Cast Stone

Rev 1 · Updated Jun 14, 2026 · View history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

NOTE This Standard governs the manufacture, finishing, anchorage, and installation of architectural cast stone units used as decorative and functional masonry trim. (1.1)
NOTE Cast stone is a manufactured concrete masonry product engineered to simulate the appearance of natural quarried stone (limestone, sandstone, or granite) at lower cost and with greater dimensional repeatability. It is produced as discrete trim units rather than as a continuous wall material, and is set as masonry within or upon a backup wall built under a separate Standard. Typical units include window sills and subsills, parapet copings, lintels, banding and string courses, water tables, quoins, keystones, door and window surrounds, base courses, and column caps and bases. (1.2)
1.3Units shall comply with ASTM C1364 for architectural cast stone, including its compressive strength, absorption, freeze-thaw, and drying-shrinkage requirements.
1.4Units shall be produced by either the wet-cast or the vibratory dry-tamp (VDT) method as required by this Standard for the unit type.
1.5This Standard applies to new construction and to renovation where new cast stone trim is installed.
NOTE The backup masonry wall into which cast stone units are set is excluded; it is governed by Unit Masonry for concrete masonry backup and Brick Masonry for clay-unit backup. (1.6)
NOTE Cast stone trim depends on a coordinated backup wall for seat heights, coursing alignment, and structural support, but the backup construction itself — its units, grouting, and reinforcement — is specified elsewhere. This Standard specifies only the interface dimensions and bearing the backup must provide. (1.7)
NOTE General masonry veneer anchors and ties are excluded; they are governed by Masonry Anchorage And Veneer. Anchors, dowels, and straps are specified here only as they secure cast stone units. (1.8)
NOTE Through-wall flashing, drip edges in the flashing plane, and weep systems behind copings, sills, and shelf angles are excluded; they are governed by Through Wall Flashing. (1.9)
NOTE Large-format architectural precast cladding panels and PCI-governed structural precast members are excluded; they are governed by Architectural Precast Concrete. (1.10)
NOTE The boundary between cast stone and architectural precast is unit scale and governing standard, not appearance: both can imitate stone. Cast stone is small-unit trim produced under ASTM C1364 and Cast Stone Institute practice; architectural precast is large-format panel cladding produced under PCI MNL-117 and ACI 533. Mixing requirements from the two standards into one section is a common source of conflicting requirements and field RFIs, so the two are specified separately. (1.11)
NOTE Glass fiber reinforced concrete (GFRC) panel systems, natural quarried stone veneer, and repair of deteriorated existing cast stone are excluded; cast stone repair is governed by Concrete Repair And Restoration. (1.12)

2 Referenced Standards

2.1Units, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard Title
ASTM C1364 Architectural Cast Stone
ASTM C1194 Compressive Strength of Architectural Cast Stone
ASTM C1195 Absorption of Architectural Cast Stone
ASTM C150/C150M Portland Cement
ASTM C595/C595M Blended Hydraulic Cements
ASTM C33/C33M Concrete Aggregates
ASTM C270 Mortar for Unit Masonry
ASTM C67/C67M Sampling and Testing Brick and Structural Clay Tile (freeze-thaw cycling)
ASTM A615/A615M Deformed and Plain Steel Bars for Concrete Reinforcement
ASTM A1064/A1064M Carbon-Steel Wire and Welded Wire Reinforcement for Concrete
ASTM A153/A153M Zinc Coating (Hot-Dip) on Iron and Steel Hardware
ASTM A276/A276M Stainless Steel Bars and Shapes
IBC Section 2103 International Building Code — Masonry Construction Materials
TMS 602 (ACI 530.1) Specification for Masonry Structures
CSI TB-37 Cast Stone Institute Technical Bulletin — Job Site Handling and Installation
CSI TB-42 Cast Stone Institute Technical Bulletin — Mortars for Cast Stone Installation
NOTE "CSI" in this Standard refers to the Cast Stone Institute, the trade body that publishes cast stone production and installation guidance, and not to any specification-format organization. (2.3)

