Fire Pump Controllers

Rev 1 · Updated Jun 13, 2026 · View history

Build a datasheet from this standard Start a project with this standard already attached — one click, no setup.
Use in a project

1 Scope

1.1This Section covers listed controllers for stationary fire pumps, including electric-motor-driven controllers, diesel-engine-driven controllers, and combination controller/power-transfer-switch units, complete with enclosure, sensing, alarm interface, and automatic test provisions.
1.2The controller shall be furnished as a factory-assembled, factory-tested, listed unit matched to the pump driver, motor horsepower, and available power supply at the point of installation.
NOTE The fire pump driver, casing, impeller, and pump assembly are specified in Fire Pumps and are outside this Section. (1.3)
NOTE Aboveground and underground fire protection piping, check valves, OS&Y valves, flow switches, and pressure gauges are specified in Fire Protection Piping and Underground Fire Service Mains. (1.4)
NOTE Feeder conductors, raceway, and overcurrent protective devices upstream of the controller line terminals are specified in Common Work Results Electrical; the fire pump motor is specified in Electric Motors. (1.5)
NOTE The jockey (pressure maintenance) pump controller is a separate listed product category and is not a listed fire pump controller under UL 218. (1.6)
1.7Where a jockey pump controller is furnished, it shall be coordinated with the main fire pump controller but specified independently.

2 Referenced Standards

2.1Equipment, materials, and installation shall comply with the latest adopted edition of each of the following unless a specific edition is cited or a more recent edition is required by the Authority Having Jurisdiction.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
Standard Title
NFPA 20 Standard for the Installation of Stationary Pumps for Fire Protection
UL 218 Fire Pump Controllers
NFPA 70 National Electrical Code (Article 695, Fire Pumps)
NFPA 72 National Fire Alarm and Signaling Code
UL 1008 Transfer Switch Equipment
NEMA ICS 14 Application Guide for Electric Power Converters
IEEE 141 Recommended Practice for Electric Power Distribution for Industrial Plants (Red Book)
CSA C22.2 No. 263 Fire Pump Controllers (tri-national, with UL 218 / NMX-J-626-ANCE)
NOTE The 2025 edition of NFPA 20 expanded automatic and remote testing requirements for both electric and diesel controllers; specifications written to the 2019 or earlier edition shall be reviewed and updated to the currently adopted edition before procurement. (2.3)

3 Submittals

3.1The Contractor shall submit the following action submittals for review before fabrication or procurement:
  • Product data for the controller, including listing marks, voltage and horsepower rating, enclosure type, short-circuit current rating, and method of starting.
  • Shop drawings showing enclosure dimensions, line and load terminal arrangement, control wiring, alarm and supervisory contact assignments, and field connection points.
  • Wiring diagrams (point-to-point and schematic) distinguishing factory and field wiring.
  • Manufacturer's listing documentation confirming UL 218 (and UL 1008 where a transfer switch is integral) compliance.
  • Power-supply coordination data, including available fault current at the controller and the controller short-circuit current rating, with supporting study reference.
Action Submittalscheckbox
Product data (rating, enclosure, SCCR, starting method)
Shop drawings (enclosure, terminals, control wiring)
Wiring diagrams (factory vs. field)
Listing documentation (UL 218 / UL 1008)
Power-supply / fault-current coordination data
3.2The Contractor shall submit the following informational submittals:
  • Field acceptance test report per NFPA 20, including the controller functional test and the pump churn/flow test witnessed by the Authority Having Jurisdiction.
  • Manufacturer's certified factory test report confirming UL 218 production-line testing.
  • Coordination record confirming the quantity and assignment of supervisory output contacts agreed with the fire alarm contractor.
Informational Submittalscheckbox
Field acceptance test report (NFPA 20)
Factory test report (UL 218)
Alarm-contact coordination record
3.3The Contractor shall submit the following closeout submittals:
  • Operation and maintenance manuals, including the manufacturer's weekly and annual test procedures.
  • Settings record listing the as-commissioned pressure setpoints, timer settings, and alarm assignments.
  • Warranty documentation.
Closeout Submittalscheckbox
Operation and maintenance manuals
As-commissioned settings record
Warranty documentation

