1.1This standard governs the selection, documentation, and field verification of building assemblies that carry a code-required hourly fire-resistance rating.
NOTEThis standard applies to every assembly that IBC Chapter 7 requires to resist the passage of fire and heat for a rated duration: walls, partitions, floor-ceiling assemblies, roof-ceiling assemblies, columns, beams, and structural frame members. (1.1.1)
NOTEThe governing rating for an assembly may originate from any of several code provisions, and the same physical wall can be subject to more than one at once. (1.1.2)
NOTEThe hourly rating may be set by the construction-type minimums of IBC Table 601, the exterior-wall separation requirements of Table 602, an occupancy separation under Section 707, a corridor under Section 1020, a shaft enclosure under Section 713, or a fire wall, fire barrier, or fire partition designation. Where two provisions apply to the same element, the more stringent rating governs. (1.1.3)
NOTEThis standard is the master coordination layer: it selects the tested assembly, cites the governing design number, and delegates material installation to the discipline standards. (1.1.4)
NOTEThe work of furring, fastening, and finishing a rated gypsum partition belongs to Gypsum Board AssembliesGypsum Board AssembliesResolves to the current edition.sync/gypsum-board-assemblies; shaft-wall system materials to Gypsum Shaft Wall AssembliesGypsum Shaft Wall AssembliesResolves to the current edition.sync/gypsum-shaft-wall-assemblies; spray-applied fireproofing on structural steel to FireproofingApplied FireproofingResolves to the current edition.sync/fireproofing; and restoration of the rating at penetrations and joints to FirestoppingFirestoppingResolves to the current edition.sync/firestopping. This standard establishes which tested assembly is required and how its rating is documented and verified. (1.1.5)
1.1.6Fire-resistance-rated assemblies shall be selected and documented for every project on which the construction type, occupancy separation, corridor protection, shaft enclosure, or fire wall, fire barrier, or fire partition designation imposes a minimum hourly rating.
1.1.7The required rating, the assembly classification, and the specific tested design number for each rated assembly shall be shown on the Contract Documents.
NOTEThis standard is not intended for the material installation of gypsum partitions, shaft walls, ceilings, fireproofing, firestopping, rated doors, or dampers, each of which is governed by its own SynC standard. (1.1.8)
2Referenced Standards
2.1Assemblies, materials, and documentation shall comply with the latest adopted edition of each of the following unless a specific edition is cited or adopted by the Authority Having Jurisdiction.
2.2Where referenced standards or code provisions conflict, the more stringent requirement shall govern unless the Authority Having Jurisdiction or the Engineer of Record directs otherwise in writing.
Standard
Title
ASTM E119
Standard Test Methods for Fire Tests of Building Construction and Materials
UL 263
Fire Resistance of Building and Construction Materials
ASTM E84
Standard Test Method for Surface Burning Characteristics of Building Materials
IBC Chapter 7
International Building Code — Fire and Smoke Protection Features
IBC Table 601
Fire-Resistance Rating Requirements for Building Elements
IBC Table 602
Fire-Resistance Rating Requirements for Exterior Walls Based on Fire Separation Distance
IBC Section 703
Fire-Resistance Ratings and Fire Tests
IBC Section 707
Fire Barriers
IBC Section 708
Fire Partitions
IBC Section 713
Shaft Enclosures
IBC Section 1020
Corridors
NFPA 101
Life Safety Code
NFPA 5000
Building Construction and Safety Code
GA-600
Fire Resistance and Sound Control Design Manual (Gypsum Association)
GA-216
Application and Finishing of Gypsum Panel Products (Gypsum Association)
UL Fire Resistance Directory
UL Fire Resistance Directory (online, continuously updated)
ICC-ES AC23
Acceptance Criteria for Spray-Applied Fire-Resistive Materials
NOTENFPA 251 was withdrawn in 2010 and shall not be referenced; the current fire-resistance test standards are ASTM E119 and UL 263, both accepted by IBC Section 703.2. (2.2.1)
NOTEGA-600 is a design resource that catalogs tested gypsum assemblies; it is not itself a test standard. (2.2.2)
NOTEIt is published by the Gypsum Association and provides fire-resistance and sound-rated designs (WP-series numbers) usable as an alternative to UL listings where the IBC accepts gypsum association designs. (2.2.3)
3Selection of the Governing Rating
3.1The rating required for each assembly is derived from the code provision that applies to that element, not assumed by analogy to other walls on the project.
