Foam Fire Suppression Systems

Rev 1 · Updated Jun 13, 2026 · View history

1 Scope

NOTE This Section specifies fixed and semi-fixed foam fire suppression systems used to extinguish or control fires involving flammable and combustible liquids. (1.1)
NOTE The systems covered protect a fundamentally different fire than ordinary water-based sprinkler systems. A flammable-liquid fire is extinguished not by cooling but by a stable foam blanket that floats on the fuel surface, excluding oxygen and suppressing the release of flammable vapor. Because the agent, the discharge devices, and the proportioning equipment all differ from water systems, foam suppression is specified as its own discipline. (1.2)
NOTE The work of this Section includes foam concentrate, proportioning equipment, discharge devices, concentrate storage, detection and actuation interfaces, and acceptance testing. (1.3)
NOTE A complete foam system is an assembly of matched components: a listed concentrate, a proportioner that injects that concentrate into the water stream at the correct ratio, piping that carries the solution, and discharge devices that aspirate and apply the finished foam. Substituting any one component without verifying compatibility with the others is the most common source of system failure. (1.4)
NOTE System types covered by this Section. (1.5)
NOTE This Section addresses the following foam system types, each suited to a distinct hazard geometry: (1.6)
  • Low-expansion surface-application systems for atmospheric storage tanks and spill areas.
  • Low-expansion subsurface (base) injection systems for cone-roof storage tanks.
  • Medium-expansion systems for dike and berm protection.
  • High-expansion total-flooding systems for enclosed spaces such as aircraft hangars, engine test cells, pump rooms, and flammable-liquid warehouses.
  • Foam-water sprinkler and foam-water spray (deluge) systems for loading racks, transformer vaults, and mixed occupancies.
NOTE Water-only deluge and pre-action sprinkler systems are not part of this Section. (1.7)
NOTE Deluge valves, releasing panels, and water-only spray coverage are specified in Pre Action And Deluge Sprinkler Systems. Where a foam-water system shares a deluge valve or releasing panel with a water system, that shared hardware is coordinated with that Section. (1.8)
NOTE Gaseous clean-agent total-flooding systems are not part of this Section. (1.9)
NOTE CO2, inert-gas, and halocarbon clean-agent systems are specified in Clean Agent Fire Suppression. Foam and clean agents are not interchangeable; the hazard analysis selects one or the other. (1.10)
NOTE Fire pumps, hydrants, fire department connections, and fuel gas piping are not part of this Section. (1.11)
NOTE Dedicated foam-system water supply pumps, drivers, and controllers are specified in Fire Pumps. Fire hydrants are specified in Fire Hydrants, fire department connections in Fire Department Connections, and fuel gas and LP-gas piping in Fuel Gas Piping. Structural spill-containment dikes and berms are civil/structural scope and are not specified here. (1.12)

2 Referenced Standards

2.1Equipment, materials, installation, and testing shall comply with the latest adopted edition of each of the following unless a specific edition is cited.
2.2Where referenced standards conflict, the more stringent requirement shall govern unless the Engineer of Record directs otherwise in writing.
2.3The Authority Having Jurisdiction (AHJ) and, for FAA-regulated airports, the Federal Aviation Administration shall be consulted to confirm the adopted editions and any local amendments before design is finalized.
NOTE Edition adoption matters more for foam than for most disciplines because NFPA 11 (2021) absorbed most of the former NFPA 16 content into a new Chapter 6, while NFPA 16 (2019) remains independently adopted in some jurisdictions. Designing to NFPA 16 in a jurisdiction that has adopted NFPA 11 Chapter 6 - or the reverse - produces conflicting requirements. Confirm which document governs at project outset. (2.4)
Standard Title
NFPA 11 (2021) Standard for Low-, Medium-, and High-Expansion Foam
NFPA 16 (2019) Standard for the Installation of Foam-Water Sprinkler and Foam-Water Spray Systems
NFPA 30 (2021) Flammable and Combustible Liquids Code
NFPA 409 (2022) Standard on Aircraft Hangars
NFPA 1 (2021) Fire Code
NFPA 72 National Fire Alarm and Signaling Code
UL 162 Foam Equipment and Liquid Concentrates
UL 260 Dry Pipe and Deluge Valves for Fire-Protection Service
MIL-PRF-24385F Fire Extinguishing Agent, Aqueous Film-Forming Foam (AFFF) Liquid Concentrate
FAA AC 150/5210-6E Aircraft Fire and Rescue Facilities and Extinguishing Agents
IBC 2021 International Building Code (Section 904, Alternative Automatic Fire-Extinguishing Systems)

