Wet-Pipe Fire Sprinkler Systems
Datasheet constraints: every range, checkbox and listbox field now states its direction
Showing changes from Rev 7
to Rev 8
in Wet-Pipe Fire Sprinkler Systems.
---
title: Wet-Pipe Fire Sprinkler Systems
…105 unchanged lines
- "Sprinkler product data"
- "Riser, control assembly, and device product data"
+constraint: all_of
```
…20 unchanged lines
- "Water supply flow test report"
- "Designer qualification"
+constraint: all_of
```
…26 unchanged lines
- "Warranty documentation"
- "Spare parts receipt"
+constraint: all_of
```
…172 unchanged lines
setpoints: [0.05, 0.10, 0.15, 0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50, 0.60]
default: derived
+constraint: min
```
…10 unchanged lines
setpoints: [500, 750, 900, 1000, 1200, 1500, 2000, 2500, 3000, 4000, 5000]
default: derived
+constraint: min
```
…9 unchanged lines
- "Increase for a ceiling sloped more than 2 in 12"
- "Increase for a dry-pipe or double-interlock pre-action system"
+constraint: all_of
```
…18 unchanged lines
setpoints: [0, 50, 100, 250, 500, 750, 1000]
default: derived
+constraint: min
```
…12 unchanged lines
max: 120
setpoints: [30, 45, 60, 90, 120]
+constraint: min
```
…25 unchanged lines
```datasheet
−label: Maximum Age of the Water Supply Flow Test at Submittal
+label: Age of the Water Supply Flow Test at Submittal
type: range
unit: months
…3 unchanged lines
setpoints: [6, 12, 24, 36]
default: 12
+constraint: max
```
…8 unchanged lines
max: 20
setpoints: [0, 5, 10, 15, 20]
+constraint: min
```
…128 unchanged lines
- "Standard spray upright"
- "Standard spray sidewall"
+constraint: any_of
```
…82 unchanged lines
```datasheet
−label: Minimum Nominal K-Factor of Standard Spray Sprinklers
+label: Nominal K-Factor of Standard Spray Sprinklers
type: range
unit: gpm/psi^0.5
…3 unchanged lines
setpoints: [2.8, 4.2, 5.6, 8.0, 11.2, 14.0]
default: 5.6
+constraint: min
```
…161 unchanged lines
- "Combined test-and-drain assembly with sight glass"
- "Pressure gauge on the system side"
+constraint: all_of
```
…130 unchanged lines
setpoints: [200, 225, 250, 275, 300, 325, 350, 375, 400]
default: derived
+constraint: min
```
…54 unchanged lines
default:
- "Authority Having Jurisdiction"
+constraint: all_of
```
…47 unchanged lines
setpoints: [1, 2, 3, 5]
default: 1
+constraint: min
```
…12 unchanged lines
max: 48
setpoints: [2, 4, 8, 24, 48]
+constraint: max
```
…18 unchanged lines
setpoints: [6, 12, 24]
default: derived
+constraint: min
```
…10 unchanged lines
- "Spare gaskets and trim parts for the alarm check valve"
- "Spare sight glass for each test-and-drain assembly type"
+constraint: all_of
```
## Spare parts shall be the same make and model as the installed items and shall be delivered in their original unopened packaging.
## An understocked or missing spare cabinet is a deficiency written at the acceptance inspection and at every annual inspection after it, and a sprinkler that opens with no matching spare on hand leaves that area unprotected until one is procured. {note}