Structured Cabling Systems

Read revision 4

Revision 4 · Oct 19, 2026 +1 −1

Remake batch 25 and its neighbor re-points, batch 24 where missing, and the adopted-electrical-code parameter: brought in line with the authoring repository
Showing changes from Rev 3 to Rev 4 in Structured Cabling Systems.
---
title: Structured Cabling Systems
…44 unchanged lines
## The field certification of the cabling plant is performed under this standard; the electrical acceptance test program under [[sync/electrical-acceptance-testing]] does not include it, and where the project is commissioned, the certification reports are delivered to the commissioning authority as inputs under [[sync/commissioning]]. {note}
−## The installation shall comply with the edition of NFPA 70 adopted with [[parameter: adopted-building-code]], including Articles 725, 770, 800, and 805, and with the amendments of the Authority Having Jurisdiction.
+## The installation shall comply with [[parameter: adopted-electrical-code]], including NFPA 70 Articles 725, 770, 800, and 805, and with the amendments of the Authority Having Jurisdiction.
## The location of every work-area outlet, the box or housing that serves it, and the identifier assigned to it shall be as indicated on [[drawing: the telecommunications plans]].
…862 unchanged lines
## Spare parts shall be identical to the installed items in manufacturer, category, shielding, connector style, and color, shall be delivered in their original packaging, and shall be labeled with the item type and the telecommunications room they are stocked for.

View current revision