NOTEConstruction type fixes the baseline ratings for structural and enclosure elements. (3.1.1)
NOTEIBC Table 601 sets minimum hourly ratings for the structural frame, floor construction, roof construction, and bearing walls by construction type from Type I-A through Type V-B. These ratings have been stable across the 2018, 2021, and 2024 IBC editions. Type I-A imposes a 3-hour structural frame and 2-hour floors; Type I-B imposes 2-hour frame and floors; Types II-A, III-A, IV-HT, and V-A impose 1-hour frame, floor, and roof; Types II-B, III-B, and V-B impose no rating on these elements. (3.1.2)
3.1.3The construction type for the project shall be established from the Contract Documents before any assembly rating is selected.
Construction Type (IBC Table 601)select
Type I-A
Type I-B
Type II-A
Type II-B
Type III-A
Type III-B
Type IV-HT
Type V-A
Type V-B
NOTETable 601 ratings are minimums and may be exceeded by other provisions or local amendments; the Authority Having Jurisdiction may require a higher rating based on occupancy separation, mixed-use conditions, or local code amendments. (3.1.4)
3.1.5The governing rating shall always be confirmed with the Authority Having Jurisdiction before being locked onto the Contract Documents.
NOTEEach rated assembly shall be classified as a fire wall, fire barrier, fire partition, horizontal assembly, or shaft enclosure, because continuity and opening-protection rules differ by classification. (3.1.6)
Assembly Classificationselect
Fire wall (IBC 706)
Fire barrier (IBC 707)
Fire partition (IBC 708)
Horizontal assembly (IBC 711)
Shaft enclosure (IBC 713)
Exterior wall (IBC Table 602)
Structural frame member (IBC Table 601)
3.1.7The required hourly rating for each assembly shall be selected from the code section applicable to that element.
Required Hourly Fire-Resistance Ratingselect
20-minute
1-hour
2-hour
3-hour
4-hour
NOTEOne-hour is the default for most commercial interiors, but it is a starting point, not a substitute for the code analysis. (3.1.8)
NOTEOne-hour ratings govern fire partitions under Section 708, shaft walls connecting fewer than four stories, and the floor and roof of Type II-A, III-A, and V-A construction. Two-hour ratings govern occupancy separations under Section 707 and shaft walls connecting four or more stories. Three-hour and four-hour ratings are reserved for fire walls and for the structural frame and floors of Type I-A construction. (3.1.9)
3.2Corridor and Shaft Rules
NOTEIn a fully sprinklered building, corridor walls for most occupancies require no fire-resistance rating. (3.2.1)
NOTEIBC Section 1020 requires 0 hours for corridor walls in fully sprinklered Group A, B, E, F, M, S, and U occupancies, and 1 hour in non-sprinklered buildings and in Group I-2 and I-3 occupancies regardless of sprinklers. The 80-percent case in modern fully-sprinklered commercial work is a 0-hour corridor, which still must satisfy smoke-partition continuity even though it carries no fire-resistance rating. (3.2.2)
Building Sprinkler Statusradio
● Fully sprinklered (NFPA 13)
○ Not fully sprinklered
3.2.3Corridor wall ratings shall be confirmed against the building's sprinkler status before any corridor wall is designated as rated.
NOTERating inflation on the drawings shall be avoided; an assembly shall not be labeled rated where the governing code section requires no rating. (3.2.4)
NOTELabeling every corridor 1-hour in a fully sprinklered building where Section 1020 requires 0 hours needlessly raises cost and forces firestopping coordination at every conduit, pipe, and cable penetration that crosses the wall. (3.2.5)
3.2.6Shaft enclosure ratings shall follow IBC Section 713.4 based on the number of stories the shaft connects.
NOTEA shaft connecting fewer than four stories requires a minimum 1-hour enclosure; a shaft connecting four or more stories requires a minimum 2-hour enclosure. (3.2.7)
Shaft Enclosure Rating Basis (IBC 713.4)radio
● Shaft connects fewer than 4 stories — 1-hour
○ Shaft connects 4 or more stories — 2-hour
NOTEThe sprinkler substitution that reduces a 2-hour separation to 1-hour does not apply universally. (3.2.8)
NOTEIBC Section 707.3.10 permits substituting a 1-hour fire barrier for a 2-hour occupancy separation in a fully sprinklered building, but the substitution does not apply to corridors in Group I-2, and it never applies to fire walls. The substitution shall not be applied to fire walls or to Group I-2 corridors. (3.2.9)
4Assembly Test Basis and Design Number
4.1A rated assembly is established by a specific tested design, and the design number is the contractual instrument that defines it.
