Eccentric Plug Valves
Revision1
EditedOct 12, 2026
StatusCurrent
Contents
- 1Scope
- 2Referenced Standards
- 3Submittals
- 3.1Action Submittals
- 3.2Closeout Submittals
- 4Quality Assurance
- 4.1Manufacturer Qualifications
- 4.2Single-Source Responsibility
- 4.3Marking and Compliance
- 5Service Conditions
- 5.1Line Fluid and Temperature
- 5.2Ambient Conditions
- 6Size, Port, and Pressure Rating
- 6.1Valve Size
- 6.2Port Area
- 6.3Rated Working Pressure
- 6.4Shutoff Direction
- 7Body, Plug, and Seat
- 7.1Body
- 7.2Plug
- 7.3Seat
- 7.4Shaft, Bearings, and Seals
- 8End Connections and Bolting
- 8.1End Connections
- 8.2Bolting
- 9Lining and Coating
- 10Manual Operators
- 10.1Operator Type
- 10.2Worm-Gear Operators
- 10.3Position Indication
- 11Power Actuation Interface
- 12Buried Service
- 13Shop Testing
- 14Installation
- 14.1Orientation
- 14.2Piping Connections and Support
- 14.3Flushing and Field Testing
- 15Delivery, Storage, and Handling
- 16Warranty
- 17Spare Parts
View changes in this revision Revision history
Current revision. This is editorial revision 1, the current text of this standard. Read it on the standard's page.
Initial publication
1 Scope
NOTE This standard covers the resilient-seated eccentric plug valve: a quarter-turn valve whose plug rotates on a shaft offset from the seat so that the plug lifts out of the flow path when it opens and presses into a raised seat when it closes, built to AWWA C517 in sizes 3 in. through 72 in. for raw water, wastewater, sludge, scum, grit, and other liquids that carry solids. (1.1)
NOTE The boundary of the work is the valve from face to face, with its manual operator or its mounting base for a power actuator, its lining and coating, and the extension stem and valve box of a buried installation. The piping the valve sits in, the pipe supports, and the actuator that drives it from the control system are governed by the standards named for them. (1.2)
NOTE A gate valve in a sludge line closes into the grit that has settled in its seat, and a ball valve traps solids in its cavity. The eccentric plug valve is specified in solids service because the plug swings clear of the port when it is open and seats without wiping across the body, so a settled solid is pushed aside rather than packed into the seal. The orientation rules in this standard exist because that advantage depends on how the valve is installed, not only on what it is. (1.3)
1.4 Eccentric plug valves shall comply with AWWA C517.
NOTE Valves in this standard are isolation valves. A plug valve that modulates against a process variable, with the positioner and actuator that duty requires, is a control valve under Control Valves And ActuatorsControl Valves and ActuatorsResolves to the current adopted revision.sync/control-valves-and-actuators, and the electric, pneumatic, or hydraulic actuator mounted on an isolation valve under this standard is furnished under Valve And Gate ActuatorsValve and Gate ActuatorsResolves to the current adopted revision.sync/valve-and-gate-actuators. (1.5)
NOTE This standard is read with Common Work Results ProcessCommon Work Results for Process EquipmentResolves to the current adopted revision.sync/common-work-results-process, the umbrella for the process discipline, and the valve is installed in piping governed by Ductile Iron Process PipingDuctile Iron Process PipingResolves to the current adopted revision.sync/ductile-iron-process-piping, Steel And Stainless Process PipingSteel and Stainless Steel Process PipingResolves to the current adopted revision.sync/steel-and-stainless-process-piping, or Plastic Process PipingPlastic Process PipingResolves to the current adopted revision.sync/plastic-process-piping inside a plant, by Water Distribution PipingSite Water Distribution PipingResolves to the current adopted revision.sync/water-distribution-piping on a buried site water main, and by Sanitary Sewer SystemsSanitary Sewer Systems (Site)Resolves to the current adopted revision.sync/sanitary-sewer-systems on a sewage force main. (1.6)
NOTE The following are outside this scope and are governed by the standards named. (1.7)
- Rubber-seated butterfly valves under AWWA C504 and C516: Butterfly ValvesButterfly ValvesResolves to the current adopted revision.sync/butterfly-valves
- Modulating control valves of every body style with their actuators and positioners: Control Valves And ActuatorsControl Valves and ActuatorsResolves to the current adopted revision.sync/control-valves-and-actuators; actuators, extension stems, and floor stands on isolation valves: Valve And Gate ActuatorsValve and Gate ActuatorsResolves to the current adopted revision.sync/valve-and-gate-actuators
- Isolation, check, and plug valves in building hydronic piping: HVAC Piping ValvesGeneral-Duty Valves for HVAC PipingResolves to the current adopted revision.sync/hvac-piping-valves; in domestic water piping: Plumbing Piping ValvesGeneral-Duty Valves for Plumbing PipingResolves to the current adopted revision.sync/plumbing-piping-valves
- Lubricated and non-lubricated plug valves in fuel gas service: Fuel Gas PipingFacility Liquefied-Petroleum and Fuel Gas PipingResolves to the current adopted revision.sync/fuel-gas-piping and Natural Gas PipingNatural Gas PipingResolves to the current adopted revision.sync/natural-gas-piping
- The discharge isolation valve furnished inside a packaged lift station: Packaged Pump StationsPackaged Pump and Lift StationsResolves to the current adopted revision.sync/packaged-pump-stations; inside a building sewage ejector package: Sump And Sewage PumpsSump and Sewage PumpsResolves to the current adopted revision.sync/sump-and-sewage-pumps
- Resilient-seated gate valves: Resilient Seated Gate ValvesResilient-Seated Gate ValvesResolves to the current adopted revision.sync/resilient-seated-gate-valves; process check valves: Process Check ValvesProcess Check ValvesResolves to the current adopted revision.sync/process-check-valves; air release and vacuum valves: Air Release And Vacuum ValvesAir Release and Vacuum ValvesResolves to the current adopted revision.sync/air-release-and-vacuum-valves; knife gate valves for sludge, slurry, grit, and dry solids: Knife Gate ValvesKnife Gate ValvesResolves to the current adopted revision.sync/knife-gate-valves; isolation actuators with their extension stems and floor stands: Valve And Gate ActuatorsValve and Gate ActuatorsResolves to the current adopted revision.sync/valve-and-gate-actuators