3 PFAS and Foam Concentrate Selection

3.1The foam concentrate type is the single most consequential decision in the system and shall be confirmed against current AHJ and state restrictions before design proceeds.
3.2Any hangar or fuel-facility project designed in 2026 should default to F3 unless the owner or AHJ holds a documented waiver.
NOTE The market is in the middle of a regulatory transition away from per- and polyfluoroalkyl substances (PFAS). Multiple states - including California, Washington, and Minnesota among others - prohibit new aqueous film-forming foam (AFFF) installations as of the 2024-2026 window, and the FAA Reauthorization Act of 2024 and the DoD AFFF phase-out (extended to September 30, 2025 for fixed systems) drive replacement toward fluorine-free foam (F3). Specifying AFFF without confirming local PFAS restrictions is the most common and most expensive error in current foam design, because the concentrate may be banned by the time the project is permitted. (3.3)
3.4The Contractor shall not substitute one concentrate family for another after award without written approval and a documented compatibility evaluation.
NOTE AFFF, alcohol-resistant AFFF (AR-AFFF), fluoroprotein (FP), and fluorine-free foam (F3) are chemically distinct and are not interchangeable. Mixing incompatible concentrates, or charging a system with a concentrate other than the one the proportioner and discharge devices were sized for, can degrade foam quality below the listing threshold. A concentrate change requires re-verifying proportioner ratio, storage volume, and discharge-device aspiration. (3.5)
3.6Fluorine-free foam shall not be substituted on a one-for-one basis for AFFF without confirming application rate against manufacturer fire-test data.
NOTE F3 foams (also marketed as Synthetic Fluorine-Free Foam, SFFF, or FFF) can exhibit lower burn-back resistance than AFFF on some hydrocarbon hazards, and manufacturer data frequently calls for application rates increased 10-25% over the AFFF baseline. A 1:1 substitution that keeps the AFFF design density can leave the hazard under-protected. (3.7)
3.8PFAS-compliant fluorine-free concentrate shall contain no intentionally added PFAS.
3.9PFAS-compliant fluorine-free concentrate shall not exceed 1 ppb total PFAS per the F3 benchmark of MIL-PRF-24385F (Rev F).
Foam Concentrate Typeradio
Fluorine-free foam (F3 / SFFF), PFAS-compliant
AFFF (aqueous film-forming foam)
AR-AFFF (alcohol-resistant AFFF)
Fluoroprotein (FP)
Alcohol-resistant fluoroprotein (ARFP)
Concentrate Proportioning Percentageradio
1%
3%
6%
Hazard Class Driving Concentrate Selectionradio
Hydrocarbon (non-polar fuels)
Polar solvent / alcohol (water-miscible fuels)