NOTEFire-resistance ratings are established by furnace testing to a standard time-temperature curve. (4.1.1)
NOTEASTM E119 and the UL-owned equivalent UL 263 expose a full-scale assembly to the standard time-temperature curve for the rated duration — 1, 2, 3, or 4 hours. For walls and partitions rated 1-hour and above, a hose-stream test is applied after the fire exposure; floor-ceiling assemblies are not typically subject to the hose stream. (4.1.2)
4.1.3Each rated assembly shall be constructed to a specific tested design listed in the UL Fire Resistance Directory or GA-600, or to a calculated fire resistance per IBC Section 722, or to an alternative protection method approved under IBC Section 104.2.3.
4.1.5The design number shall be recorded in the assembly schedule for each rated assembly.
Cited Design Numbertext
Enter value...
Per drawings — fire-rated assembly schedule
NOTEA rating specified without a design number invites substitution and generates RFIs. (4.1.6)
NOTEA note on the drawings that reads only "1-hour fire-rated" leaves the contractor free to select any listed design, which may carry different stud gauges, board counts, or framing requirements than the architect assumed. The design number removes that ambiguity. (4.1.7)
NOTEUL design numbers are organized by a prefix that identifies the element type, which the specifier shall use to confirm the design matches the element being rated. (4.1.8)
NOTEThe prefix groups are: U, V, and W for walls and partitions; L for floor-ceiling assemblies; P for roof-ceiling assemblies; J for beams; X for columns; and D for composite assemblies. Selecting an L-series design for a wall, or a U-series design for a floor, is a fundamental misapplication. (4.1.9)
NOTEThe UL Fire Resistance Directory is online and continuously updated; the cited design shall be confirmed current at the time of construction. (4.1.10)
NOTEListings are revised and occasionally withdrawn. The directory at the UL online product database is the authoritative source, and a design number copied from an old project may no longer be valid. (4.1.11)
5Assembly Material Family and Configuration
5.1The material family of the rated assembly determines which tested designs are available and which discipline standard governs installation.
5.1.1The assembly material family shall be selected to match the tested design, because each family follows a different installation standard.
Assembly Material Familyselect
Gypsum board on steel framing
Gypsum shaft-wall system
Concrete masonry unit (CMU)
Cast-in-place or precast concrete
Composite steel deck and beam with spray fireproofing
NOTEGypsum-board-framed assemblies are the most common interior rated construction, and their rating is sensitive to every component. (5.1.2)
NOTEThe achieved rating depends on the stud gauge and spacing, the number and type of board layers, the board thickness, the fastener schedule, and any cavity insulation. Changing any one of these from the tested design can invalidate the rating or move the assembly to a different design number. (5.1.3)
NOTEFraming gauge and spacing shall match the tested design number; substituting a lighter or wider-spaced stud changes the applicable design and may reduce the rating. (5.1.4)
Steel Stud Gauge and Spacing (per cited UL design)select
20-gauge at 16 in. o.c.
20-gauge at 24 in. o.c.
25-gauge at 16 in. o.c.
25-gauge at 24 in. o.c.
5.1.5Board layer count, type, and thickness shall match the tested design number.
Gypsum Board Configuration (per cited UL design)select
Single layer 5/8 in. Type X each face
Double layer 5/8 in. Type X each face
Single layer 5/8 in. Type C each face
Double layer 5/8 in. Type C each face
NOTEA 5/8-inch Type X board layer contributes roughly 30 minutes of fire resistance per layer per side, but the exact contribution shall be taken only from the cited design. (5.1.6)
NOTEThis rule of thumb explains why most 1-hour partitions use a single layer each face and most 2-hour partitions use a double layer, but it is a heuristic only — the specific tested construction, not the heuristic, establishes the rating. (5.1.7)
5.1.8Where cavity insulation is part of the tested design, its presence, type, and thickness shall match that design.