- Sleeved plug valves for chemical feed service: not yet owned by a SynC standard
2 Referenced Standards
2.1 Valves, operators, coatings, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2 Where the Contract Documents, the adopted codes, and a referenced standard differ on the same matter, the most stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
| Standard | Title |
|---|---|
| AWWA C517 | Resilient-Seated Cast-Iron Eccentric Plug Valves |
| AWWA C550 | Protective Interior Coatings for Valves and Hydrants |
| AWWA C105 / A21.5 | Polyethylene Encasement for Ductile-Iron Pipe Systems |
| AWWA C111 / A21.11 | Rubber-Gasket Joints for Ductile-Iron Pressure Pipe and Fittings |
| AWWA C540 | Power-Actuating Devices for Valves and Slide Gates |
| AWWA C542 | Electric Motor Actuators for Valves and Slide Gates |
| AWWA C606 | Grooved and Shouldered Joints |
| AWWA M49 | Quarter-Turn Valves: Head Loss, Torque, and Cavitation Analysis |
| ASME B16.1 | Gray Iron Pipe Flanges and Flanged Fittings: Classes 25, 125, and 250 |
| ASME B16.42 | Ductile Iron Pipe Flanges and Flanged Fittings: Classes 150 and 300 |
| ASTM A126 | Gray Iron Castings for Valves, Flanges, and Pipe Fittings |
| ASTM A276 / A276M | Stainless Steel Bars and Shapes |
| ASTM A307 | Carbon Steel Bolts, Studs, and Threaded Rod 60 000 PSI Tensile Strength |
| ASTM A536 | Ductile Iron Castings |
| ASTM D2000 | Classification System for Rubber Products in Automotive Applications |
| ASTM F593 | Stainless Steel Bolts, Hex Cap Screws, and Studs |
| MSS SP-25 | Standard Marking System for Valves, Fittings, Flanges, and Unions |
| NSF/ANSI 61 | Drinking Water System Components: Health Effects |
| NSF/ANSI/CAN 372 | Drinking Water System Components: Lead Content |
3 Submittals
3.1 Action Submittals
3.1.1 The Contractor shall submit the following for the Engineer of Record's review and return before any valve under this standard is released for manufacture:
- Product data for each valve size and configuration, identifying the AWWA C517 designation, port area as a percentage of the nominal pipe area, rated working pressure in each direction, body, plug, seat, shaft, and bearing materials, plug facing elastomer, shaft seal type, end connection and flange drilling, and the lining and coating system
- A valve schedule keyed to the tag numbers on the drawings, listing for each valve its size, service, end connections, rated pressure, operator or actuator, orientation, and buried or exposed installation
- Operator data for each manually operated valve, identifying the operator type, gear ratio, input device, rim pull or input torque at the valve's rated differential pressure, and the position indicator
- Seating, unseating, and running torque at the rated differential pressure for each power-actuated valve, with the mounting base dimensions and the coupling detail, for use by the actuator supplier
- Shop drawings showing the installed orientation of each valve: the seat end, the shaft axis, and the position of the plug when the valve is open
- Lining and coating product data with the AWWA C550 compliance statement, the dry film thickness, and the NSF/ANSI 61 certification where required
- Extension stem, operating nut, and valve box product data for each buried valve, with the stem length computed from the bury depth
- The manufacturer's affidavit of compliance with AWWA C517
Action Submittals Requiredcheckbox
☑ Valve product data by size and configuration
☑ Valve schedule keyed to drawing tags
☑ Manual operator data with rim pull or input torque
☑ Torque data and mounting base detail for power-actuated valves
☑ Shop drawings showing installed orientation
☑ Lining and coating product data
☐ Extension stem, operating nut, and valve box data
☑ Affidavit of compliance with AWWA C517
3.1.2 A valve shall not be released for manufacture until the submittal covering it has been returned by the Engineer of Record.
NOTE The orientation shop drawing is the submittal that catches the most errors on this product, because a plug valve that is correct in every material and rating still fails in solids service when its shaft is vertical or its seat faces the wrong way. Reviewing the orientation on paper, valve by valve, is far cheaper than finding it in a sludge line. (3.1.3)
3.2 Closeout Submittals
3.2.1 The Contractor shall submit the following before the valves are accepted:
- Certified shop test reports for each valve, recording the shell test and the seat leakage test in each direction tested
- Field operation test records for each installed valve, recording the full-cycle operation, the stop settings, and the indicator agreement
- Operation and maintenance data covering seal replacement, stop adjustment, operator lubrication, and the plug and seat inspection procedure
- Record drawings showing the installed location, orientation, and tag of each valve, and the valve box location and stem length of each buried valve
- Warranty documentation naming the warranty start date and the party responsible for warranty service
Closeout Submittals Requiredcheckbox
☑ Certified shop test reports
☑ Field operation test records
☑ Operation and maintenance data
☑ Record drawings with valve locations and orientation
☑ Warranty documentation
4 Quality Assurance
4.1 Manufacturer Qualifications
4.1.1 Valves shall be the product of a manufacturer that has produced AWWA C517 eccentric plug valves of the sizes furnished for not less than ten years.
4.1.2 The manufacturer shall certify that the valve design furnished has passed the proof-of-design testing of AWWA C517.
4.1.3 Replacement plugs, seats, shaft seals, bearings, and operator parts shall be available from the manufacturer for not less than fifteen years from the date of shipment.