4 Submittals

4.1The Contractor shall submit the following Action Submittals for review before fabrication or installation:
  • Foam system shop drawings showing piping, proportioner location, discharge-device layout, and hydraulic node references.
  • Hydraulic calculations demonstrating the design application rate, flow, and pressure at the most remote and most demanding discharge devices.
  • Foam concentrate product data and UL 162 listing for the proposed concentrate, including expansion ratio and 25% drainage time.
  • Proportioner product data, listing, and accuracy data across the design flow range.
  • Discharge-device (foam maker, generator, sprinkler, spray nozzle, monitor) product data and listings.
  • Concentrate-storage tank data, including material, working pressure, and temperature limits.
Action Submittalscheckbox
Foam system shop drawings
Hydraulic calculations
Foam concentrate product data and UL 162 listing
Proportioner product data and accuracy data
Discharge-device product data and listings
Concentrate-storage tank data
4.2The Contractor shall submit the following Informational Submittals:
  • Concentrate compatibility statement confirming the concentrate is approved by the proportioner and discharge-device manufacturers.
  • PFAS compliance documentation for fluorine-free concentrates, including no-intentionally-added-PFAS certification and test data.
  • FAA approval documentation for foam systems at FAA-regulated airports and hangars, where applicable.
  • Detection and actuation coordination matrix identifying the division of work between the foam installer and the fire alarm contractor.
Informational Submittalscheckbox
Concentrate compatibility statement
PFAS compliance documentation (F3)
FAA approval documentation (where applicable)
Detection and actuation coordination matrix
4.3The Contractor shall submit the following Closeout Submittals before final acceptance:
  • Acceptance test records, including foam quality (expansion ratio and 25% drainage time) and proportioning accuracy at minimum, design, and maximum flow.
  • As-built drawings reflecting the installed system.
  • Operation and maintenance manuals and a recommended inspection, testing, and maintenance schedule.
  • Manufacturer certification of the installed concentrate batch, lot number, and shelf life.
Closeout Submittalscheckbox
Acceptance test records
As-built drawings
Operation and maintenance manuals
Concentrate batch / lot certification

5 Quality Assurance

5.1The installing contractor shall be experienced in the design and installation of foam fire suppression systems.
5.2The installing contractor shall hold any licensing required by the AHJ.
5.3Foam concentrate, proportioners, foam makers, generators, sprinklers, and spray nozzles shall be listed to UL 162 for the intended service and concentrate.
NOTE UL 162 is the listing basis for foam equipment and concentrates and defines the foam-quality tests - expansion ratio and 25% drainage time - that determine whether a discharge device produces an acceptable foam blanket. Components not listed together as a system are not a system. (5.4)
5.5Deluge valves used as the releasing device in foam-water systems shall be listed to UL 260.
5.6For foam systems serving FAA-regulated airports and hangars, the design shall be approved by the FAA per AC 150/5210-6E before an AHJ permit is issued.
NOTE A frequent error is pursuing only the local building permit while overlooking that new or modified foam systems at airports require separate FAA approval. The two approvals are sequential, and missing the FAA step stalls the project at permit. (5.7)
5.8For aircraft hangars, the NFPA 409 group classification (Group I, II, III, or IV) shall be established before system type is selected.
NOTE The group classification governs whether the hangar uses a low-expansion foam-water system over the floor or a high-expansion total-flooding system, and it drives the structural and drainage coordination. Establishing the group late forces a system-type change that ripples through the entire design. (5.9)
NFPA 409 Aircraft Hangar Group (if applicable)select
Not an aircraft hangar
Group I
Group II
Group III
Group IV

6 Environmental and Service Conditions

6.1Foam concentrate shall be stored within the temperature range specified by the concentrate manufacturer, and freeze protection shall be provided where ambient conditions can fall below that range.
6.2F3 concentrate storage temperature limits shall be verified against the manufacturer's submittal data.
NOTE Most AFFF concentrates are rated for storage between 35°F and 120°F (2°C to 49°C); F3 concentrates vary by manufacturer. Concentrate stored outside its rated range can stratify or lose performance, and frozen concentrate is unusable. (6.3)
6.4Concentrate-wetted piping, tanks, and proportioner components shall be of materials compatible with the selected concentrate for the life of the system.
6.5Concentrate lines shall be stainless steel or another manufacturer-approved corrosion-resistant material.
NOTE Foam concentrate - AFFF in particular - is corrosive to ordinary carbon steel. Specifying standard carbon-steel concentrate piping is a recurring defect that leads to early failure. (6.6)
6.7Foam-contaminated firewater runoff shall be contained and managed in coordination with the civil engineer and the requirements of NFPA 30.
NOTE Discharged foam solution is regulated as hazardous waste in many jurisdictions and cannot be allowed to enter stormwater. The spill control and secondary containment required by NFPA 30 must be coordinated with the site drainage design before the system is approved. Failing to coordinate drainage and containment is a common cause of approval delay. (6.8)
Minimum Ambient Storage Temperaturerange
°F
-2060
Default: 35 °F
Concentrate-Wetted Piping Materialradio
Type 304 stainless steel
Type 316 stainless steel
CPVC (manufacturer-approved for concentrate)