4 Quality Assurance

4.1The controller shall bear the listing mark of a Nationally Recognized Testing Laboratory under UL 218 for the specific type, voltage, and horsepower furnished.
NOTE A non-listed general-purpose motor controller, soft-starter, or transfer switch shall not be substituted for a listed fire pump controller. (4.2)
NOTE Substituting a non-listed motor controller is a common value-engineering proposal; it will be rejected by the Authority Having Jurisdiction and the property insurance carrier, and it voids the fire pump system listing. (4.3)
4.4The controller manufacturer shall be regularly engaged in the production of listed fire pump controllers and shall provide field service support within the project region.
4.5Where the controller includes an integral automatic transfer switch, the transfer switch portion shall be listed under UL 1008 and the combined unit shall be listed under UL 218 as a combination controller/power-transfer-switch.
4.6The controller short-circuit current rating shall equal or exceed the available fault current at the point of installation, as determined by the project short-circuit study.
NOTE Generator-fed systems can present unexpectedly high X/R ratios; the available fault current used to verify the controller short-circuit current rating shall reflect both the utility source and the alternate (generator) source. (4.7)

5 Power Supply and NEC Article 695 Compliance

5.1The controller and its power supply arrangement shall comply with NFPA 70 (NEC) Article 695 for disconnecting means, overcurrent protection, conductor sizing, voltage drop, and source separation.
5.2The fire pump branch-circuit overcurrent device shall be sized to carry the locked-rotor current indefinitely and shall not open within 2 minutes at 600% of the motor full-load current.
5.3Fire pump branch-circuit conductors shall be sized at not less than 125% of the motor full-load current.
5.4Voltage at the controller line terminals shall not drop more than 15% below the controller-rated voltage during motor starting under locked-rotor conditions.
5.5Voltage at the motor terminals shall not drop more than 5% below the motor-rated voltage when the motor is running at 115% of full-load current.
NOTE A fire pump fed from a transformer shared with other large motor loads can satisfy a steady-state voltage study yet fail the 15% starting limit; the starting voltage drop shall be evaluated at the fire pump locked-rotor condition, not at normal building load. (5.6)
5.7Where two power sources are provided, the normal and alternate source conductors shall be routed with physical separation in accordance with NEC 695.6(B) so that a single fault, fire, or physical event cannot disable both sources.
NOTE Routing normal and alternate power conduits through the same raceway or the same portion of the building defeats the redundant-source requirement and is a frequent field error; the two sources shall maintain independent routing. (5.8)
5.9The available fault current at the controller and the controller short-circuit current rating shall be coordinated with the Engineer of Record before procurement.
Service Voltage and Phaseselect
208 V, 3Φ
240 V, 3Φ
480 V, 3Φ
600 V, 3Φ
2400 V, 3Φ (medium voltage)
4160 V, 3Φ (medium voltage)
Power Supply Arrangementradio
Single utility source
Utility normal + generator alternate
Utility normal + separate utility alternate feeder
Controller Short-Circuit Current Rating (SCCR)range
kA
25200
Default: 65 kA

6 Controller Type and Method of Starting

6.1The controller type and method of starting shall match the pump driver and the horsepower and voltage of the motor as scheduled.
NOTE Across-the-line (full-voltage) starting is the default electric method; it is the simplest, most reliable arrangement and is acceptable where the resulting inrush does not exceed the 15% starting voltage-drop limit at the line terminals. (6.2)
NOTE Reduced-inrush starting (wye-delta, part-winding, or solid-state soft-start) is used where full-voltage inrush would violate the starting voltage-drop limit or exceed the capacity of the supply; it limits inrush current at the cost of added components. (6.3)
NOTE Variable-speed (VFD) controllers listed under UL 218 maintain a constant discharge pressure across a range of flow and require an inverter-duty rated motor. (6.4)
6.5A VFD fire pump controller shall be coordinated with Electric Motors to confirm inverter-duty motor selection.
6.6A limited-service controller may be used only for an across-the-line, squirrel-cage motor rated 30 hp or less at 600 V or less, and only where accepted by the Authority Having Jurisdiction.
NOTE A limited-service controller shall not be used for high-rise buildings or high-hazard occupancies. (6.7)
6.8The controller horsepower and voltage rating shall equal or exceed the pump motor nameplate horsepower and voltage.
NOTE Specifying a controller horsepower or voltage that does not match the motor nameplate forces a custom or substitute unit and generates avoidable requests for information. (6.9)
6.10The controller horsepower and voltage rating shall be verified against the final motor nameplate before the controller is released for procurement.
Pump Driver Typeradio
Electric motor
Diesel engine
Electric Controller Starting Methodradio
Across-the-line (full voltage)
Wye-delta (reduced inrush)
Part-winding (reduced inrush)
Solid-state reduced voltage (soft-start)
Variable speed (VFD, UL 218)
Limited service (across-the-line, ≤30 hp)
Motor Horsepower Ratingrange
hp
5500
Default: 100 hp