NOTE A plug valve in a treatment plant is serviced in place for decades, and the part that wears is the plug facing. A manufacturer that can still supply a plug for a thirty-year-old body is what keeps a seal replacement from becoming a valve replacement with a piping modification around it. (4.1.4)
4.2 Single-Source Responsibility
4.2.1 Every eccentric plug valve on the project shall be the product of a single manufacturer.
4.2.2 Where a valve is furnished with a manual operator, the operator shall be mounted, adjusted, and tested on the valve by the valve manufacturer before shipment.
4.2.3 Where a valve is furnished with a power actuator, the valve manufacturer shall mount the actuator, set the stops, and stroke the assembly before shipment, whichever party furnishes the actuator.
NOTE The stop settings on an eccentric plug valve are what put the plug on the seat without driving it past, and they are set against the actual plug and seat the valve shipped with. An actuator mounted in the field is set by a party that did not build the valve, against a seat it cannot see. (4.2.4)
4.3 Marking and Compliance
4.3.1 Each valve body shall be permanently marked with the manufacturer's name or mark, the valve size, the rated working pressure, the body material designation, and the seat end, in accordance with MSS SP-25 and AWWA C517.
4.3.2 Where the datasheet requires NSF/ANSI 61 certification, every wetted component of the valve, including the lining, the plug facing, the seat, and the shaft seals, shall be certified to NSF/ANSI 61, and the valve shall be certified to NSF/ANSI/CAN 372.
NSF/ANSI 61 Certification of Wetted Componentsradio
○ Required
○ Not required
NOTE A valve on a raw water line ahead of a drinking-water plant, or on finished, backwash, or reclaimed water, is a drinking water system component to most regulators, and the certification is what the regulator and the utility accept as proof. A valve on wastewater, sludge, or scum carries no such requirement, and a certified lining costs more and narrows the list of manufacturers. The decision follows the service of the valves on the project, which is why the field has no default. (4.3.3)
5 Service Conditions
5.1 Line Fluid and Temperature
5.1.1 The line fluid at each valve shall be as shown on the process and instrumentation diagrams, and the plug facing, seat, lining, and bolting selections of this standard shall be made for that fluid.
5.1.2 The maximum continuous line fluid temperature at the valves shall be as indicated in the datasheet.
Highest Continuous Line Fluid Temperaturerange
°F
406080100120140150180200250
Per drawings — the valve schedule (deferred by default)
5.1.3 Every elastomer, bearing, seal, and lining in the valve shall be rated by its manufacturer for continuous service at the maximum line fluid temperature.
5.1.4 Where the line fluid carries grit, sand, or other abrasive solids, the valve shall be furnished with seals at the shaft journals that exclude the line fluid from the bearings.
5.2 Ambient Conditions
5.2.1 Operators, actuator mounting bases, and position indicators installed outdoors shall be rated for continuous exposure to the range from Site Ambient Temperature MinimumSite Ambient Temperature MinimumParameterEach project supplies its own value.site-ambient-temperature-minimum to Site Ambient Temperature MaximumSite Ambient Temperature MaximumParameterEach project supplies its own value.site-ambient-temperature-maximum.
5.2.2 Where Site Ambient Temperature MinimumSite Ambient Temperature MinimumParameterEach project supplies its own value.site-ambient-temperature-minimum is below 32°F, a valve installed outdoors or in an unheated structure shall be provided with the drain, heat tracing, or insulation the standard governing the connected piping requires for that location.
NOTE The body of a closed plug valve holds a pocket of line fluid on each side of the plug that does not drain with the pipe. Where that fluid can freeze, the pocket is the part of the line that breaks, and the piping standard's freeze provisions have to reach the valve body, not stop at the flange. (5.2.3)
5.2.4 Valves installed in a vault, a wet well, or a below-grade gallery subject to flooding shall be furnished with operators and seals suitable for intermittent submergence.
6 Size, Port, and Pressure Rating
6.1 Valve Size
6.1.1 The nominal size of each valve shall be as indicated in the datasheet.
Valve Sizerange
in. NPS
3468101214161820243036424854606672
Per drawings — the valve schedule and the process and instrumentation diagrams (deferred by default)
6.1.2 A valve shall be the same nominal size as the pipe it is installed in unless the process and instrumentation diagrams show a reduced valve with reducers on each side.
NOTE Valves smaller than 3 in. in process service are outside AWWA C517 and this standard, and the piping standard governing the line selects the small valve. (6.1.3)
6.2 Port Area
6.2.1 The port area of the valves shall be as indicated in the datasheet.
Port Arearadio
○ Full port
○ Standard port
6.2.2 A full port valve shall have a port area of not less than 100 percent of the nominal pipe area, round or rectangular, with no projection into the flow path when the valve is open.
6.2.3 A standard port valve shall have a port area of not less than the minimum AWWA C517 requires for the valve size.
NOTE AWWA C517's minimum port area is a fraction of the pipe area, about 80 percent for most sizes, and the standard-port valve built to it is the valve most manufacturers stock and most plants own. Its head loss is small in isolation service, where the valve is either open or closed. A full port valve costs more and has a longer body, and it is selected where the line is pigged or cleaned with a tool that has to pass through the valve, where the valve is throttled in a fixed position and the loss across the reduced port would matter, or where a sludge line is sized tightly enough that the port reduction would raise the velocity at the valve above what the solids tolerate. The choice follows the lines on the project rather than the product, so the field carries no default. (6.2.4)
6.2.5 Valves in a line that the process and instrumentation diagrams show as pigged shall be full port regardless of the datasheet selection.
6.3 Rated Working Pressure
6.3.1 The rated working pressure of each valve shall be as indicated in the datasheet.
Rated Working Pressurerange
psi
150175200250
Derived — the valve size, per the AWWA C517 size rating, and the design pressure of the connected piping including surge (by default)
6.3.2 Each valve shall carry a rated working pressure not less than the AWWA C517 rating for its size.
6.3.3 Each valve shall carry a rated working pressure not less than the design pressure of the connected piping, including the surge allowance that piping is designed for under the standard governing it.
