC conduit, NEMA TC-6 & 8 PVC duct, or HDPE duct), conduit spacers, end bells, and pull/splice structures (precast handholes, manholes, and pull boxes) with load rating
+- Product data for dry-utility conduit and duct (NEMA TC-2 PVC conduit, NEMA TC-6 & 8 PVC duct, or HDPE duct), conduit spacers, end bells, and pull/splice structures (precast handholes, manholes, and pull boxes, as specified in [[sync/utility-manholes-and-handholes]]) with load rating
- Shop drawings for sanitary manholes, drop connections, and any cast-in-place structures, including resilient pipe connectors per ASTM C923 and the manhole joint sealing method
- Shop drawings and a duct-bank section detail showing conduit count, configuration, spacer type and spacing, reinforcing (where specified), concrete encasement dimensions and cover, and minimum bend radius
…722 unchanged lines
## The installation shall satisfy the utility owner's acceptance and bonding requirements where the system is to be turned over to the public utility for ownership and maintenance.