7 Diesel Engine Controllers

7.1A diesel engine controller shall be a listed unit providing automatic and manual engine start, dual-battery management, integral battery chargers, and the alarm and supervisory functions required by NFPA 20.
7.2The controller shall provide two independent battery banks, each sized to provide a minimum of six complete engine start attempts.
7.3Each battery bank shall be served by a dedicated integral battery charger matched to the engine manufacturer's battery specification.
NOTE The diesel controller battery charger and cable sizing shall be coordinated with the engine manufacturer; a mismatch between the controller charger and the engine OEM battery specification causes start failures and is a frequent field problem. (7.4)
7.5The controller shall initiate the automatic weekly test cycle and shall record the engine run for the documented test duration.
Diesel Battery System Voltageradio
12 V DC
24 V DC
Engine Start Attempts per Battery Bankrange
starts
612
Default: 6 starts

8 Pressure Sensing and Start/Stop Control

8.1The controller shall sense system pressure through a dedicated sensing line connected to a stable point on the pump discharge header and shall start the pump automatically on a pressure drop below the start setpoint.
8.2The pressure sensing line shall be connected at a stable static point on the pump discharge header, not at a location subject to water hammer or surge.
NOTE A sensing line tapped at a surge-prone point produces nuisance starts and controller fault alarms. (8.3)
8.4The sensing-line tap location shall be selected to read stable static pressure, away from locations subject to water hammer or surge.
8.5The pump start setpoint shall be set below the system residual (no-flow) pressure by the margin established by the Engineer of Record, typically 10 psi.
8.6The controller shall be configured for manual stop unless automatic stop on pressure recovery is specifically accepted in writing by the Authority Having Jurisdiction.
NOTE NFPA 20 generally requires that the pump not stop automatically on pressure recovery, and many Authorities Having Jurisdiction reject automatic-stop configurations. (8.7)
8.8The pump stop mode shall be confirmed with the Authority Having Jurisdiction early in design before the controller is specified.
8.9The pump start location on the drawings shall be coordinated with the sensing-line connection point pump discharge header sensing tap.
Pump Stop Moderadio
Manual stop only
Automatic stop on pressure recovery (AHJ approval required)
Pump Start Pressure Setpointrange
psi
10175
Default: 100 psi
Start Setpoint Margin Below System Residual Pressurerange
psi
525
Default: 10 psi

9 Automatic Transfer Switch Provisions

9.1Where a generator serves as the alternate power source, the controller shall include either an integral listed automatic transfer switch or be paired with a separate listed fire pump power transfer switch.
9.2The transfer switch furnished for fire pump service shall be listed under UL 1008 and, where integral, the combined unit shall be listed under UL 218; a general-purpose transfer switch not listed for fire pump service shall not be used.
NOTE Omitting the transfer switch from the controller specification when a generator is the alternate source, or substituting a general power transfer switch, is non-compliant with NFPA 20 and is a common scope gap. (9.3)
9.4The transfer switch arrangement shall be defined in the controller specification where a generator serves as the alternate power source.
9.5The transfer switch shall sense loss of the normal source, transfer the controller to the alternate source, and retransfer to the normal source on its restoration, in the sequence required by NFPA 20.
Transfer Switch Provisionradio
None (single source)
Integral combination controller/ATS (UL 218 + UL 1008)
Separate listed fire pump power transfer switch

10 Alarm and Supervisory Interface

10.1The controller shall provide dry-contact alarm and supervisory outputs for interface with the fire alarm and building automation systems in accordance with NFPA 72 Chapter 17 and NFPA 20.
10.2Each alarm and supervisory output shall be a dry contact rated for not less than 0.5 A at 24 V DC.
10.3The quantity, type, and labeling of supervisory output contacts shall be coordinated with the fire alarm contractor's input module schedule before procurement.
NOTE Failing to coordinate the contact count and type with the fire alarm contractor results in field wiring changes and fire alarm panel reprogramming. (10.4)
10.5The alarm-contact coordination record shall be completed and accepted before the controller is released for procurement.
10.6At a minimum, the controller shall provide supervisory outputs for pump running, phase reversal or loss, loss of power or transfer to alternate source, low suction pressure, high pump room temperature, and controller trouble.
Supervisory Output Contacts Requiredcheckbox
Pump running
Phase reversal / phase loss
Power loss / transfer to alternate source
Low suction pressure
High pump room temperature
Controller trouble
Alarm Contact Formselect
SPDT (Form C)
DPDT (Form CC)