NOTE AWWA C517 rates valves 12 in. and smaller at 175 psi and 14 in. and larger at 150 psi, and that rating covers nearly every raw water, wastewater, and sludge line a treatment plant has. Where a force main or a high-head pump discharge is designed above it, manufacturers offer heavier bodies in the smaller sizes, which is why the field is derived from the size and the piping design pressure rather than fixed at the standard's number. (6.3.4)
6.4 Shutoff Direction
6.4.1 The shutoff rating direction of the valves shall be as indicated in the datasheet.
Shutoff Rating Directionradio
○ Bidirectional
○ Direct-pressure direction only
6.4.2 A valve rated bidirectional shall be drip-tight at the rated working pressure with the pressure applied from either side of the closed plug.
6.4.3 A valve rated in the direct-pressure direction only shall be drip-tight at the rated working pressure with the pressure applied to the side that presses the plug onto the seat, and the manufacturer shall publish the pressure at which the valve is drip-tight in the reverse direction.
NOTE Line pressure that reaches the plug from the side opposite the seat presses the plug into the seat, and the valve seals more tightly as the pressure rises. Pressure that arrives from the seat side tries to lift the plug off, and the seal then depends on the operator's seating force and the elastomer's interference alone, so the reverse rating of a valve is often well below its direct rating. A bidirectional valve carries a seat and a seating load that hold either way, at a higher operating torque and price. The decision is a matter of where the pressure comes from when the valve is closed: a valve that always closes against one direction, such as a tank outlet, is served by a direct-pressure valve installed the right way round; a valve that sees pressure from both sides, such as a pump discharge that holds back the force main when the pump is off and holds back the pump when it runs against a closed valve, or any valve whose line can be pressurized from either end for maintenance, needs the bidirectional rating. (6.4.4)
7 Body, Plug, and Seat
7.1 Body
7.1.1 The body material shall be as indicated in the datasheet.
Body Materialradio
● Cast iron
○ Ductile iron
7.1.2 Cast iron bodies shall conform to ASTM A126 Class B.
7.1.3 Ductile iron bodies shall conform to ASTM A536, Grade 65-45-12.
NOTE Cast iron is the material AWWA C517 is written around and the body nearly every plug valve in a treatment plant is cast in, at the lowest cost and with the full size range available. Ductile iron carries roughly twice the tensile strength and a ductility that cast iron lacks, so it is selected where the valve is rated above the standard pressure, where it is buried in a line subject to ground movement or heavy surface loads, or where a flanged body is bolted to a steel flange and the bolting load would overstress a gray iron flange. (7.1.4)
7.1.5 The body shall be a one-piece casting with a bolted cover, and the plug, seat, bearings, and shaft seals shall be serviceable through the cover without removing the body from the line.
7.1.6 The cover shall be gasketed to the body with a full-face elastomer gasket retained in a machined recess.
7.2 Plug
7.2.1 The plug material shall be as indicated in the datasheet.
Plug Materialradio
○ Cast iron
○ Ductile iron
7.2.2 The plug shall be a one-piece casting of the material selected, conforming to ASTM A126 Class B for cast iron or ASTM A536 Grade 65-45-12 for ductile iron, with the shaft integral with the plug or keyed to it so that the plug cannot rotate on the shaft.
NOTE The plug is the part that carries the seating load and the operator's torque, and a plug in a large valve sees a bending moment across its full width every time it closes against pressure. Ductile iron carries that moment with margin and is the material most manufacturers cast large plugs in; cast iron is lighter and less costly in the small sizes, where the moment is small. The two castings are independent choices because a cast iron body with a ductile iron plug is a common and sound combination. (7.2.3)
7.2.4 The plug facing elastomer shall be as indicated in the datasheet.
Plug Facing Elastomerselect
Chloroprene
Nitrile
EPDM
Chlorosulfonated polyethylene
Fluoroelastomer
7.2.5 The plug facing shall be molded to and bonded with the plug over the full seating surface, shall conform to ASTM D2000 for the elastomer selected, and shall not be a loose or mechanically retained ring.
NOTE Chloroprene is the facing the eccentric plug valve was developed around and is the standard offering for raw water, wastewater, and sludge, with a long service record against sewage and a modest resistance to oil. Nitrile holds up against the grease and petroleum oils that reach a scum line or an industrial sewer and is the facing selected where those are present. EPDM carries the highest water-service temperature of the common facings and resists chlorine and chloramine, which attack chloroprene and nitrile over years of contact, so it is selected on chlorinated and chloraminated water. Chlorosulfonated polyethylene resists ozone and oxidizing chemicals. Fluoroelastomer carries the broadest chemical resistance and the highest temperature rating at the highest price, and is selected where the line carries a chemical the others cannot tolerate. (7.2.6)
7.2.7 Where the line fluid carries free oil or grease, the plug facing shall be nitrile or fluoroelastomer regardless of the datasheet selection.
7.3 Seat
7.3.1 The seat construction shall be as indicated in the datasheet.
Seat Constructionselect
Welded-in nickel overlay
Welded-in stainless steel overlay
Mechanically retained stainless steel seat ring
7.3.2 A welded-in nickel overlay seat shall be a weld deposit of not less than 90 percent nickel on all body surfaces that contact the plug facing, machined to a smooth seating surface after welding.
7.3.3 A welded-in stainless steel overlay seat shall be a weld deposit of Type 316 stainless steel on all body surfaces that contact the plug facing, machined after welding.
7.3.4 A mechanically retained seat ring shall be Type 316 stainless steel, retained in the body so that it cannot rotate or lift under reverse pressure, and replaceable through the cover opening.