3 Submittals

3.1 Action Submittals

3.1.1The Contractor shall submit the following action submittals for review and approval before fabrication:
  • Product data for each cast stone unit type, including mix design summary, casting method (wet-cast or VDT), and finish.
  • Shop drawings showing each unit's dimensions, profiles, joint locations, anchor and dowel locations, reinforcement, and unit weights, keyed to the elevations.
  • Color-and-texture samples of each unit finish for the Architect's approval and retention as the project color standard.
  • Manufacturer's mix design with cement type, aggregate source, pigment type and dosage, and air content.
  • Anchor, dowel, and tie schedule identifying material, grade, size, and finish for each condition.
Action submittals requiredcheckbox
Product data (unit types, casting method, finish)
Shop drawings (dimensions, joints, anchors, reinforcement, weights)
Color-and-texture samples
Mix design summary
Anchor, dowel, and tie schedule
3.1.2Shop drawings shall locate every coordinable item against the contract drawings; unit setting locations and coursing references are indicated cast stone elevations.
NOTE Color-and-texture samples shall be retained by the Architect as the contractual standard against which delivered units are judged. (3.1.3)
NOTE Cast stone color and texture vary measurably between batches and between plants because they depend on pigment dosage, aggregate source, and finishing technique. Without an approved physical sample, the Owner has no enforceable color standard and disputes over delivered color cannot be resolved on a contractual basis. (3.1.4)

3.2 Informational Submittals

3.2.1The Contractor shall submit the following informational submittals:
  • Test reports from an independent laboratory showing compliance with ASTM C1364 for compressive strength, absorption, and freeze-thaw durability.
  • Manufacturer's certification that the producing plant operates a documented quality-control program, and evidence of Cast Stone Institute plant certification where required.
  • Manufacturer's job-site handling and installation instructions, including maximum unit weights and lifting points.
Informational submittals requiredcheckbox
Independent test reports (C1364 strength, absorption, freeze-thaw)
Plant quality-control certification
Cast Stone Institute plant certification
Handling and installation instructions
NOTE Independent third-party test reports shall be submitted; manufacturer self-certification to ASTM C1364 alone shall not be accepted as proof of compliance. (3.2.2)
NOTE ASTM C1364 sets the performance limits but contains no mandatory third-party compliance mechanism. A specification that names the standard without also requiring independent test reports or plant certification leaves the door open to substandard product, because the producer is the only party attesting to compliance. Requiring independent reports closes that gap. (3.2.3)

3.3 Closeout Submittals

3.3.1The Contractor shall submit the following closeout submittals:
  • Cleaning and maintenance instructions for installed cast stone, including approved and prohibited cleaning agents.
  • Records of the approved color-and-texture sample and the mix design as built.
Closeout submittals requiredcheckbox
Cleaning and maintenance instructions
As-built color sample and mix design records

4 Quality Assurance

4.1The manufacturer shall be an established cast stone producer with a documented quality-control program covering mix proportioning, casting, curing, finishing, and dimensional inspection.
4.2A Cast Stone Institute certified plant should be specified where third-party verification of production practice is required by the Owner.
4.3A field sample panel of representative units, set with the specified mortar and joint treatment, should be erected and approved before bulk installation proceeds.
4.4The approved color-and-texture sample shall govern acceptance; units differing visibly in color, texture, or finish from the approved sample shall be rejected.
NOTE Plant certification and independent testing are the two complementary quality controls for cast stone, and a robust specification uses both. (4.5)
NOTE Plant certification attests to the production process — that the plant has the equipment, procedures, and quality records to make compliant units consistently. Independent testing attests to the product — that representative units actually meet the strength, absorption, and freeze-thaw limits. Each addresses a failure mode the other does not, so both are specified rather than treating one as a substitute for the other. (4.6)
Plant certification requirementradio
Cast Stone Institute certified plant required
Documented quality-control program required, certification not mandatory

