Utility Manholes and Handholes

Read revision 5

Revision 5 · Oct 17, 2026 +2 −2

Cross-references point to the standards that now own the topic after the October electrical rewrites: MV cable to medium-voltage-cables, energy storage to battery-energy-storage-systems, service grounding to grounding-and-bonding, lightning to lightning-protection.
Showing changes from Rev 4 to Rev 5 in Utility Manholes and Handholes.
---
title: Utility Manholes and Handholes
…2 unchanged lines
description: >
When to use: Selecting and specifying below-grade access structures for underground electrical and low-voltage systems — precast concrete manholes (personnel-entry), precast concrete handholes/vaults, and polymer-concrete or composite handholes serving medium-voltage feeders, low-voltage distribution, lighting circuits, and communications/data ductbanks. Covers ductbank pull points, cable splice and termination locations, inspection access, cover and frame assemblies, load/tier ratings, cover markings, sumps and drainage, grounding/bonding attachments, pulling irons, and cable rack inserts.
− Not intended for: Underground conduit/ductbank routing, trench design, and concrete encasement (see [[sync/underground-ductbank]]); conduit and raceway material, fittings, and methods (see [[sync/raceways-and-conduit]]); conductors, cables, splices, and cable tray (see [[sync/conductors-and-cables]]); broader storm/sanitary/water/gas main coordination (see [[sync/site-utilities]]); above-grade pull, junction, and outlet boxes; AASHTO bridge-loaded roadway manholes; and wet-well or sump-pump drainage structures.
+ Not intended for: Underground conduit/ductbank routing, trench design, and concrete encasement (see [[sync/underground-ductbank]]); conduit and raceway material, fittings, and methods (see [[sync/raceways-and-conduit]]); shielded conductors above 1000 V and their joints (see [[sync/medium-voltage-cables]]), low-voltage conductors and cables (see [[sync/conductors-and-cables]]), and cable tray (see [[sync/cable-tray]]); broader storm/sanitary/water/gas main coordination (see [[sync/site-utilities]]); above-grade pull, junction, and outlet boxes; AASHTO bridge-loaded roadway manholes; and wet-well or sump-pump drainage structures.
---
…14 unchanged lines
- Underground conduit and ductbank routing, trench design, and concrete encasement — see [[sync/underground-ductbank]].
- Conduit and raceway material selection, fittings, and installation methods — see [[sync/raceways-and-conduit]].
−- Conductors, cables, splicing methods and materials, and cable tray — see [[sync/conductors-and-cables]].
+- Medium-voltage cable and its splices — see [[sync/medium-voltage-cables]]; low-voltage conductors and cables — see [[sync/conductors-and-cables]]; cable tray — see [[sync/cable-tray]].
- Broader site utility coordination for storm, sanitary, water, and gas mains — see [[sync/site-utilities]].
- Above-grade pull boxes, junction boxes, and outlet boxes mounted on walls or in ceilings, which are governed by NEC Article 314 but are not the subject of this standard.
…703 unchanged lines
default: 2
```