NOTE The seat is the one metal surface the plug facing bears on, and the raised seating surface of a plug valve is in the flow when the valve is open. A welded-in nickel overlay is corrosion resistant against the full range of sewage chemistry, fused to the body so there is no joint for grit to work into, and it is what AWWA C517 valves have carried for decades. A stainless overlay serves the same purpose where the owner standardizes on stainless wetted parts. A retained seat ring can be replaced in the field when it is scored, at the cost of a joint between ring and body that the line fluid can reach, which matters most in grit service. (7.3.5)
7.4 Shaft, Bearings, and Seals
7.4.1 The shaft shall be Type 304 or Type 316 stainless steel conforming to ASTM A276 / A276M, or an integral extension of a ductile iron plug where the manufacturer's standard design so provides.
7.4.2 Shaft bearings shall be sleeve type in both the upper and lower journals, of stainless steel or bronze, permanently lubricated, and shall not require field lubrication.
7.4.3 The shaft seal type shall be as indicated in the datasheet.
Shaft Seal Typeselect
Self-adjusting V-type packing
Adjustable pull-down packing
U-cup seals
7.4.4 The shaft seal shall be replaceable without removing the plug from the body and without removing the operator or the actuator mounting base from the valve.
7.4.6 Grit excluders or secondary seals shall be provided at each bearing journal so that the line fluid does not reach the bearing surfaces.
8 End Connections and Bolting
8.1 End Connections
8.1.1 The end connection of the valves shall be as indicated in the datasheet.
End Connectionselect
Flanged
Mechanical joint
Grooved
Threaded
8.1.2 Threaded ends shall be furnished only on 3 in. valves.
NOTE Flanged ends are the connection of exposed plant piping, where the valve is bolted between flanges it can be unbolted from for service, and they are the standard offering in every size. Mechanical joint ends take the restrained gasketed joint of a buried ductile iron main and let the valve be assembled in the trench without flange alignment, and they are the connection of buried service. Grooved ends suit a grooved process piping system in the sizes the coupling manufacturer rates for the line pressure. Threaded ends are available only in the smallest size and suit a threaded sludge or drain line where a flange would not fit. (8.1.3)
8.1.4 Buried valves shall have mechanical joint ends unless the connected main is flanged, in which case the valve shall be joined to the main with restrained flanged adapters as the standard governing the main requires.
8.1.5 The flange drilling of flanged valves shall be as indicated in the datasheet.
Flange Drillingradio
● ASME B16.1 Class 125
○ ASME B16.1 Class 250
8.1.6 Flanges on ductile iron bodies drilled to the Class 125 template shall conform to ASME B16.42 Class 150, and flanges drilled to the Class 250 template shall conform to ASME B16.42 Class 300.
NOTE Class 125 drilling matches the flanges of every ductile iron fitting and flanged pipe in a plant and every cast iron valve, and it is what the valve is bolted to on nearly every project. Class 250 drilling is selected where the connected piping is Class 250 or Class 300 for a pressure above the Class 125 rating, and the heavier flange needs the heavier body behind it. (8.1.7)
8.1.8 Flanged valves shall be flat faced.
8.1.9 Mechanical joint ends shall conform to AWWA C111 / A21.11 and shall be furnished with the gland, gasket, and bolting the joint requires.
8.1.10 Grooved ends shall conform to AWWA C606, cut or rolled to the coupling manufacturer's groove dimensions for the body material.
8.2 Bolting
8.2.1 The body and cover bolting material shall be as indicated in the datasheet.
Body and Cover Boltingselect
Zinc-plated carbon steel
Type 304 stainless steel
Type 316 stainless steel
8.2.2 Zinc-plated carbon steel bolting shall conform to ASTM A307, and stainless steel bolting shall conform to ASTM F593, Alloy Group 1 for Type 304 and Alloy Group 2 for Type 316.
8.2.3 Bolting on buried, submerged, and vault-installed valves shall be stainless steel regardless of the datasheet selection.
NOTE Plated carbon steel is the bolting a valve ships with and is adequate in a dry, heated gallery where it is inspected and painted with the valve. Type 304 holds up in the damp, hydrogen sulfide atmosphere of a wet well or a sludge gallery, where plated steel rusts within a few years and a seized cover bolt turns a seal replacement into a body replacement. Type 316 adds resistance to chlorides and is selected in a chlorinated water gallery, near the coast, or wherever the plant standardizes on it. The decision follows the atmosphere the valves sit in, which the project knows and the standard does not. (8.2.4)
8.2.5 Stainless steel bolting shall be assembled with an anti-seize compound on the threads.
9 Lining and Coating
9.1 The interior lining and exterior coating system of the valves shall be as indicated in the datasheet.
Lining and Coating Systemselect
Fusion-bonded epoxy
Two-part liquid epoxy
Manufacturer's standard (by default)
9.2 The interior lining shall comply with AWWA C550 and shall be applied to all ferrous wetted surfaces other than the seat and the machined bearing and seal surfaces.
9.3 The exterior coating shall be the same system as the interior lining, applied to all exterior ferrous surfaces other than flange faces and machined surfaces.
9.4 The dry film thickness of the lining and coating shall be not less than the value indicated in the datasheet, and not less than the coating manufacturer's published minimum for the service.
Lining and Coating Dry Film Thicknessrange
mils
468101216
NOTE Both epoxy systems comply with AWWA C550 and both are standard offerings, which is why the manufacturer's choice is acceptable. Fusion-bonded epoxy is applied as a powder to a heated casting and cures into a hard, uniform film that resists abrasion from grit, and it is the system most plug valves are lined with. Liquid epoxy is applied cold and suits a repair, a touch-up, or a casting too large for the manufacturer's oven. A thicker film buys abrasion life in grit and sludge service and holiday-free coverage on a rough casting, at a cost in cure time and in the risk of sagging on vertical surfaces. (9.5)
9.6 Where the datasheet requires NSF/ANSI 61 certification, the lining shall be certified to NSF/ANSI 61 for the valve size and the line fluid temperature.
