Variable Air Volume Terminal Units
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 3
to Rev 4
in Variable Air Volume Terminal Units.
---
title: Variable Air Volume Terminal Units
…81 unchanged lines
- Simultaneous heating and cooling compliance calculation
- Published airflow control tolerance and minimum controllable airflow
+constraint: all_of
```
…23 unchanged lines
- Network point list
- Trend log configuration
+constraint: all_of
```
…20 unchanged lines
- Fourteen-day occupied trend logs
- Reloadable controller parameter file
+constraint: all_of
```
…16 unchanged lines
setpoints: [2, 3, 5, 10, 15, 20]
default: 10
+constraint: max
```
…126 unchanged lines
setpoints: [20, 30, 40, 50, 60, 70, 80, 90, 100]
default: derived
+constraint: max
```
…181 unchanged lines
setpoints: [0.1, 0.15, 0.2, 0.25, 0.3, 0.35, 0.4, 0.5, 0.75, 1]
default: derived
+constraint: max
```
…96 unchanged lines
### Deficiencies identified in the trend review shall be corrected by the party assigned controller programming responsibility under [[sync/air-terminal-units]].