11 Enclosure and Environmental Conditions

11.1The controller enclosure shall be selected for the installed environment and shall provide not less than NEMA Type 2 protection for indoor or damp locations as required by NFPA 20.
11.2A NEMA Type 3R enclosure shall be provided for outdoor or unconditioned locations, and a NEMA Type 4 or 4X enclosure shall be provided for wash-down or corrosive environments.
NOTE Specifying a NEMA 2 enclosure in an outdoor pump house or a location subject to hose-down is a frequent error; the actual installed environment often exceeds the NFPA 20 minimum. (11.3)
11.4The controller enclosure rating shall be matched to the actual installed environment and shall meet or exceed the NFPA 20 minimum rating for that environment.
11.5The pump room ambient temperature and ventilation shall be maintained within the controller manufacturer's listed operating range.
11.6The controller mounting location and orientation shall be coordinated with the pump room layout fire pump room controller location.
Enclosure Typeselect
NEMA 2 (indoor / damp)
NEMA 3R (outdoor)
NEMA 4 (wash-down)
NEMA 4X (corrosive)

12 Testing

12.1The controller shall provide automatic weekly test capability with local audible and visual indication, and shall support the remote and automatic test provisions required by the currently adopted edition of NFPA 20.
12.2The controller shall be capable of an automatic weekly test of not less than 10 minutes run duration, with the test recorded for documentation.
12.3A factory production-line test of all controller functions shall be performed under UL 218 before shipment, and the certified factory test report shall be provided.
12.4A field acceptance test shall be performed in accordance with NFPA 20 Section 14.2, witnessed by the Authority Having Jurisdiction, and shall include the controller functional test and the pump flow test.
12.5The as-commissioned pressure setpoints, timer settings, and alarm assignments shall be recorded and submitted following the field acceptance test.
Automatic Weekly Test Run Durationrange
min
1030
Default: 10 min
Remote Automatic Test Capabilityradio
Local automatic test only
Local plus remote automatic test (NFPA 20-2025)

13 Installation

13.1The controller shall be installed in accordance with the manufacturer's listed instructions, NFPA 20, and NEC Article 695.
13.2The controller shall be located within sight of the fire pump driver, in the fire pump room, and mounted so the line and load terminals are accessible for service.
13.3Field wiring shall be terminated only at the controller terminals designated for field connection on the approved wiring diagrams, and factory wiring shall not be altered.
13.4The pressure sensing line shall be installed with the isolation and test fittings required by NFPA 20 and shall be connected to the discharge header tap.
13.5Supervisory output wiring to the fire alarm and building automation systems shall be installed per the coordinated contact schedule and supervised in accordance with NFPA 72.
13.6The controller shall be grounded in accordance with NEC Article 695 and the manufacturer's instructions.

14 Delivery, Storage, and Handling

14.1The controller shall be delivered factory-assembled and factory-tested in protective packaging bearing the listing marks and rating data.
14.2The controller shall be stored indoors in a clean, dry, conditioned space and protected from moisture, dust, and physical damage until installation.
NOTE A controller exposed to moisture or contamination during storage shall be inspected and, where required by the manufacturer, reconditioned or replaced before energization. (14.3)
14.4The controller shall be handled and rigged using the manufacturer's designated lifting provisions to avoid damage to the enclosure and internal components.

15 Warranty

15.1The manufacturer shall warrant the controller against defects in materials and workmanship for a period of not less than 1 year from the date of substantial completion.
15.2The warranty shall include parts and field service labor for repair or replacement of defective components.
15.3Where an integral transfer switch is furnished, the warranty shall cover the complete combination controller/transfer-switch unit as a single assembly.
Warranty Periodrange
years
15
Default: 1 years

16 Spare Parts

16.2A complete record of as-commissioned settings shall be retained with the spare parts and operation and maintenance documentation to support future service.
Spare Parts Packagecheckbox
Indicating lamps / LEDs
Control fuses
Spare batteries (diesel controllers)
Spare control relay(s)

Edit this page

SynC Standards are reference material provided for informational purposes only and as a guide. They are not engineering, architectural, or legal advice and are not a substitute for the judgment of a licensed design professional. It is the responsibility of the user to determine the applicability of any standard to a specific project and to verify all requirements against the governing codes, manufacturer data, and project conditions. SynC does not render professional services and forms no professional relationship by publishing this content. Provided "as is," without warranty of any kind, including fitness for a particular purpose. See our Terms of Use for the complete terms.

This standard is published by SynC and licensed under Creative Commons Attribution-ShareAlike 4.0. You may share and adapt it, including commercially, provided you give credit, link to the license, indicate any changes, and license your adaptations under the same terms. Keep the attribution and notice below with any copy — it includes the warranty disclaimer the license requires you to retain.

Attribution & reuse notice — keep this with any copy:
"Fire Pump Controllers." SynC Standards. Licensed under CC BY-SA 4.0 (https://creativecommons.org/licenses/by-sa/4.0/). Source: https://synergyinconstruction.com/wiki/sync/fire-pump-controllers — reference material only; not professional engineering advice and provided without warranty. Verify against governing codes and have a licensed professional review before use.