7 System Type and Configuration

7.1The foam system type shall be selected to match the hazard geometry, fuel type, and governing code as established by the hazard analysis.
NOTE There is no universal foam system. A surface fire on an open spill is handled differently from a fire inside a fixed-roof tank, which is handled differently again from a fire in an enclosed hangar. The configuration below is the primary design fork, and it determines the discharge devices, the proportioner sizing, and the application rate tables that apply. (7.2)
Foam System Typeradio
Low-expansion surface application (storage tanks, spill areas)
Low-expansion subsurface injection (cone-roof tanks)
Medium-expansion (dike / berm protection)
High-expansion total flooding (enclosed spaces)
Foam-water sprinkler / spray (deluge)
7.3Foam expansion ratio shall fall within the band defined for the selected system type by NFPA 11.
NOTE NFPA 11 classifies foam by how much the finished foam expands relative to the foam solution: low expansion is less than 20:1, medium expansion is 20:1 to 200:1, and high expansion is 200:1 to 1,000:1. The expansion band follows from the system type and the discharge device; it is not independently selected. (7.4)
Foam Expansion Classradio
Low expansion (< 20:1)
Medium expansion (20:1 to 200:1)
High expansion (200:1 to 1000:1)
7.5The discharge device shall be matched to the selected system type and listed for use with the selected concentrate.
NOTE Foam makers apply low-expansion foam to tank surfaces, high-expansion generators flood enclosed volumes, foam-water sprinklers and open spray nozzles cover deluge areas, and monitors or cannons project foam across open-air fuel-handling areas. Each device aspirates and expands the foam differently, so the device, the concentrate, and the proportioner must be a listed match. (7.6)
Primary Discharge Deviceradio
Foam-water sprinklers
Open spray nozzles
Foam makers (low-expansion tank application)
High-expansion foam generators
Monitors / cannons
Subsurface foam injection

8 Proportioning

8.1The proportioning method shall be selected for the system's flow range and shall maintain proportioning accuracy across the full range of expected operating flows.
NOTE The proportioner injects concentrate into the water stream at the design ratio. The available methods - inline balanced-pressure, bladder-tank, around-the-pump, variable-flow balanced-pressure, and premixed storage - differ in how they hold ratio as flow changes. A balanced-pressure proportioner sized for a large flow will not hold ratio when only a fraction of the deluge heads operate, so the full flow-range analysis, not just the peak flow, governs the selection. (8.2)
8.3The proportioning system shall deliver concentrate within ±30% of the nominal proportioning percentage at all design flows, per NFPA 11.
NOTE For a 3% system this means the delivered concentration shall remain between 2.1% and 3.9% across minimum, design, and maximum flow. A proportioner that meets accuracy only at peak flow but starves the foam at low flow does not satisfy this requirement. (8.4)
8.5Concentrate storage volume shall be sized for the design proportioning percentage and the full minimum application time, with no credit for a lower percentage.
NOTE Under-sizing concentrate storage is a frequent and costly RFI: storage volume calculated at 1% when the system is designed at 3% leaves only a third of the required concentrate. Size the bladder tank or concentrate tank for the design percentage multiplied by the design solution flow and the full required application time, plus the manufacturer's reserve. (8.6)
Proportioning Methodradio
Bladder-tank proportioner
Inline balanced-pressure proportioner
Variable-flow balanced-pressure proportioner
Around-the-pump proportioner
Premixed storage
Proportioner Working Pressure Rangerange
psi
30175
30175
Default: 175 psi
Concentrate Storage Typeradio
Stainless steel bladder tank
Polyethylene atmospheric concentrate tank
In-line stored concentrate