NOTEInsulation affects both fire-resistance and acoustic performance in many UL and GA designs; substituting or omitting it can invalidate the listed rating. (5.1.9)
Cavity Insulation (per cited design)select
None (per design)
Mineral wool batt
Glass-fiber batt
NOTENon-symmetrical assemblies require a design that covers the exact two-sided configuration. (5.1.10)
NOTEA wall finished differently on each face — gypsum board on one side and brick veneer, tile backer, or masonry on the other — shall be constructed to a UL design that lists that exact configuration, or to a separate engineering judgment from a qualified party. A symmetrical design number does not cover a non-symmetrical wall. (5.1.11)
5.2Common Rated Configurations
NOTEThe following configurations represent the assemblies most frequently specified in commercial construction; the cited design number always governs the exact construction. (5.2.1)
1-hour steel-stud gypsum partition: 3-5/8 in. 20-gauge studs at 24 in. o.c., single layer 5/8 in. Type X each face — the most common interior fire partition.
2-hour steel-stud gypsum partition: 3-5/8 in. 20-gauge studs, double layer 5/8 in. Type X each face — standard corridor and occupancy-separation wall in higher-rated conditions.
1-hour shaft wall: 1 in. coreboard or E-stud system with Type X board — standard vertical shaft enclosure under four stories.
2-hour shaft wall: double-layer Type X on E-stud chassis or solid coreboard — for four-or-more-story shafts per IBC 713.
1-hour CMU bearing wall: 6 in. normal-weight CMU, ungrouted, no additional protection at most densities.
2-hour CMU: 8 in. normal-weight CMU or solid-grouted lighter units.
1-hour composite floor-ceiling: steel beam and deck with spray fireproofing, ubiquitous in Type II-B floors.
2-hour composite floor: deck-and-beam with SFRM thickness set by the beam W/D ratio, common in Type I-B high-rise.
2-hour fire wall: structurally independent masonry or concrete, continuous through the roof.
NOTEComposite floor-ceiling and structural-frame ratings depend on spray-applied fireproofing whose thickness is set by the structural member, requiring coordination with the structural drawings. (5.2.2)
NOTEThe SFRM thickness for a composite beam-and-deck floor is governed by the W/D ratio (weight-to-heated-perimeter) of the specific beam section in the cited UL design. The structural engineer must provide the beam sizes, and the fireproofing specification under FireproofingApplied FireproofingResolves to the current edition.sync/fireproofing must coordinate to those sizes. Specifying the rating without coordinating the framing produces field conflicts. (5.2.3)
6Continuity and Opening Protectives
6.1A rated assembly performs only if it is continuous and its openings are protected; both are part of the rating, not afterthoughts.
6.1.1Fire barriers and fire partitions shall extend from the floor to the underside of the structural deck above, or to a fire-rated floor-ceiling assembly above.
6.1.2Fire barriers and fire partitions shall be continuous through concealed spaces, including plenums and interstitial spaces.
NOTEStopping a rated partition at the acoustic-tile ceiling is a common and serious code violation. (6.1.3)
NOTEIBC Sections 707.5 and 708.4 require continuity to the deck or to a rated horizontal assembly above. A 1-hour partition that dies at the lay-in ceiling provides no rated separation in the plenum and is routinely flagged during inspection. (6.1.4)
6.1.5Openings in a rated assembly shall be protected by opening protectives whose rating corresponds to the assembly rating per IBC Table 716.1.
NOTEA 1-hour barrier requires a 3/4-hour door; a 2-hour barrier requires a 1.5-hour door; a 3-hour barrier requires a 3-hour door or shutter; a 20-minute partition requires a 20-minute door. (6.1.6)
Opening Protective Rating (IBC Table 716.1)select
20-minute door (in 20-minute partition)
3/4-hour door (in 1-hour barrier)
1.5-hour door (in 2-hour barrier)
3-hour door or shutter (in 3-hour barrier)
NOTEOpening protectives — rated doors, frames, glazing, and dampers — are governed by their own standards and shall be coordinated, not specified here. (6.1.7)
NOTERated door, frame, and hardware assemblies are governed by Doors Frames And HardwareDoors, Frames, and HardwareResolves to the current edition.sync/doors-frames-and-hardware; fire and combination fire/smoke dampers in rated duct penetrations are governed by HVAC DuctworkHVAC DuctworkResolves to the current edition.sync/hvac-ductwork. This standard establishes the required opening-protective rating; those standards establish the products. (6.1.8)
NOTEThe gap between the top track and the structural deck is not part of the wall design and requires a separate fire-resistive joint system. (6.1.9)
NOTEThe head-of-wall joint between a rated wall and the deck above is a movement joint that a UL wall design does not cover. It requires a tested fire-resistive joint system per UL 2079, governed by FirestoppingFirestoppingResolves to the current edition.sync/firestopping. Specifiers routinely omit this and the firestopping subcontractor inherits unexpected scope. (6.1.10)
6.1.11Through-penetrations of a rated assembly by pipe, conduit, cable, and duct shall be sealed with a tested firestop system that restores the assembly rating, per FirestoppingFirestoppingResolves to the current edition.sync/firestopping.
