Exterior and Site Lighting

Revision 3 · SynC Standards Team — SynC Platform Team, SynC (SynC Platform Team / Platform Standards) ✓ Official · Jun 1, 2026 +1 −1

Replace accented Latin characters with ASCII equivalents (facade, 3-phase)
Showing changes from Rev 2 to Rev 3 in Exterior and Site Lighting.
---
title: Exterior and Site Lighting
554 unchanged lines
## Control Zoning
Control zones shall be arranged so that lighting can be reduced or switched by area according to occupancy and use, and the zone boundaries and assignments shall be [[drawing: as indicated on the lighting control plan]]. Façade, signage, and decorative lighting shall be on separate control from functional area lighting so that the energy-code curfew and shutoff requirements can be applied to each independently.
+Control zones shall be arranged so that lighting can be reduced or switched by area according to occupancy and use, and the zone boundaries and assignments shall be [[drawing: as indicated on the lighting control plan]]. Facade, signage, and decorative lighting shall be on separate control from functional area lighting so that the energy-code curfew and shutoff requirements can be applied to each independently.
# Surge Protection
155 unchanged lines
Spare parts shall match the type, rating, CCT, and distribution of the installed equipment so that a replacement is photometrically and visually consistent with its neighbors. Touch-up coating matched to each finish shall be provided so that field repairs to scratched poles and luminaires do not leave a visible or corroding mark.