9 Application Rates and Duration

9.1The design application rate (density) and minimum application time shall be taken from the governing NFPA table for the hazard class and system type, and shall not be reduced below those minimums.
NOTE Application rate is the heart of foam design. For low-expansion surface application on hydrocarbons, NFPA 11 Table 5.3.3.1 sets a minimum of 0.10 gpm/ft²; most designs land between 0.10 and 0.16 gpm/ft² depending on hazard category. Foam-water sprinkler systems under NFPA 16 use a minimum of 0.16 gpm/ft² over the design area. High-expansion total flooding for aircraft hangars is sized by floor-area fill rate per NFPA 409 Table 5.2.1, typically 1.0 to 2.0 cfm/ft² at a 10:1 expansion ratio. The values below are the common design cases; the governing table for the actual hazard always controls. (9.2)
9.3Minimum application time shall match the hazard, from 10 minutes for a loading-rack deluge to as much as 65 minutes for certain storage-tank hazards under NFPA 11 Chapter 5.
NOTE The application rate and the application time together fix the concentrate storage volume. Selecting the rate without the matching time, or vice versa, produces a storage tank that is too small for the design event. (9.4)
9.5For NFPA 409 Group I hangars, low-expansion foam shall be applied at not less than 0.16 gpm/ft² over the entire floor area plus the approach, unless the AHJ approves an alternative.
NOTE Group III and IV hangars are typically protected by high-expansion generators sized for a one-foot-per-minute fill rate or as approved by the AHJ. The group classification, established earlier in Quality Assurance, selects which of these rules applies. (9.6)
Design Application Rate (Low-Expansion / Foam-Water)range
gpm/ft²
0.10.3
0.10.160.2
Default: 0.16 gpm/ft²
High-Expansion Total-Flooding Rate (Hangars)range
cfm/ft²
0.52.5
12
Default: 1 cfm/ft²
Minimum Application Timerange
min
1065
103065
Default: 30 min

10 Detection and Actuation

10.1The detection and actuation arrangement shall be selected for the hazard and coordinated with the fire alarm system designer under NFPA 72.
NOTE Foam systems may actuate automatically on heat, flame, or gas detection, or by manual means only, and automatic releasing may be single-interlock or cross-zoned. The releasing devices interface with the fire alarm and detection system, and the division of work between the foam installer and the fire alarm contractor must be fixed in the coordination matrix. Leaving this interface ambiguous is a reliable generator of RFIs. (10.2)
10.3Automatic releasing systems for high-hazard occupancies should use cross-zoned (double-interlock) detection to reduce the risk of accidental discharge unless the hazard analysis requires single-interlock for faster response.
10.4A manual release station shall be provided at an accessible, identified location for every automatically actuated foam system.
Actuation Methodradio
Automatic - heat detection
Automatic - flame detection
Automatic - gas detection
Manual only
Automatic Releasing Interlockradio
Single-interlock
Cross-zoned (double-interlock)

11 Water Supply

11.1The water supply shall provide the flow and pressure required by the selected system at the proportioner inlet for the full minimum application time.
NOTE A foam system can share the site fire main or use a dedicated supply, but in either case the supply must satisfy the proportioner's inlet pressure requirement simultaneously with all other demands during the design event. Bladder-tank proportioners in particular impose an inlet-pressure requirement that a shared main may not meet under concurrent demand. Where a dedicated foam-system pump is required, it is sized and specified under Fire Pumps. (11.2)
11.3Where a foam-water system shares a deluge valve or releasing panel with a water-only system, that shared hardware shall comply with Pre Action And Deluge Sprinkler Systems.
Water Supply Arrangementradio
Shared site fire main
Dedicated foam-system supply
Dedicated Foam-System Fire Pump Requiredradio
No
Yes