5 Environmental and Service Conditions

5.1Units exposed to freeze-thaw cycling, de-icing salts, or marine environments shall be specified with air entrainment, absorption limits, and anchor materials appropriate to that exposure.
NOTE Exposure conditions drive several mix and hardware decisions at once, and selecting the wrong exposure class is a durability error that surfaces only after years in service. (5.2)
NOTE A unit specified for a benign interior or sheltered exposure may use grey cement, standard absorption limits, and galvanized anchors. The same unit on a parapet coping in a freeze-thaw climate, or near de-icing salt or salt spray, needs entrained air, a tighter absorption limit, and stainless anchors. Because the visible unit looks identical in both cases, the exposure class must be stated explicitly so the producer proportions the mix and selects hardware correctly. (5.3)
Exposure classradio
Interior or sheltered exterior (no freeze-thaw)
Exterior, freeze-thaw exposure
Severe exterior, freeze-thaw with de-icing salts
Marine or coastal (chloride exposure)
5.3.1Units in freeze-thaw exposure shall be air-entrained to 4 to 8 percent.
Air content (wet-cast, freeze-thaw exposed)range
%
48
Default: 6 %
5.3.2Units in freeze-thaw exposure shall exhibit not more than 5.0 percent mass loss after 300 freeze-thaw cycles.

6 Materials and Mix Design

6.1Cement shall be Portland cement complying with ASTM C150 (Type I or Type III) or blended hydraulic cement complying with ASTM C595, white or grey as required to achieve the approved color.
6.2Aggregates shall comply with ASTM C33 and shall be selected for color and gradation to match the approved sample.
6.3Pigments shall be inorganic mineral-oxide pigments and shall not exceed 10 percent of the cement weight.
NOTE Mineral-oxide pigments are specified because they are colorfast and integral to the unit, holding color through weathering and abrasion. (6.4)
NOTE Inorganic mineral-oxide pigments are dispersed throughout the mix and are stable under ultraviolet exposure, so color does not fade or wash off and a chipped face still shows the body color. Surface-applied coloring, by contrast, weathers off and exposes a different color beneath, and is not an acceptable means of meeting the approved-sample requirement. Capping pigment dosage prevents the strength and shrinkage penalties that high pigment loading causes. (6.5)

6.6 Casting Method

6.6.1Wet-cast units shall be produced where reinforcement cages, complex geometry, or fine profile detail are required.
6.6.2Vibratory dry-tamp (VDT) units may be produced for simpler unreinforced units where a uniform fine-grained texture is acceptable.
NOTE The casting method is not a free interchange, and specifying a reinforced unit without specifying wet-cast is a common error that forces a non-compliant substitution. (6.6.3)
NOTE The vibratory dry-tamp process compacts a near-zero-slump mix and cannot encase a reinforcing cage, so it is limited to unreinforced units. Wet-cast uses a flowable mix that surrounds reinforcement and fills intricate forms. When a lintel or long cantilever coping that must be reinforced is specified without naming the casting method, the producer either cannot comply or quietly substitutes an unreinforced VDT unit in a structural location. Reinforced units therefore must be specified as wet-cast. (6.6.4)
Casting methodradio
Wet-cast
Vibratory dry-tamp (VDT)
Wet-cast for reinforced units, VDT permitted for unreinforced trim

6.7 Unit Construction

6.7.1Homogeneous units shall have a uniform mix throughout the unit cross-section.
6.7.2Facing-and-backup units shall have a face mix of the approved color and texture bonded monolithically to a backup mix, cast wet against wet so the two layers cure as one unit.
NOTE Facing-and-backup construction lets the color aggregate be concentrated where it shows, which can lower cost on larger units without changing the visible result. (6.7.3)
NOTE In homogeneous units the entire cross-section uses the color mix, which is simple and is the usual choice for small trim. In facing-and-backup units the costly color and aggregate are placed only in the exposed face layer while a plain backup mix forms the body, cast at the same time so the layers bond monolithically. The two approaches produce the same visible face; the choice is an economic one that the unit size and quantity drive. (6.7.4)
Unit constructionradio
Homogeneous
Facing-and-backup (two-layer)
6.8Cement color selection
Cement colorradio
White Portland
Grey Portland
Blended (white or grey with supplementary cementitious material)
6.9Aggregate selection
Aggregate typeselect
Crushed limestone
Granite
Quartz
Natural gravel
NOTE Aggregate color shall match the approved color-and-texture sample, and the specified aggregate shall be confirmed as available from the selected manufacturer before it is made a requirement. (6.10)
NOTE Some aggregate colors are region-specific and are not stocked by every cast stone plant. Specifying an aggregate the chosen producer cannot readily source forces a long-lead special order or a re-sampling cycle. Confirming availability against the actual producer's stock before finalizing the requirement avoids that delay. (6.11)