NOTEThe finish rating of a tested design shall be observed where combustible structural elements are framed within the assembly. (6.1.12)
NOTEA UL design carries both a fire rating and a finish rating; the finish rating is the time before the unexposed face of the protective membrane reaches an average 250°F rise, and it is the life-safety metric that protects combustible framing inside the cavity. Overlooking the finish rating on a wood-framed rated wall is a substitution pitfall. (6.1.13)
7Temperature and Performance Criteria
7.1The rated performance is defined by the failure criteria of the test, which the selected assembly must have demonstrated for the required duration.
NOTEEach rated assembly shall demonstrate the ASTM E119 / UL 263 endpoint criteria for the full required rating duration. (7.1.1)
NOTEThe fire test fails the assembly when the unexposed surface temperature rise, the passage of flame or hot gases, or (for load-bearing assemblies) the loss of structural capacity exceeds the standard limits before the rated time elapses. The selected design number must have passed for at least the required duration. (7.1.2)
7.1.3For protected structural connections, the temperature rise shall not exceed the IBC Section 703.2.3 limits for the duration equal to the required rating of the connected element.
NOTEIBC Section 703.2.3 sets a single fixed limit for protected structural connections: an average temperature rise of 250°F and a maximum temperature rise of 325°F at any point on the unexposed face of the connection. These values are not project-selectable; they apply universally to any assembly whose rating is based on protection of a structural connection. (7.1.4)
7.1.5Materials placed within a rated assembly cavity shall meet the surface-burning requirements of ASTM E84 where required by the IBC for interior finishes and concealed insulation.
Cavity Material Surface-Burning Class (ASTM E84, where required)select
Class A (flame spread ≤ 25, smoke developed ≤ 450)
Class B (flame spread 26–75)
Not applicable (noncombustible)
8Submittals
8.1Action Submittals
8.1.1The Contractor shall submit the following action submittals for each rated assembly before fabrication or installation:
Schedule of all rated assemblies, keyed to the drawings, listing classification, required rating, and the cited design number for each.
The complete tested design listing (UL or GA-600 page) for every cited design number.
Product data confirming each component of the assembly matches the cited design — stud gauge and spacing, board type and thickness, layer count, insulation, and fasteners.
Shop drawings of head-of-wall and intersection conditions identifying the separate fire-resistive joint systems required.
Engineering judgment documentation for any non-listed condition, signed by a qualified party.
8.3.1The Contractor shall submit the following closeout submittals:
Inspection records documenting verification of each rated assembly before concealment.
As-built rated assembly schedule reflecting any approved substitutions and the final design number for each assembly.
Record copies of all engineering judgments and Authority Having Jurisdiction approvals.
Closeout Submittalscheckbox
☐ Pre-concealment inspection records
☐ As-built rated assembly schedule
☐ Engineering judgments and AHJ approvals
9Quality Assurance
9.1Documentation, substitution control, and field verification protect the rating from the gap between what is tested and what is built.
NOTESubstituting any component of a listed assembly invalidates the tested rating unless a revised design number is selected. (9.1.1)
NOTEChanging the gypsum board manufacturer or thickness, the stud gauge, the insulation type, or the fastener schedule from what the listed design specifies breaks the chain of evidence that the assembly will perform. Each component shall match the cited listing, or a different design number that covers the substitution shall be selected and documented. (9.1.2)
9.1.3Any proposed substitution of a listed component shall be submitted as a revised design number with supporting listing documentation, and shall not be made in the field.
9.1.4A qualified party shall prepare an engineering judgment for any rated condition not covered by a published tested design, subject to Authority Having Jurisdiction acceptance.
9.1.5Special inspection of spray-applied fireproofing on structural members shall be performed per IBC Chapter 17, coordinated with Special Inspections And TestingSpecial Inspections and Structural TestingResolves to the current edition.sync/special-inspections-and-testing.