12 Piping and Installation

12.1Foam solution piping shall be installed to drain after operation and shall be flushed of foam solution following any discharge or test.
NOTE Residual foam solution left standing in piping accelerates corrosion and can foul discharge devices. Provide drains at low points and a means to flush the system after each discharge. (12.2)
12.3Concentrate lines shall be kept separate from water-wetted piping and shall use only the concentrate-compatible materials specified in Environmental and Service Conditions.
12.4Discharge devices shall be located and oriented to develop and distribute the foam blanket over the entire protected area without shadowing by structure or equipment.
NOTE Foam relies on a continuous floating blanket; a discharge device aimed into a column, a duct, or stored equipment leaves an unprotected pocket. Coordinate device locations with the structural and equipment layout. Device locations, routing, and protected-area extents are shown on the drawings foam system layout. (12.5)
12.6Piping shall be supported, braced, and where required seismically restrained in accordance with the governing code and NFPA 13 hanger and bracing practice as adopted by the AHJ.

13 Testing

13.1The completed foam system shall be acceptance-tested in the presence of the AHJ before being placed in service.
NOTE Acceptance testing proves two independent things: that the proportioner delivers concentrate at the correct ratio, and that the discharge devices produce foam of acceptable quality. Both are required; a system that proportions correctly but produces poor foam, or produces good foam at the wrong ratio, fails. (13.2)
13.3Proportioning accuracy shall be verified at minimum, design, and maximum flow using conductivity or refractometry per NFPA 11 §13.4.
NOTE Testing at a single flow point does not demonstrate the ±30% accuracy required across the operating range. The three-point test catches proportioners that hold ratio at design flow but drift at the extremes. (13.4)
13.5Foam quality shall be verified by measuring expansion ratio and 25% drainage time at each discharge-device type per NFPA 11 §13.5 and UL 162.
13.6For low-expansion foam at rated concentration, the 25% drainage time shall be not less than 4 minutes.
NOTE A 25% drainage time faster than 4 minutes indicates a thin, unstable blanket that will not hold the vapor down. (13.7)
13.8Flow, pressure, and discharge-pattern tests shall be performed to confirm that the design application rate is achieved over the protected area.
Acceptance Testscheckbox
Proportioning accuracy at min / design / max flow
Foam expansion ratio at each device type
25% drainage time at each device type
Flow and pressure test
Discharge-pattern / coverage test
Detection and actuation functional test
Minimum 25% Drainage Time (Low-Expansion)range
min
210
Default: 4 min

14 Delivery, Storage, and Handling

14.1Foam concentrate shall be delivered in its original sealed containers, marked with manufacturer, concentrate type, proportioning percentage, batch or lot number, and shelf-life expiration date.
14.2Concentrate shall be stored within its rated temperature range and protected from freezing, direct sunlight, and contamination until installed.
14.3Proportioner components, bladder tanks, and discharge devices shall be stored under cover and protected from corrosion, contamination, and physical damage until installation.
14.4Concentrate that has exceeded its shelf life or been stored outside its rated temperature range shall not be installed without manufacturer re-certification.

15 Warranty

15.1The Contractor shall warrant the complete foam system against defects in materials and workmanship for a period of not less than one year from the date of Substantial Completion.

16 Spare Parts

16.1The Contractor shall furnish spare foam concentrate sufficient to fully recharge the system to its design minimum application time after a single design discharge.
NOTE A foam system that has discharged is out of service until it is recharged. Providing a full recharge volume of the installed concentrate type and percentage returns the system to service without waiting on a concentrate order. (16.2)
Spare Concentrate Recharge Quantityradio
One full design-discharge recharge
Two full design-discharge recharges

Edit this page