7 Physical Performance

7.1Units shall attain a minimum compressive strength of 6,500 psi at 28 days when tested per ASTM C1194.
7.2Reinforced lintels and units in high-traffic or high-load locations should be specified at a higher compressive strength where the structural demand warrants it.
NOTE The 6,500 psi minimum is the ASTM C1364 baseline and is sufficient for the great majority of trim units; higher strength is reserved for genuine structural demand. (7.3)
NOTE The C1364 minimum already exceeds typical masonry trim service loads, so specifying it satisfies most units without over-specification. A higher class (8,000 to 10,000 psi) is appropriate for reinforced lintels carrying real spans, for stair treads, or for units in high-traffic locations, where the added strength is doing work. Routinely raising the strength on every unit adds cost and tightens the mix unnecessarily. (7.4)
Minimum compressive strength at 28 daysrange
psi
650010000
Default: 6500 psi
7.5Units shall exhibit cold-water absorption not exceeding 6 percent and boiling-water absorption not exceeding 10 percent when tested per ASTM C1195.
7.6A tighter cold-water absorption limit of 4 percent should be specified only for severe marine or de-icing-salt exposure.
NOTE Absorption is the single best field indicator of cast stone durability, because a denser, less absorptive unit resists freeze-thaw and salt damage. (7.7)
NOTE Water that a unit absorbs is water available to freeze, expand, and spall the face, and to carry chlorides into the body. The 6 percent cold-water limit is the standard durability threshold and is correct for ordinary freeze-thaw exposure. Dropping to 4 percent meaningfully improves resistance in the harshest marine and de-icing-salt service, but it is harder to achieve and should not be imposed where the milder exposure does not need it. (7.8)
Maximum cold-water absorptionrange
%
46
Default: 6 %
7.9Linear drying shrinkage shall not exceed 0.065 percent.

8 Reinforcement

8.1Reinforcing bars shall comply with ASTM A615 and welded wire reinforcement shall comply with ASTM A1064.
8.2Reinforcement shall be positioned with cover sufficient to protect against corrosion, and corrosion-resistant or galvanized reinforcement shall be used where cover is limited or exposure is severe.
8.3Unreinforced units shall be limited to spans not exceeding 4 feet; units spanning more than 4 feet shall be wet-cast and reinforced.
8.4Lintels, long sills, and cantilever copings shall be wet-cast and reinforced regardless of nominal span.
NOTE Span and cantilever, not unit length alone, decide whether a unit must be reinforced. (8.5)
NOTE A short unit set in continuous bearing carries little bending and can be unreinforced. A unit that spans an opening, projects as a cantilever, or runs long between supports develops tensile stress on its underside that plain cast stone cannot reliably carry, so it must be wet-cast around a reinforcing cage. The 4 foot unreinforced limit is the conventional dividing line, with lintels and cantilevers always reinforced because their geometry guarantees bending. (8.6)
Reinforcementradio
Unreinforced (trim units within span limit)
Fiber-reinforced
Bar or welded-wire reinforced (wet-cast)

9 Finish

9.1The unit finish shall match the approved color-and-texture sample.
NOTE Finish is selected to imitate the target natural stone, and each finish exposes the aggregate differently. (9.2)
NOTE An as-cast smooth finish reads as a fine, sealed stone face. Acid-etching lightly opens the surface for a honed limestone look. Sandblasting, in light, medium, or heavy degrees, removes progressively more cement paste to expose aggregate and deepen texture. Tooled finishes cut linear or bush-hammered patterns. The choice is governed by the natural stone being matched and must be represented in the approved sample so delivered units can be judged against it. (9.3)
Finishselect
As-cast smooth
Acid-etched
Sandblasted (light)
Sandblasted (medium)
Sandblasted (heavy)
Tooled