9.7 Flange faces, the seat, machined bearing and seal surfaces, and the plug facing shall be masked during coating.
9.8 Buried valves shall be polyethylene encased in accordance with AWWA C105 / A21.5 where the connected main is encased, and the encasement shall be continuous over the valve body and the mechanical joints.
9.9 Coating damaged in shipment or installation shall be repaired with the lining manufacturer's recommended repair material before the valve is put in service, and the Contractor shall bear the cost of the repair.
10 Manual Operators
10.1 Operator Type
10.1.1 Lever operators shall be furnished on valves 6 in. and smaller as indicated in the datasheet, and every other valve shall be furnished with a worm-gear operator.
Lever Operatorsselect
Permitted on valves 6 in. and smaller
Permitted on valves 4 in. and smaller
Not permitted
NOTE A lever is the fastest operator a plug valve can have, a quarter turn from open to closed, and in the small sizes the operating torque is low enough for one person to close it against rated pressure. At 6 in. the torque in sludge service is at the edge of what a lever can deliver, and a lever that cannot be moved by hand gets a pipe extension put on it. A worm-gear operator trades speed for a rim pull anyone can apply and for a self-locking gear train that holds the plug where it is set, so a plant that throttles its small plug valves in a fixed position, or whose operators work from a platform, tends to specify gears down to the smallest size. (10.1.2)
10.1.3 Lever operators shall be furnished with a lever of a length that closes the valve against the rated differential pressure, a position indicator, and adjustable open and closed stops, and shall be lockable in the open and closed positions.
10.1.4 Lever operators shall be furnished with a quadrant that holds the plug at intermediate positions for throttling where the valve schedule designates a valve for fixed-position throttling.
10.2 Worm-Gear Operators
10.2.1 Worm-gear operators shall be totally enclosed, grease packed, self-locking, and sized to close the valve against the rated differential pressure in the direction the valve is rated for.
10.2.2 Each worm-gear operator shall have adjustable open and closed stops, a position indicator visible from the operating floor, and a gear housing sealed against the environment of the installed location.
10.2.3 The input device on worm-gear operators of exposed valves shall be as indicated in the datasheet.
Worm-Gear Operator Input Deviceselect
Handwheel
Chainwheel
2 in. square operating nut
Handwheel with a 2 in. square operating nut
NOTE A handwheel is the operator of a valve at an operating floor, where the operator stands at it. A chainwheel is the operator of a valve mounted overhead, and it is selected per location rather than per project. A 2 in. square operating nut is the input of a buried valve and of an exposed valve the plant operates with a portable wrench or key, and a handwheel fitted with a nut lets the same valve be operated by hand at the floor and by a portable actuator when the pull is heavy. (10.2.4)
10.2.5 Operators whose centerline is above the operating floor by more than the height indicated in the datasheet shall be furnished with a chainwheel regardless of the input device selected, with the chain reaching to within 4 ft of the floor.
Operator Height Above Floor Requiring a Chainwheelrange
ft
566.578
10.2.6 The rim pull required at the handwheel or chainwheel to close a valve against its rated differential pressure shall not exceed the value indicated in the datasheet.
Rim Pull at Rated Differentialrange
lb
406080
Default: Not more than 80 lb
NOTE Eighty pounds is the rim pull the AWWA valve standards have long used as the limit a person can apply to a handwheel, and it is the figure nearly every waterworks specification carries. A lower limit buys an easier valve at the cost of a higher gear ratio and more turns from open to closed, and it is selected where the operators work from a ladder or a platform, or where a plant standardizes on a lower figure. (10.2.7)
10.2.8 Valves shall open counterclockwise or clockwise as indicated in the datasheet, and the direction shall be cast or stamped on the operator.
Opening Directionradio
● Counterclockwise to open
○ Clockwise to open
NOTE Counterclockwise to open is the AWWA default and the direction nearly every plant and utility operates, and a valve that opens the other way is a valve an operator will close when they mean to open it. Clockwise to open is selected only where the owning utility has standardized on it across its system, so that every valve the same crew touches turns the same way. (10.2.9)
10.3 Position Indication
10.3.1 Where the process and instrumentation diagrams show open or closed status for a manually operated valve, the operator shall be furnished with limit switches that signal the open and closed positions, and the wiring from those switches shall be installed under Control Systems IntegrationControl Systems Integration and TestingResolves to the current adopted revision.sync/control-systems-integration.
11 Power Actuation Interface
11.1 The actuation of each valve shall be as indicated in the datasheet.
Actuationselect
Manual operator
Electric motor actuator
Pneumatic cylinder actuator
Hydraulic cylinder actuator
Per drawings — the valve schedule (deferred by default)
NOTE Electric motor actuators under AWWA C542 and pneumatic and hydraulic cylinder actuators under AWWA C541 on valves under this standard are furnished and specified under Valve And Gate ActuatorsValve and Gate ActuatorsResolves to the current adopted revision.sync/valve-and-gate-actuators; the actuator of a plug valve in a modulating control loop is furnished under Control Valves And ActuatorsControl Valves and ActuatorsResolves to the current adopted revision.sync/control-valves-and-actuators. (11.2)
11.3 Each power-actuated valve shall be furnished with a mounting base and a shaft coupling that accept the actuator, and the valve manufacturer shall furnish the seating, unseating, and running torque of the valve at its rated differential pressure, determined in accordance with AWWA M49, for the actuator to be sized from.
11.4 The actuator shall be sized by the actuator supplier from the valve manufacturer's torque data with the margin the actuator standard requires, and the valve manufacturer shall not substitute a lower torque figure for the actuator's benefit.