NOTEField verification of SFRM thickness and density shall follow ICC-ES AC23 and the applicable AWCI procedures where spray fireproofing establishes the rating. (9.1.6)
NOTEFor composite floor-ceiling and structural-frame assemblies, the rating depends on the as-applied thickness and density of the SFRM. These are verified in the field against the cited UL design; the installation itself is governed by FireproofingApplied FireproofingResolves to the current edition.sync/fireproofing. (9.1.7)
10Field Verification and Concealment
10.1A rated assembly must be inspected and documented while it is still visible, because concealment hides the components the rating depends on.
10.1.1Rated assemblies shall be inspected and documented before being concealed by drywall, ceiling tile, or other finish, per IBC Section 110.3.4.
NOTEConcealment before inspection is a frequent schedule conflict and a code violation. (10.1.2)
NOTEIBC Section 110.3.4 prohibits covering rated assemblies — especially fireproofing on structural steel — before inspection by the Authority Having Jurisdiction or the special inspector. Framing and finish trades that move quickly often close up walls and ceilings before the inspection hold point is released; this requires the work to be reopened. (10.1.3)
10.1.4Inspection hold points for each rated assembly shall be established in the construction schedule and released in writing before concealment.
Pre-Concealment Inspection Hold Point Requiredradio
● Required for all rated assemblies
○ Required only for structural fireproofing
10.1.5Each rated assembly shall be field-verified against its cited design number for stud gauge and spacing, board layers, fastener schedule, insulation, and continuity to the deck before sign-off.
NOTEThere is no published field-inspection standard specific to rated drywall assemblies; verification relies on the cited design, the Authority Having Jurisdiction's visual inspection, and contractor documentation. (10.1.6)
NOTEUnlike spray fireproofing, which has thickness and density verification procedures, rated gypsum assemblies are confirmed by comparing the as-built construction to the cited listing and recording that comparison. The documentation is the evidence of compliance. (10.1.7)
11Identification and Labeling
11.1A rated assembly that is not labeled cannot be maintained or verified after the building is occupied.
11.1.1Rated walls and barriers shall be permanently identified in concealed spaces above ceilings and in accessible shafts with stenciled or labeled signage stating the assembly rating, per IBC Section 703.7.
☐ Stenciled rating text in plenum and concealed spaces
☐ Markings spaced not more than 30 ft on center
☐ Letters not less than 3 in. high
11.1.2Marking text shall identify the wall as a fire or smoke-resistant assembly and state the hourly rating in a contrasting color legible from the accessible space.
12Coordination with Other Standards
12.1This standard selects and documents the assembly; the installation, protection, and openings are executed under the discipline standards.
12.1.1Installation of rated gypsum partitions, ceilings, and area-separation walls shall be executed under Gypsum Board AssembliesGypsum Board AssembliesResolves to the current edition.sync/gypsum-board-assemblies to the design number cited under this standard.
12.1.2Shaft-wall system materials and installation shall be executed under Gypsum Shaft Wall AssembliesGypsum Shaft Wall AssembliesResolves to the current edition.sync/gypsum-shaft-wall-assemblies.
12.1.3Spray-applied fire-resistive materials on structural steel and concrete shall be executed under FireproofingApplied FireproofingResolves to the current edition.sync/fireproofing to the thickness required by the cited design.
12.1.4Through-penetration firestops and fire-resistive joint systems that restore the rating at openings and gaps shall be executed under FirestoppingFirestoppingResolves to the current edition.sync/firestopping.
NOTECold-formed framing used within rated assemblies shall be designed under Cold Formed Metal FramingCold-Formed Metal FramingResolves to the current edition.sync/cold-formed-metal-framing, and cast-in-place concrete for rated slabs and walls shall be governed by Cast In Place ConcreteCast-in-Place ConcreteResolves to the current edition.sync/cast-in-place-concrete. (12.1.5)
13Warranty
13.1Warranty obligations cover the documentation and installation that this standard controls, not the inherent fire resistance of code-compliant materials.
13.1.1The Contractor shall warrant that each rated assembly was constructed to the cited tested design and that no component was substituted without an approved revised design number, for the project warranty period.
13.1.2Defects in rated-assembly construction discovered during the warranty period — including missing continuity, unprotected openings, or substituted components — shall be corrected at no cost to the Owner.
NOTEThe fire-resistance rating of a code-compliant listed assembly is established by test, not by a manufacturer's warranty; the warranty here covers conformance of construction to the cited design. (13.1.3)