10 Unit Geometry and Drainage

10.1Sill and coping units exposed to weather shall be cast with a positive wash slope of not less than 15 degrees (approximately 1:4) to shed water.
10.2Sill, coping, and projecting units shall be cast with a continuous drip edge on the underside of the projection.
NOTE Positive wash and a drip edge are the two geometric defenses that keep water off the wall, and omitting either lets water enter at the joints. (10.3)
NOTE A flat-topped sill or coping ponds water, which then migrates through head joints into the wall below. A wash slope sheds that water to the face. A drip edge — a groove or kerf on the underside of the projection — breaks the surface tension that would otherwise carry runoff back along the soffit to the wall. Both features are cast into the unit and cost nothing to include, but are easily left off a profile and are then impossible to add in the field. (10.4)
Coping profileselect
Single-slope
Saddle (double-slope)
Flat-top with drip edges
Coping widthselect
8
10
12
14
16
10.5Minimum unit thickness for exterior copings and projecting sills shall be 3-1/2 inches; non-structural decorative panels shall be not less than 2 inches thick.
10.6Maximum unit weight for unassisted field handling shall be coordinated with the installer; units exceeding the agreed limit shall be set with crane or mechanical lift assistance.
NOTE Unit weight must be a stated requirement, not an afterthought, because it governs both safety and placement quality. (10.7)
NOTE A long coping or reinforced lintel can readily exceed what two workers can safely set by hand, commonly in the range of 150 to 300 pounds. If the specification is silent on weight, oversized units arrive without lifting provisions, leading to dropped units, injuries, and pieces forced into place out of alignment. Stating a maximum unit weight for hand setting, and requiring mechanical lift above it, makes the handling method an explicit part of the design. (10.8)
Maximum unit weight for unassisted hand settingrange
lb
150300
Default: 200 lb

11 Anchorage

11.1Anchors, dowels, ties, and straps shall be Type 304 stainless steel as the default, hot-dip galvanized per ASTM A153 where permitted by exposure, or Type 316 stainless steel for marine and coastal exposure.
11.2Galvanized anchors shall not be used in marine, coastal, or de-icing-salt exposure.
NOTE Anchor material is a long-life durability decision, and using galvanized hardware in a salt environment causes staining and spalling within the building's service life. (11.3)
NOTE Hot-dip galvanizing protects embedded steel adequately in ordinary exposure, but in marine air or where de-icing salts are present the zinc coating is consumed and the steel corrodes, expanding and cracking the surrounding cast stone and bleeding rust stains down the face within roughly 10 to 15 years. Stainless steel, Type 304 generally and Type 316 in chloride-laden environments, avoids this and is the default precisely because anchor replacement after installation is effectively impossible. (11.4)
Anchor and dowel materialradio
Type 304 stainless steel
Hot-dip galvanized (ASTM A153)
Type 316 stainless steel (marine/coastal)
11.5Copings and projecting units shall be secured with stainless steel dowels of 3/8 inch or 1/2 inch diameter set into the supporting masonry.
Dowel diameterradio
3/8
1/2
11.6Anchor and dowel locations, types, and embedment shall be shown on the shop drawings for each unit condition.

12 Mortar, Setting, and Joints

12.1Setting mortar shall comply with ASTM C270, Type N for above-grade setting beds and joints.
12.2Type S mortar may be used for below-grade or high-load bearing applications where the additional strength is required.
NOTE Type N is the correct default for cast stone, and a blanket Type S requirement is a durability mistake. (12.3)
NOTE Type S mortar is stronger and less permeable than Type N, and in many cast stone mixes it is also harder than the units it sets. A mortar harder than the stone concentrates movement and freeze-thaw stress at the unit face instead of relieving it in the softer joint, causing the cast stone — not the mortar — to spall. Type N is softer and more forgiving and is correct for the great majority of above-grade work; Type S is reserved for the specific below-grade and high-load cases that genuinely need it. (12.4)
Setting mortar typeradio
Type N (above-grade setting beds and joints)
Type S (below-grade or high-load)
12.5Mortar joints shall be 3/8 inch wide for masonry-coursed installations, or 1/4 inch where a tight joint is architecturally required.
Mortar joint widthradio
3/8
1/4

12.6 Joint Treatment

12.6.1Joints required to remain open for drainage shall not be filled with mortar or sealant, and shall be identified on the drawings.
12.6.2Sealant joints shall be used at relief and expansion locations and at junctions with dissimilar materials.
NOTE Identifying which joints stay open for drainage is as important as specifying the sealant, because a sealed weep path traps water in the wall. (12.6.3)
NOTE Behind copings and above flashing, certain head joints are deliberately left open to let water that reaches the flashing plane drain out. If the specification calls for sealant at all joints without exempting these drainage joints, the installer seals the weeps, water collects in the backup wall, and the failure shows up as efflorescence and freeze-thaw damage well away from its cause. The drawings must distinguish drainage joints from sealed joints; coordination with the weep system is governed by Through Wall Flashing. (12.6.4)
Joint treatment at relief and movement locationsradio
Sealant joint
Mortar joint