NOTE The torque of an eccentric plug valve rises with the differential pressure, with the seating interference of the facing, and with the time the valve has sat closed in sludge, and the figure that matters for the actuator is the breakaway torque at the rated differential after that sit. A valve that is sized from running torque alone stalls its actuator the first time it is asked to open against a full force main. (11.5)
11.6 Mechanical stops in the valve or the operator shall absorb the actuator's seating thrust, and the actuator shall not drive the plug past the closed stop.
12 Buried Service
12.1 Buried valves shall be installed at the depth of the main they are set in, whose depth of cover is set below Frost DepthFrost DepthParameterEach project supplies its own value.frost-depth by the standard governing the main.
12.2 The access to each buried valve shall be as indicated in the datasheet.
Buried Valve Accessradio
○ Valve box with an extension stem to an operating nut at grade
○ Precast valve vault with the operator at the valve
○ Not applicable, no buried valves
NOTE A valve box is the lowest-cost access, a cast iron shaft from the operator to a lid in the surface, and a crew operates the valve from grade with a key. It suits an isolation valve that is operated a few times a year and needs no inspection. A vault puts the operator, the shaft seal, and the flanges where a person can reach them, and it is selected for a valve that is operated often, that carries a power actuator, or that sits where a leak at the seal has to be seen before it reaches the ground, at the cost of the structure and the confined-space entry it creates. (12.3)
12.4 Buried valves operated through a valve box shall be furnished with a totally enclosed worm-gear operator sealed and grease packed for buried service, a 2 in. square operating nut, and an extension stem of a length that brings the operating nut to within the depth indicated in the datasheet below finished grade.
Depth of Operating Nut Below Finished Graderange
in.
12182430364860
NOTE A shallow nut lets a short key reach it and a crew see the nut before engaging it; a deep nut needs a longer key and a crew working blind. Utilities that operate many valves tend to set a shallow limit; a plant with a few buried valves on deep force mains tends to accept a deeper nut rather than a long stem that whips in the box. (12.5)
12.6 Extension stems shall be solid steel, coupled to the operating nut of the valve with a pinned coupling, centered in the valve box by a guide, and shall not be the operating nut's only means of alignment.
12.7 Valve boxes shall be cast iron, two-piece or three-piece slide type, of a shaft diameter that clears the extension stem and its guide, set plumb over the operating nut and supported on the backfill rather than on the valve, with the lid set flush with finished grade and marked with the service of the main.
NOTE A valve box that bears on the valve transfers wheel loads and settlement from the surface into the body and the main, and a box that is off plumb binds the key at the lid and the stem at the nut, so the valve box is set on compacted backfill and checked plumb before the surface is finished. The buried valve is the one valve nobody sees after the trench is closed, and the box is the only path to it. (12.8)
12.9 The orientation of each buried valve shall be recorded on the record drawings before the trench is backfilled.
13 Shop Testing
13.1 Each valve shall be shop tested in accordance with AWWA C517, including a hydrostatic shell test with the plug open at the pressure and for the duration AWWA C517 prescribes, and a seat leakage test at the rated working pressure with the plug closed, applied in each direction for which the valve is rated.
13.2 Each valve shall be operated through a full cycle after assembly, with the operator or the actuator mounted, and the stop settings, the position indicator, and the rim pull or input torque shall be verified against the submittal.
13.3 A valve that leaks past the seat at the rated pressure, leaks at the shaft seal, or exceeds the rim pull limit shall be corrected and retested at the manufacturer's expense before shipment.
13.4 Shop test witnessing shall be as indicated in the datasheet.
Shop Test Witnessingradio
● Certified test reports, unwitnessed
○ Witnessed by the Engineer of Record or the Owner's representative
NOTE A certified report is what nearly every project accepts for a product tested to a consensus standard in a factory with a quality system, and a witnessed test adds travel and a factory hold for each lot. Witnessing is selected where the valves are large, where the project carries a bidirectional rating or a pressure above the standard rating that the Engineer of Record wants to see proven, or where a prior project with the same manufacturer found a seat leak after delivery. (13.5)
13.6 Where witnessed testing is selected, the manufacturer shall give the witnessing party not less than ten business days notice of the test date, and shall not ship a valve the witness has not accepted.
14 Installation
14.1 Orientation
14.1.1 Each valve shall be installed in the orientation shown on the accepted orientation shop drawing.
14.1.2 A valve in horizontal piping that carries wastewater, sludge, scum, grit, or any other liquid with settleable solids shall be installed with the shaft horizontal and with the plug in the upper half of the body when the valve is open.
NOTE A plug that opens downward swings into the bottom of the body, where the solids that drop out of the flow settle, and it closes by lifting through that bed of grit every time. A plug that opens upward stores above the flow where nothing settles on it, and the solids collect in the bottom of the body where the seat is not. A vertical shaft puts the lower bearing in the sediment and the plug's travel in the same plane the solids settle in, which is why the shaft is horizontal in solids service whatever the piping layout prefers. (14.1.3)
14.1.4 A valve rated for shutoff in the direct-pressure direction only shall be installed with the seat end on the lower-pressure side of the closed plug, so that the line pressure presses the plug onto the seat.
14.1.5 The orientation of a direct-pressure valve shall be set for the pressure condition that exists while the valve is closed for its intended duty rather than for the normal running condition.
NOTE A pump discharge isolation valve is closed so the pump can be serviced, and while it is closed the pump is off and the force main's static head is on the far side of the plug. Orienting that valve for the running condition, with the pump pressure on the seat, seals it while the pump runs and lets it weep onto the open pump while the mechanic works on it. The closed condition that matters is the one the valve is closed for. (14.1.6)
14.1.7 A valve in vertical piping, and any valve whose service or arrangement is not covered by the rules above, shall be installed in the orientation the manufacturer publishes for that service.
14.1.8 Where a valve is installed in an orientation that differs from the accepted shop drawing, the Contractor shall remove and reinstall it at the Contractor's cost, including the cost of draining and refilling the line.
14.2 Piping Connections and Support
14.2.1 Valves shall be installed with the connected flanges aligned and parallel before the bolts are drawn up, and the bolting shall not be used to pull the piping into alignment with the valve.
NOTE A cast iron valve flange bends across the edge of a misaligned mating flange as the bolts are tightened, and cast iron has almost no ductility to absorb the bending. The crack appears at the valve, and the valve is blamed for a piping error. (14.2.2)
14.2.3 Flange bolts shall be tightened in a crossing pattern to the torque the gasket manufacturer publishes, and a raised-face flange shall be mated to a cast iron valve only through a flat-face adapter or a full-face gasket with the raised face removed.
14.2.4 Valves 8 in. and larger, and every power-actuated valve, shall be supported independently of the connected piping under the standard governing that piping, so that the weight of the valve and the actuator is not carried by the flanges.
14.2.5 Clearance shall be maintained around each valve for the cover to be removed, the plug to be withdrawn, and the operator or actuator to be removed, as shown on the piping plans and sections.
14.2.6 The operator of each exposed valve shall be positioned so that the handwheel, lever, or chainwheel is reachable from the operating floor or a permanent platform without climbing on the piping.
14.3 Flushing and Field Testing
14.3.1 Each valve shall be installed with its plug open during flushing of the connected piping, and the Contractor shall remove any construction debris that lodges in the body before the valve is first closed.
14.3.2 Installed valves shall be tested with the connected piping under the hydrostatic test of the standard governing that piping, with the plug open.
14.3.3 Where a valve forms the boundary of a piping test, the test pressure applied to the closed plug shall not exceed the valve's rated seat pressure in the direction the test pressure is applied, and a valve rated in the direct-pressure direction only shall not be used as a test boundary with the test pressure on its seat side.
NOTE A valve that forms a piping test boundary is being asked to hold the test pressure on its seat, and the test pressure of the piping is set above the valve's rating by design. A direct-pressure valve with the test on the wrong side of the plug leaks, the test fails, and the valve is blamed; a bidirectional valve with the test above its seat rating is damaged by the test it was never rated for. A blind flange is the test boundary, and the valve is tested open inside it. (14.3.4)
14.3.5 After installation and before the line is placed in service, the Contractor shall operate each valve through two full cycles, from fully open to fully closed and back, and shall verify that the plug reaches both stops, that the position indicator agrees with the plug, and that the operator moves without binding.
14.3.6 Each buried valve shall be operated through two full cycles from grade with the key, through the installed valve box and extension stem, after the trench is backfilled and before the surface is finished.
14.3.7 Each power-actuated valve shall be stroked under the actuator after the actuator is wired, and the stop settings shall be verified against the valve manufacturer's settings, under Control Systems IntegrationControl Systems Integration and TestingResolves to the current adopted revision.sync/control-systems-integration.
14.3.8 The field operation test of each valve shall be recorded on a report identifying the valve tag, the date, the persons present, the cycles performed, and any deficiency found and its correction.
14.3.9 A valve that fails its field operation test shall be corrected or replaced by the Contractor, and the retest shall be at the Contractor's cost.
15 Delivery, Storage, and Handling
15.1 Valves shall be shipped with the plug in the open position, the flange faces and ends protected by covers, and the operator or actuator mounted.
15.2 Valves shall be stored off the ground, with the end covers in place, and valves with elastomer facings shall be stored out of direct sunlight and away from ozone sources such as motors and welding equipment.
15.3 Valves shall be lifted by the body or by the lifting lugs the manufacturer provides, and shall not be lifted by the operator, the actuator, the extension stem, or the shaft.
NOTE A plug valve lifted by its operator carries the full weight of the body through the operator's mounting bolts and the shaft, and the stops and the indicator that were set at the factory are the first things to shift. The valve arrives on site looking undamaged and closes past its seat on the first cycle. (15.4)
15.5 The plug shall remain open throughout storage, and a valve stored closed for more than thirty days shall be cycled before installation.
NOTE An elastomer facing held against its seat under full interference for months takes a set at the seat line that it does not recover from, and the valve then seals at that one position and weeps at every other. Storing the valve open keeps the facing unloaded. (15.6)
16 Warranty
16.1 The Contractor shall warrant each valve, with its operator, lining, and buried-service components, against defects in materials and workmanship for the period indicated in the datasheet, measured from the date of substantial completion.
Warranty Periodrange
years
1235
Default: Not less than 1 years
16.2 Where the contract General Conditions specify a longer warranty period than the datasheet, the longer period shall govern.
16.3 A valve that leaks past the seat or at the shaft seal, binds in operation, or shows lining failure within the warranty period shall be repaired or replaced by the Contractor at no cost to the Owner.
16.4 The Contractor shall bear the cost of draining and refilling the line, of excavation and backfill at a buried valve, and of the repair of other work disturbed, where a warranted repair requires them.
16.5 A repaired or replaced valve shall carry a warranty running for a full new term from the date the repair is accepted, or for the remainder of the original term, whichever ends later.
16.6 Manufacturer warranties on the valves shall be assigned to the Owner and shall run from the date of substantial completion.
17 Spare Parts
17.1 The Contractor shall furnish the following spare parts, delivered to the Owner before substantial completion:
- One shaft seal set for each valve size furnished
- One cover gasket for each valve size furnished
- Two operating keys of a length to reach the deepest buried operating nut, where buried valves are furnished
- Two portable wrenches for each lever operator size furnished
- One grease charge for each worm-gear operator size furnished
Spare Parts Furnishedcheckbox
☑ Shaft seal set per valve size
☑ Cover gasket per valve size
☑ Operating keys for buried valves
☐ Portable wrenches per lever operator size
☐ Grease charge per worm-gear operator size
17.2 Spare parts shall be the products of the valve manufacturer, packaged, labeled with the valve size and model they serve, and listed on a receipt signed by the Owner's representative.