12.7 Movement Joints

12.7.1Continuous runs of cast stone trim shall be interrupted by movement joints at intervals not exceeding 20 feet.
12.7.2Movement joints shall align with the building's expansion and control joints where they occur in the same plane.
NOTE Cast stone moves with temperature and moisture, and a long uninterrupted run with no movement joint cracks at the weakest point. (12.7.3)
NOTE Like all cementitious materials, cast stone expands and contracts with temperature and moisture change. A run of trim longer than about 20 feet with no relief accumulates enough movement to crack, and the crack appears at a mortar joint or straight through a unit at whatever point is weakest, not where it can be controlled. Designed movement joints at regular intervals give that movement a planned location to occur. (12.7.4)

13 Installation

13.1Units shall be set in accordance with the approved shop drawings and the manufacturer's job-site handling and installation instructions.
13.2Units shall be dampened immediately before setting so they do not draw water out of the setting mortar.
13.3Mortar shall be kept damp for not less than 7 days after setting to allow proper cure.
13.4Face of units shall be set within 1/4 inch of plumb measured over any 10 foot length, in accordance with TMS 602 masonry construction tolerances.
13.5Cast stone coursing heights, sill heights, and lintel seat heights shall be coordinated with the backup masonry module before fabrication.
NOTE Coursing coordination must happen on paper before units are cast, because a mismatch discovered in the field is expensive to correct. (13.6)
NOTE Cast stone sill heights, lintel seats, and band course elevations have to land on the backup wall's coursing module — the CMU or brick course heights set under Unit Masonry or Brick Masonry. If the trim is dimensioned independently and the modules do not align, the mismatch is found only when units arrive and will not seat at the coursing, forcing field shimming, cut units, or remanufacture. Reconciling the trim dimensions with the backup module during shop drawing review prevents this. (13.7)
13.8Units shall be cleaned with the manufacturer's approved methods only; acids and aggressive cleaners that etch or discolor the face shall not be used.

14 Delivery, Storage, and Handling

14.1Units shall be delivered with non-staining separators between stacked pieces and shall be protected from chipping and soiling during transport.
14.2Units shall be stored off the ground on level dunnage and protected from rain saturation, ground splash, and construction traffic.
14.3Units shall be lifted at the points and by the methods identified in the manufacturer's handling instructions, using slings and padding that do not mark the finished face.
NOTE Cast stone is most vulnerable to damage before it is set, when its finished faces are exposed and its arrises are unsupported. (14.4)
NOTE A unit that is flawless leaving the plant is easily chipped, stained, or cracked by careless stacking, ground contact, or point lifting on the job site. Because the finished face cannot be repaired invisibly and a cracked unit must be replaced on a long lead, handling and storage discipline directly protect the schedule and the appearance. The manufacturer's lifting points exist because units are engineered to be picked a certain way; ignoring them risks cracking long or reinforced pieces. (14.5)

15 Warranty

15.1The manufacturer shall warrant that cast stone units comply with ASTM C1364 and are free of defects in materials and manufacture for the warranty period.
15.2The installer shall warrant that installation is free of defects in workmanship for the warranty period.
Warranty periodradio
1 year
2 years
5 years

16 Spare Units

16.1The Contractor shall deliver attic-stock spare units of selected profiles, from the same production run as the installed work, for future replacement.
NOTE Spare units should be furnished for the most exposed and most likely-to-be-damaged profiles, such as copings, sills, and base course units. (16.2)
NOTE Cast stone color and texture cannot be matched exactly in a later production run because aggregate lots, pigment dosage, and finishing crews change over time. Holding spares from the original run gives the Owner color-correct replacements for the units most likely to be struck or weathered. Coordination, quality, and submittal procedures common to this and other trades are governed by Submittal And Quality Procedures. (16.3)
Spare unit profiles to stockcheckbox
Copings
Sills
Lintels
Banding / string course
Quoins
Base course

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Cast Stone." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/cast-stone — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.